| Parameter | Value |
|---|---|
| 2, 3, 4-wire | |
| Note | Notes on operation Line protection for the power cable, maximum 25 A. Observe derating of the POWER COMBICON connector |
| Depth | 139 mm |
| Width | 384 mm |
| Height | 182 mm |
| Number | 1 |
| Ripple | Permissible ripple 3.6 Vppwithin the permissible voltage range |
| Input name | Digital inputs |
| Net weight | 3500 g |
| Designation | Terminal strip X13 |
| Filter time | 3 ms |
| Output name | Digital outputs |
| Input voltage | 24 V DC (US1) |
| Mounting type | Wall mounting |
| Output current | max. 500 mA (per channel) |
| Supply current | typ. 0.25 A (at US1= 24 V; plus current of digital inputs/outputs) |
| Supply voltage | 24 V DC (US1/ US2) |
| Switching rate | 5 cycles per minute, maximum |
| Fieldbus system | PROFINET |
| Frequency range | 50 Hz ... 60 Hz (mains frequency) |
| Number of inputs | 10 |
| Parameterization | via PROFINET |
| Connection method | 8-pos. RJ45 socket on motor starter |
| Number of outputs | 4 |
| Operating voltage | 360 V AC ... 550 V AC (line voltage 50/60 Hz) |
| Drill hole spacing | 360 mm |
| Note on dimensions | Module electronics without lower part |
| Type of protection | Electronic short-circuit/overload protection, damping diode |
| Number of positions | 8 |
| Pg screw connection | Pg11 |
| Degree of protection | IP67 in acc. with IEC 60529 |
| Supply voltage range | 20 V DC ... 30 V DC (including ripple) |
| Utilization category | On the basis of AC 3 |
| Nominal current range | 2.4 A ... 6 A |
| Parameterization range | 2.4 A ... 6 A |
| Air pressure (operation) | 86 kPa ... 106 kPa (up to 2000 m above mean sea level) |
| Power supply for sensors | UINI= US1minus 1 V 500 mA Short-circuit/overload protection |
| Designation connection point | X30 and X31 |
| Note on weight specifications | Module electronics without lower part |
| Input voltage range "0" signal | -3 V DC ... 5 V (binary "0") |
| Input voltage range "1" signal | 15 V DC ... 30 V DC (binary "1") |
| Max. current carrying capacity | 10 A |
| Ambient temperature (operation) | -25 °C ... 50 °C (non-condensing) |
| Air pressure (storage/transport) | 86 kPa ... 106 kPa (up to 2000 m above mean sea level) |
| Permissible humidity (operation) | 0 % ... 85 % (non-condensing) |
| Typical input current per channel | approx. 3 mA (for US1= 24 V) |
| Permissible conductor cross section | max. 0.14 mm² ... 0.22 mm² |
| Ambient temperature (storage/transport) | -25 °C ... 70 °C (non-condensing) |
| Permissible humidity (storage/transport) | 75 % (slight temporary condensation may sometimes appear on the housing) |
| Minimum output voltage with nominal current | US2minus 1 V |
Technical specifications and performance data
Installation and operation guide