Service time: Monday to Friday 9:00-18:00
ELR H5-ES-SC-24DC/500AC-9 - ELR H5-ES-SC- 24DC/500AC-9 2900561 PHOENIX CONTACT Hybrid motor starter
In Stock Hot Product

ELR H5-ES-SC-24DC/500AC-9

ELR H5-ES-SC- 24DC/500AC-9 2900561 PHOENIX CONTACT Hybrid motor starter

$0.00USD
4192 in stock
Key Specifications
GTIN:4046356527842
Orderkey:2900561
(UL data):Safe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC
Catalog page:Page 179 (IF-2011)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
GTIN4046356527842
Orderkey2900561
(UL data)Safe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC
Catalog pagePage 179 (IF-2011)
Packing unit1 pc
(Input data)6.5 A (AC-53a)
(Device supply)19.2 V (“1” signal)
Torque (General)0.5 Nm ... 0.6 Nm
Country of originDE (Germany)
(Connection data 2)30 A (class CC or J, SCCR 100kA, #24 - 14 AWG max, solid and stranded)
Custom tariff number85371098
Insulation (UL data)Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
(Ambient conditions)Reverse polarity protection
Designation (UL data)Isolation characteristics between the control input and control supply voltage to auxiliary circuit
Screw thread (General)M3
FLA (Connection data 2)6.5 A (500 V AC)
Output name (Input data)AC output
SCCR (Connection data 2)100 kA (500 V AC (fuse: 30 A class CC/30 A class J (high fault)))
(Approvals/conformities)For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Connection name (General)Control circuits
Cooling time (Input data)20 min. (for auto reset)
(Output data load output)2 A (24 V, DC13)
Input name (Device supply)Control input right/left
Stripping length (General)8 mm
Torque (Connection data 1)0.5 Nm ... 0.6 Nm
Connection method (General)Screw connection
Depth (Key Commercial Data)113.7 mm
Width (Key Commercial Data)22.5 mm
(Standards and Regulations) II (2) D [Ex t] [Ex p]
Height (Key Commercial Data)106.6 mm
Leakage current (Input data)0 mA
Mains frequency (Input data)50/60 Hz
(Insulation characteristics) II (2) D [Ex t] [Ex p]
Degree of pollution (UL data)2
Rated surge voltage (UL data)6 kV
Note (Output data load output)Confirmation: floating change-over contact, signal contact
Overvoltage category (UL data)III
Indication (Overspeed tripping)Red LED
Load current range (Input data)1.5 A ... 9 A (see to derating)
Switching level (Device supply)< 5 V DC (For EMERGENCY STOP)
Type of protection (Input data)Surge protection
ATEX (Standards and Regulations) II (2) G [Ex e] [Ex d] [Ex px]
Screw thread (Connection data 1)M3
ATEX (Insulation characteristics) II (2) G [Ex e] [Ex d] [Ex px]
Category code (Connection data 2)NLDX / NRNT
Degree of protection (Dimensions)IP20
Mounting type (Overspeed tripping)DIN rail mounting
Rated insulation voltage (UL data)500 V
Type of protection (Device supply)Reverse polarity protection
China RoHS (Approvals/conformities)Environmentally Friendly Use Period = 50
Connection name (Connection data 1)Load circuit
Operating mode (Overspeed tripping)100% operating factor
Status display (Overspeed tripping)Yellow LED
Switching threshold (Device supply)9.6 V (“0” signal)
Operating voltage range (Input data)42 V AC ... 550 V AC
Stripping length (Connection data 1)8 mm
Weight per Piece (excluding packing)217.180 g
Conductor cross section AWG (General)24 ... 14
Connection method (Connection data 1)Screw connection
Output name (Output data load output)Acknowledge output
Typical turn-off time (Device supply)< 30 ms
Contact type (Output data load output)1 PDT
Group installation (Connection data 2)20 A (class RK5, SCCR 5kA, #24 - 14 AWG max. solid and stranded)
Mounting position (Overspeed tripping)vertical (horizontal DIN rail, motor output below)
Conductor cross section solid (General)0.2 mm² ... 2.5 mm²
Rated operating current Ie (Input data)9 A (AC-51)
Rated operating voltage Ue (Input data)500 V AC
Type of protection (Ambient conditions)Surge protection
Designation (Insulation characteristics)Standards/regulations
Response time (Output data reply output)< 2 s
Switching frequency (Overspeed tripping)≤ 2 Hz (Load-dependent)
Triggering voltage range (Device supply)19.2 V DC ... 30 V DC
Assembly instructions (Overspeed tripping)alignable, for spacing see derating
Conductor cross section flexible (General)0.2 mm² ... 2.5 mm²
Rated actuating current IC (Device supply)5 mA
Rated actuating voltage UC (Device supply)24 V DC
UL certificate (Standards and Regulations)NLDX.E228652
Ambient temperature (operation) (Dimensions)-25 °C ... 70 °C (observe derating)
Operate threshold (Output data reply output)> 45 A
Maximum power dissipation (Overspeed tripping)14.6 W
Minimum power dissipation (Overspeed tripping)1.1 W
Operating voltage display (Overspeed tripping)Green LED
Conductor cross section AWG (Connection data 1)24 ... 14
Conductor cross section solid (Connection data 1)0.2 mm² ... 2.5 mm²
Control supply voltage range (Ambient conditions)19.2 V DC ... 30 V DC
Standards/regulations (Insulation characteristics)IEC 60947-1
Ambient temperature (storage/transport) (Dimensions)-40 °C ... 80 °C
Conductor cross section flexible (Connection data 1)0.2 mm² ... 2.5 mm²
Rated control supply current IS (Ambient conditions)40 mA
Category acc. to EN ISO 13849 (Standards and Regulations)≤ 3 (Safe shutdown)
EU-type examination certificate (Standards and Regulations)PTB 07 ATEX 3145
Rated control circuit supply voltage US (Ambient conditions)24 V DC
Trigger characteristic in acc. with IEC 60947-4-2 (Input data)Class 10A
Performance level according to ISO 13849 (Standards and Regulations)≤ e (Safe shutdown)
Switching capacity according to IEC 60947-5-1 (Output data load output)3 A (230 V, AC15)
Safety Integrity Level according to IEC 61508 (Standards and Regulations)≤ 3 (Safe shutdown)

Product Description

Hybrid start controller for reversing motors from 3~ AC up to 550 V AC, with 24 V DC input, 9 A output current and emergency stop function.
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top