Key Specifications
:Safe isolation (EN 50178) at operating voltage ≤ 300 V AC
FLA:2.4 A (500 V AC)
Note:Confirmation: floating change-over contact, signal contact
SCCR:100 kA (500 V AC (fuse: 30 A class CC/30 A class J (high fault)))
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
Safe isolation (EN 50178) at operating voltage ≤ 300 V AC
FLA2.4 A (500 V AC)
NoteConfirmation: floating change-over contact, signal contact
SCCR100 kA (500 V AC (fuse: 30 A class CC/30 A class J (high fault)))
Depth114 mm
Width22.5 mm
Height107 mm
Altitude≤ 2000 m
Input nameControl input
CertificateNLDX.E228652
Cooling time20 min. (for auto reset)
Product typeHybrid motor starters
Screw threadM3
Assembly notealignable, for spacing see derating
Category codeNLDX / NRNT
Mounting typeDIN rail mounting
Operating mode100% operating factor
Product familyCONTACTRON
Status displayLED (yellow)
Leakage current0 mA
Mains frequency50/60 Hz
Article revision09
Error indicationRed LED
Number of phases3
Stripping length8 mm
Connection methodScrew connection
Coordination type1
Mounting positionvertical (horizontal DIN rail, motor output below)
Tightening torque0.5 Nm ... 0.6 Nm
Group installation20 A (class RK5, SCCR 5kA, #24 - 14 AWG max. solid and stranded)
Load current range180 mA ... 2.4 A (see to derating)
Motor starter typeDirect starter
Protective circuitSurge protection
Degree of pollution2
Rated surge voltage4 kV
Switching frequency≤ 2 Hz (Load-dependent)
Switching threshold44 V AC (“0” signal)
Degree of protectionIP20
Overvoltage categoryIII
Standards/regulationsIEC 60947-1
Typical turn-off time< 70 ms
Contact switching type1 changeover contact
Operating voltage range42 V AC ... 550 V AC
Rated insulation voltage500 V
Triggering voltage range85 V AC ... 253 V AC
Maximum power dissipation4.7 W
Minimum power dissipation2.6 W
Operating voltage displayGreen LED
Rated actuating current IC7 mA (Input type 1)
Rated actuating voltage UC230 V AC
Rated operating current Ie2.4 A (AC-51)
Rated operating voltage Ue500 V AC
Conductor cross section AWG24 ... 14
Control supply voltage range85 V AC ... 253 V AC
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Ambient temperature (operation)-25 °C ... 70 °C (observe derating)
Rated control supply current IS4 mA
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Flammability rating according to UL 94V0 (Housing)
Ambient temperature (storage/transport)-40 °C ... 80 °C
Rated control circuit supply voltage US230 V AC
Maximum power dissipation for nominal condition2.2 W
Trigger characteristic in acc. with IEC 60947-4-2Class 10A
Switching capacity in accordance with IEC 60947-5-13 A (230 V, AC15)
Isolation characteristics between the control input and control supply voltage to auxiliary circuitSafe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuitSafe isolation (IEC 60947-1) at operating voltage ≤ 300 V AC

Product Description

Hybrid start controller for starting motors from 3~ AC up to 550 V AC, with 230 V DC input, 2.4 A output current and adjustable overload disconnection.
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty