| Parameter | Value |
|---|---|
| See extension module | |
| Note | Voltage and other connections |
| Color | black (RAL 9005) |
| Depth | 82 mm |
| Width | 96 mm |
| Height | 96 mm |
| Altitude | ≤ 2000 m |
| Precision | 0.2 % |
| Input name | Voltage measuring input V1, V2, V3 |
| Mains type | 3-phase (3 or 4-conductor), 2-phase (2-conductor), and single-phase (1-conductor) |
| Certificate | CE-compliant |
| Product type | Energy measuring device |
| Test voltage | 3.5 kV AC (50 Hz, 1 min.) |
| Input current | 9999 A (primary) |
| Input voltage | 500 kV AC (Primary, via external voltage transducers) |
| Measured value | AC sine (50 Hz/60 Hz) |
| Operating mode | Indoor use |
| Supply voltage | 24 V DC |
| Surge voltages | transient overvoltage according to installation classes |
| Measuring range | 0 A ... 9999 A |
| Article revision | 01 |
| Current overload | 10 x INfor 1 s |
| Pollution degree | 2 |
| Stripping length | 6 mm |
| Connection method | COMBICON plug-in screw terminal block |
| Mounting position | Front panel installation, horizontal |
| Overload capacity | 6 A (Permanent) |
| Power consumption | 20 VA (with max. number of extension modules) |
| Tightening torque | 0.4 Nm ... 0.4 Nm |
| Output description | via extension module |
| Input current range | via external transformers |
| Input voltage range | 18 V AC ... 700 V AC (Phase/Phase) |
| Measuring principle | True r.m.s. value measurement |
| Degree of protection | IP52 (Front) |
| Electrical isolation | EN 61010-1 (Safe isolation) |
| Messbereich_Leistung | 0 MW ... 8000 MW |
| Overvoltage category | III (For mains voltage <300 V AC (L/N)) |
| Supply voltage range | 12 V DC ... 48 V DC -6 % ... +20 % |
| Voltage input signal | Via extension module |
| Max. salt spray content | ≤ 2.5 % |
| Acquisition of harmonics | up to 63rd harmonic |
| Nominal power consumption | 10 VA |
| Conductor cross section AWG | 20 ... 14 |
| Active energy (IEC 62053-22) | Class 0.5 S |
| Nominal supply voltage range | 12 V DC ... 48 V DC -6 % ... +20 % |
| Conductor cross section rigid | 0.5 mm² ... 2.5 mm² |
| Reactive power (IEC 62053-23) | Class 2 |
| Ambient temperature (operation) | -10 °C ... 55 °C (14 °F ... 131 °F) |
| Conductor cross section flexible | 0.5 mm² ... 2.5 mm² |
| Overvoltage category of the supply | Min. II |
| Ambient temperature (storage/transport) | -20 °C ... 85 °C (-4 °F ... 185 °F) |
| Max. permissible relative humidity (operation) | ≤ 95 % |
| Response threshold from measuring range nominal value | 10 mA |
Technical specifications and performance data
Installation and operation guide