| Parameter | Value |
|---|---|
| GTIN | 4017918176068 |
| Orderkey | 2964319 |
| Catalog page | Page 453 (C-5-2017) |
| Packing unit | 10 pc |
| Country of origin | CN (China) |
| Custom tariff number | 85364190 |
| Note (Ambient conditions) | Use of EB 80-DIK... bridges in the DEK terminal blocks: Absorption of humidity from the ambient air as well as an unfavorable tolerance between a larger number of DEK terminal blocks and the EB 80-DIK... bridge may cause (minor) expansion of the DEK housing. When the EB 80-DIK... bridges are used, therefore, it is recommended that these be disconnected after about 10 to 12 DEK terminal blocks and a wire bridge to the next DEK terminal block be inserted in their place. |
| Depth (Key Commercial Data) | 56 mm |
| Max. limit values (General) | 26 V (at UV= 24 V; UV+ 2 V) |
| Min. limit values (General) | -2 V |
| Width (Key Commercial Data) | 6.2 mm |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Height (Key Commercial Data) | 80 mm |
| Leakage current (Dimensions) | < 1 mA |
| Switch-on threshold (General) | < 5 V (at UV= 24 V; < (UV- 19 V)) |
| Switch-off threshold (General) | > 15 V (at UV= 24 V; > (UV- 9 V)) |
| Continuous current (Dimensions) | 200 mA |
| Standards/regulations (General) | IEC 60664 |
| Supply voltage range (Dimensions) | 20 V DC ... 30 V DC (UV) |
| Type of note (Ambient conditions) | Note on application |
| Residual voltage drop (Dimensions) | < 1 V |
| Screw thread (PNP input/NPN output) | M3 |
| Weight per Piece (excluding packing) | 19.900 g |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Stripping length (PNP input/NPN output) | 8 mm |
| Connection method (PNP input/NPN output) | Screw connection |
| Max. limit values (NPN input/PNP output) | 26 V (at UV= 24 V; UV+ 2 V) |
| Max. transmission frequency (Dimensions) | 15 kHz |
| Min. limit values (NPN input/PNP output) | -2 V |
| Connection in acc. with standard (General) | CUL |
| Switch-on threshold (NPN input/PNP output) | > 19 V |
| Switch-off threshold (NPN input/PNP output) | < 9 V |
| Ambient temperature (operation) (Connection data) | -20 °C ... 50 °C |
| Conductor cross section AWG max. (PNP input/NPN output) | 12 |
| Conductor cross section AWG min. (PNP input/NPN output) | 24 |
| Ambient temperature (storage/transport) (Connection data) | -20 °C ... 70 °C |
| Conductor cross section solid max. (PNP input/NPN output) | 4 mm² |
| Conductor cross section solid min. (PNP input/NPN output) | 0.2 mm² |
| Conductor cross section flexible max. (PNP input/NPN output) | 2.5 mm² |
| Conductor cross section flexible min. (PNP input/NPN output) | 0.2 mm² |
Technical specifications and performance data