| Parameter | Value |
|---|---|
| 60 Hz | |
| FLA | 2 A (at 500 V, AC Resistance) |
| SCCR | 5 kA (20 A RK5 (standard fault) fuse) |
| Depth | 114.5 mm |
| Width | 40 mm |
| Height | 99 mm |
| Input name | Control input right/left |
| Certificate | NMFT.E323771 |
| Product type | Solid-state contactor |
| Screw thread | M3 |
| Assembly note | Can be aligned with spacing = 20 mm |
| Mounting type | DIN rail mounting |
| Surge current | 200 A (t = 10 ms) |
| Operating mode | 100% operating factor |
| Status display | LED (yellow) |
| Leakage current | 6 mA |
| Mains frequency | 50 Hz |
| Max. load value | 250 A2s |
| Article revision | 05 |
| Error indication | Red LED |
| Number of phases | 3 |
| Residual voltage | < 1.5 V |
| Stripping length | 8 mm |
| Connection method | Screw connection |
| Mounting position | Vertical (horizontal DIN rail) |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| Load current range | 100 mA ... 2 A (see to derating) |
| Protective circuit | Surge protection; Varistor |
| Degree of pollution | 2 |
| Rated surge voltage | 6 kV |
| Switching frequency | ≤ 1 Hz |
| Switching threshold | 48 V AC (“0” signal) |
| Degree of protection | IP20 |
| Overvoltage category | III |
| Peak offstate voltage | 1200 V |
| Standards/regulations | DIN EN 50178 |
| Operating voltage range | 48 V AC ... 575 V AC |
| Rated insulation voltage | 500 V |
| Surge voltage protection | > 575 V AC |
| Triggering voltage range | 92 V AC ... 253 V AC |
| Rated actuating current IC | 12.5 mA |
| Rated actuating voltage UC | 230 V AC |
| Rated operating voltage Ue | 500 V AC |
| Conductor cross section AWG | 24 ... 14 |
| Test voltage (Input/output) | 5 kVrms(50 Hz, 60 s) |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Ambient temperature (operation) | -25 °C ... 70 °C |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Rated operating current at AC-51 | 2 A |
| Rated operating current at AC-53a | 2 A |
| Voltage range with reference to UC | 0.4 ... 1.1 |
| Ambient temperature (storage/transport) | -25 °C ... 70 °C |
| Insulation characteristics between the control input voltage to the main circuit | Basic insulation |
Technical specifications and performance data