| Parameter | Value |
|---|---|
| 4 mA ... 20 mA | |
| Depth | 77.14 mm |
| Width | 53.6 mm |
| Colour | traffic grey A RAL 7042 |
| Height | 126.1 mm |
| Marked | II 3G Ex ec IIC T4 Gc |
| Certificate | DEMKO 20 ATEX 2334X |
| Construction | blockmodular |
| Product Type | I/O Component |
| EMC Indication | EMC: Class A product, see manufacturer's statement in the download center |
| Product Family | Axioline P |
| Supply voltage | 19.2 V DC ... 30 V DC (via bus socket module (UL) to AXL P BK...) |
| Surge Category | Ii |
| Connection type | Bus Socket Module |
| Dimension Scheme | |
| Protection Index | IP20 |
| Type of mounting | Rail mounting |
| UL, USA / Canada | Class I, Div. 2, Groups A, B, C, D T4Class I, Zone 2, IIC T4 |
| Number of Entries | 8 (HART) |
| Current absorption | max. 135 mA |
| Denomination Entry | Passive Analog Inputs |
| Kind of protection | III (IEC 61140, EN 61140, VDE 0140-1) |
| Protection Circuit | Prot. Departures against Inv. polarity |
| Ticket Description | Passive analog input signals, HART-ready |
| Transmission speed | 100 MBit/s |
| Degree of pollution | 2 |
| Input Signal Current | 0 mA ... 20 mA |
| AWG Conductor Section | 24 ... 16 |
| Connection technology | 2 conductors |
| Position for mounting | at discretion (no temperature derating) |
| Air Pressure (Service) | 70 kPa ... 106 kPa (up to 2000 m above NN) |
| Denomination Connection | Axioline P Connector |
| Rigid conductor section | 0.2 mm² ... 1.5 mm² |
| Length to be de-insulated | 8 mm |
| Flexible conductor section | 0.2 mm² ... 1.5 mm² |
| Ambient Temperature (Service) | -40 °C ... 70°C (Standard) |
| Note about the connection type | Please note the instructions on cable sections in the user manual "Axioline P: System and Installation". |
| A Note on Connection Technology | shielded, braided in pairs |
| Note on Measurement Indications | The depth is valid in the use of a symmetrical rail TH 35-7.5 (according to EN 60715). |
| Air Pressure (Storage/Transport) | 70 kPa ... 106 kPa (up to 2000 m above NN) |
| Permissible air humidity (service) | 5 % ... 95% (non-condensing) |
| Ambient Temperature (Storage/Transport) | -40 °C ... 85 °C |
| Test Voltage: Field for Functional Ground | 500 V AC, 62 Hz, 1 min. |
| Permissible air humidity (storage/transport) | 5 % ... 95% (non-condensing) |
| Test voltage: Field for 5 V and 24 V power supplies | 1500 V AC, 62 Hz, 1 min. |
| Test voltage: 24 V power supply (periphery) / functional ground | 500 V AC, 62 Hz, 1 min. |
| Test voltage: 5 V power supply from local bus (UBus)/Functional Earth | 500 V AC, 62 Hz, 1 min. |