| Parameter | Value |
|---|---|
| GTIN | 4046356644952 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2688433 |
| Catalog page | Page 122 (C-6-2017) |
| Packing unit | 1 pc |
| (Interfaces) | Transient protection |
| (Encoder data) | -10 V ... 10 V |
| (Analog outputs) | Analog I/O 500 V AC 50 Hz 1 min. |
| (Encoder inputs) | Transient protection |
| Country of origin | DE (Germany) |
| Custom tariff number | 85389091 |
| Designation (General) | Axioline F local bus |
| (Electrical isolation) | Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g |
| Designation (Interfaces) | Supply voltage input UI |
| Precision (Encoder data) | typ. 0.1 % (of output range final value) |
| No. of channels (General) | 2 |
| Output name (Encoder data) | Analog outputs |
| Connection method (General) | Bus base module |
| Data formats (Encoder data) | IB IL, S7-compatible, standardized representation |
| Depth (Key Commercial Data) | 54 mm |
| Supply voltage (Interfaces) | 24 V DC |
| Width (Key Commercial Data) | 35 mm |
| (Standards and Regulations) | No hazardous substances above threshold values |
| Height (Key Commercial Data) | 126.1 mm |
| Net weight (Connection data) | 135 g |
| Parity (Axioline potentials) | Even, odd or no parity |
| Transmission speed (General) | 100 Mbps |
| D/A resolution (Encoder data) | 16 bit |
| Test section (Analog outputs) | Logic 500 V AC 50 Hz 1 min. |
| Power consumption (Interfaces) | max. 1.4 W (Supply of the SSI interface and the analog output (20 mA), without sensor supply) |
| Voltage range (Encoder inputs) | 19.5 V DC ... 30 V DC (including all tolerances, including ripple) |
| Mounting type (Connection data) | DIN rail |
| Type of protection (Interfaces) | Surge protection of the supply voltage |
| Connection method (Encoder data) | Push-in connection |
| Current consumption (Interfaces) | max. 60 mA (Supply of the SSI interface and the analog output (20 mA), without sensor supply) |
| Designation (Ambient conditions) | Axioline F connector |
| Input name (Axioline potentials) | SSI interface |
| Number of outputs (Encoder data) | 1 |
| Degree of protection (Dimensions) | IP20 |
| Supply voltage range (Interfaces) | 19.2 V DC ... 30 V DC including all tolerances, including ripple |
| Type of protection (Encoder data) | Surge protection |
| D/A conversion time (Encoder data) | 5 µs |
| Type of protection (Encoder inputs) | Surge protection |
| Connection technology (Encoder data) | 2-wire (shielded, twisted pair) |
| Current output signal (Encoder data) | 0 mA ... 20 mA |
| Voltage output signal (Encoder data) | 0 V ... 5 V |
| Weight per Piece (excluding packing) | 135.000 g |
| Air pressure (operation) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Encoder signals (Axioline potentials) | Single-turn and multi-turn encoder, length measuring sticks |
| Input frequency (Axioline potentials) | to 2 MHz (Can be parameterized: 67.5 kHz, 125 kHz (default), 250 kHz, 500 kHz, 1 MHz, 2 MHz) |
| Stripping length (Ambient conditions) | 8 mm |
| China RoHS (Standards and Regulations) | Environmentally friendly use period: unlimited = EFUP-e |
| Connection method (Ambient conditions) | Push-in connection |
| Number of inputs (Axioline potentials) | 1 |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| Connection method (Axioline potentials) | Push-in connection |
| Mechanical tests (Electrical isolation) | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g |
| Nominal output voltage (Encoder inputs) | 24 V DC (UI- 0.5 V) |
| Permissible cable length (Encoder data) | max. 250 m |
| Protection class (Electrical isolation) | III, IEC 61140, EN 61140, VDE 0140-1 |
| Note on dimensions (Key Commercial Data) | The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715). |
| Dimensional drawing (Key Commercial Data) | |
| Current carrying capacity (Encoder inputs) | max. 500 mA |
| Adjustable resolution (Axioline potentials) | 8 ... 56 bit |
| Protective circuit/component (Encoder data) | Electronic (35 V, permanent) |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 60 °C |
| Encoder supply voltage (Axioline potentials) | 24 V DC (UI- 0.5 V) |
| Measured value representation (Encoder data) | 16 bits |
| Transmission frequency (Axioline potentials) | 2 MHz |
| Air pressure (storage/transport) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % (non-condensing) |
| Description of the input (Axioline potentials) | RS-422 interface according to SSI specification |
| Load/output load current output (Encoder data) | max. 500 Ω |
| Load/output load voltage output (Encoder data) | > 2 kΩ |
| Representation of output values (Encoder data) | 16 bits (15 bits + sign) |
| Note on weight specifications (Connection data) | with connectors and bus base module |
| Note on the connection method (Ambient conditions) | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Conductor cross section AWG max. (Ambient conditions) | 16 |
| Conductor cross section AWG min. (Ambient conditions) | 24 |
| Permissible humidity (storage/transport) (Dimensions) | 5 % ... 95 % (non-condensing) |
| Conductor cross section solid max. (Ambient conditions) | 1.5 mm² |
| Conductor cross section solid min. (Ambient conditions) | 0.2 mm² |
| Conductor cross section flexible max. (Ambient conditions) | 1.5 mm² |
| Conductor cross section flexible min. (Ambient conditions) | 0.2 mm² |
Technical specifications and performance data