| Parameter | Value |
|---|---|
| 2.5 mm² / 0.7 kg | |
| Note | Please observe the current carrying capacity of the DIN rails. |
| Color | gray (RAL 7042) |
| Width | 6.2 mm |
| Height | 83.5 mm |
| Result | Test passed |
| Potentials | 4 |
| Revolutions | 135 |
| Product type | Motor terminal block |
| Screw thread | M3 |
| Mounting type | NS 35/7,5 |
| Grounding foot | Yes |
| Number of rows | 4 |
| Rotation speed | 10 rpm |
| Nominal current | 19 A |
| Nominal voltage | 400 V (when using EB insertion bridges, the nominal voltage is reduced to 250 V.) |
| Open side panel | No |
| Article revision | 08 |
| Stripping length | 8 mm |
| Time of exposure | 30 s |
| Cross section AWG | 24 ... 12 (converted acc. to IEC) |
| Tightening torque | 0.5 ... 0.6 Nm |
| Depth on NS 35/15 | 77.5 mm |
| Degree of pollution | 3 |
| Depth on NS 35/7,5 | 70 mm |
| Insulating material | PA |
| Rated surge voltage | 6 kV |
| Test force setpoint | 1 N |
| Maximum load current | 24 A (with 4 mm² conductor cross section) |
| Overvoltage category | III |
| Nominal cross section | 2.5 mm² |
| Number of connections | 7 |
| Test voltage setpoint | 7.3 kV |
| DIN rail/fixing support | NS 35 |
| Insulating material group | I |
| Internal cylindrical gage | A3 |
| Conductor cross section rigid | 0.2 mm² ... 4 mm² |
| Ambient temperature (assembly) | -5 °C ... 70 °C |
| Conductor cross section/weight | 0.2 mm² / 0.2 kg |
| Ambient temperature (actuation) | -5 °C ... 70 °C |
| Ambient temperature (operation) | -60 °C ... 110 °C (Operating temperature range incl. self-heating; for max. short-term operating temperature, see RTI Elec.) |
| Number of connections per level | 2 |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Connection in acc. with standard | IEC 60947-7-1/IEC 60947-7-2 |
| Permissible humidity (operation) | 20 % ... 90 % |
| Requirement temperature-rise test | Increase in temperature ≤ 45 K |
| Short-time withstand current 4 mm² | 0.48 kA |
| Short-time withstand current 2.5 mm² | 0.3 kA |
| Flammability rating according to UL 94 | V0 |
| Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
| Ambient temperature (storage/transport) | -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C) |
| Conductor cross section, flexible [AWG] | 24 ... 14 (converted acc. to IEC) |
| Permissible humidity (storage/transport) | 30 % ... 70 % |
| Cross-section with insertion bridge, rigid | 4 mm² |
| Surface flammability NFPA 130 (ASTM E 162) | passed |
| Cross-section with insertion bridge, flexible | 2.5 mm² |
| Static insulating material application in cold | -60 °C |
| Maximum power dissipation for nominal condition | 0.77 W |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
| Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
| Flexible conductor cross section (ferrule with plastic sleeve) | 0.25 mm² ... 2.5 mm² |
| Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
| Conductor cross-section flexible (ferrule without plastic sleeve) | 0.25 mm² ... 2.5 mm² |
Technical specifications and performance data