| Parameter | Value |
|---|---|
| GTIN | 4046356450805 |
| Note | Made to Order (non-returnable) |
| (Cable) | NFDV551 |
| Orderkey | 2322773 |
| Catalog page | Page 517 (C-5-2017) |
| Packing unit | 1 pc |
| Torque (General) | 0.5 Nm (Screw connection) |
| Country of origin | DE (Germany) |
| Controller (Cable) | YOKOGAWA STARDOM |
| Custom tariff number | 85444290 |
| Connection name (General) | Control side |
| Pitch (Connection data 1) | 2.54 mm |
| - suitable I/O card (Cable) | NFDV151 |
| Connection method (General) | Yokogawa, I/O cards compatible |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Number of positions (General) | 50 |
| Shielding (Connection data 2) | yes |
| Insulation (Connection data 2) | Semi-rigid PVC |
| Number of connections (General) | 1 |
| Cable capacity (Connection data 2) | approx. 130 pF/m |
| Cable impedance (Connection data 2) | approx. 120 Ω |
| Connection name (Connection data 1) | Field level |
| Length of cable (Connection data 2) | 15 m |
| Structural data (Connection data 2) | in acc. to UL style 2464/1061 |
| Cable resistance (Connection data 2) | approx. 155 Ω/km |
| Weight per Piece (excluding packing) | 2,858.900 g |
| Connection method (Connection data 1) | IDC/FLK socket strip |
| External diameter (Connection data 2) | 11 mm |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Halogen-free cable (Connection data 2) | No |
| Flame resistance (Supported controller) | IEC 60332-3-22 |
| Number of positions (Connection data 1) | 14 |
| Resistance to oil (Supported controller) | DIN VDE 0472 Part 803, test type B |
| Number of connections (Connection data 1) | 4 |
| External sheath, color (Connection data 2) | gray RAL 7035 |
| Gasoline resistance (Supported controller) | against occasional splashes |
| Outer sheath, material (Connection data 2) | PVC |
| Max. conductor resistance (Connection data 2) | 0.16 Ω/m |
| Max. permissible current (Ambient conditions) | 500 mA (per path at 70°C) |
| Single wire, cross section (Connection data 2) | 0.14 mm² |
| Cable insulation resistance (Connection data 2) | approx. 153 MΩ/km |
| Ambient temperature (operation) (Key Commercial Data) | -20 °C ... 50 °C |
| Max. permissible operating voltage (Ambient conditions) | 30 V DC |
| Ambient temperature (storage/transport) (Key Commercial Data) | -20 °C ... 70 °C |
| Conductor construction: Number of litz wires: (Connection data 2) | 7 |
Technical specifications and performance data