| Parameter | Value |
|---|---|
| GTIN | 4055626536897 |
| Orderkey | 1032926 |
| (Drawings) | |
| Catalog page | Page 49 (C-5-2019) |
| Packing unit | 1 pc |
| (Input data) | 16 A (TA= 40 °C) |
| Depth (Drawings) | 141 mm |
| Width (Drawings) | 35 mm |
| Country of origin | MT (Malta) |
| ETIM 5.0 (eCl@ss) | EC002055 |
| ETIM 6.0 (eCl@ss) | EC002055 |
| ETIM 7.0 (eCl@ss) | EC002055 |
| Height (Drawings) | 110 mm |
| (Connection data 2) | EN 55011 |
| Custom tariff number | 85362010 |
| (Ambient conditions) | ≥ 4 V DC (“1” signal) |
| Screw thread (General) | M3 |
| Output name (Input data) | Load output |
| Connection name (General) | Control circuits |
| Stripping length (General) | 8 mm |
| Surge current (Input data) | 1900 A (t = 10 ms) |
| Connection method (General) | Screw connection |
| Leakage current (Input data) | < 3 mA (In off state) |
| eCl@ss 6.0 (Classifications) | 27371000 |
| eCl@ss 7.0 (Classifications) | 27371014 |
| eCl@ss 8.0 (Classifications) | 27371014 |
| eCl@ss 9.0 (Classifications) | 27371014 |
| Residual voltage (Input data) | < 1 V |
| Screw thread (Connection data) | M4 |
| Designation (Connection data 2) | Standards/regulations |
| Input name (Ambient conditions) | Control input |
| Load current range (Input data) | 500 mA ... 50 A (see to derating) |
| Type of protection (Input data) | Varistor |
| Connection name (Connection data) | Load circuit |
| Stripping length (Connection data) | 12 mm |
| Connection method (Connection data) | Screw connection |
| Operating voltage range (Input data) | 42 V AC ... 660 V AC |
| Weight per Piece (excluding packing) | 520.000 g |
| Conductor cross section AWG (General) | 18 ... 12 |
| Conductor cross section solid (General) | 0.5 mm² ... 2.5 mm² |
| Switching threshold (Ambient conditions) | ≤ 1 V DC (“0” signal) |
| Standards/regulations (Connection data 2) | EN 61000-4-2 |
| Conductor cross section flexible (General) | 0.5 mm² ... 2.5 mm² |
| Mounting position (Output data load output) | Vertical (horizontal DIN rail) |
| Transmission frequency (Ambient conditions) | 25 Hz |
| Ambient temperature (operation) (Dimensions) | -30 °C ... 70 °C |
| Conductor cross section AWG (Connection data) | 14 ... 10 |
| Rated operating current at AC-51 (Input data) | 50 A |
| Triggering voltage range (Ambient conditions) | 4 V DC ... 32 V DC |
| Operating voltage display (Ambient conditions) | Green LED |
| Rated operating current at AC-53a (Input data) | 30 A (TA= 25 °C) |
| Assembly instructions (Output data load output) | Can be aligned with ≥ 22.5 mm spacing |
| Conductor cross section solid (Connection data) | 2.5 mm² ... 6 mm² |
| Rated actuating current IC (Ambient conditions) | approx. 12 mA |
| Rated actuating voltage UC (Ambient conditions) | 24 V DC |
| Conductor cross section flexible (Connection data) | 1 mm² ... 4 mm² |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 80 °C |
Technical specifications and performance data