| Parameter | Value |
|---|---|
| GTIN | 4055626066806 |
| Orderkey | 2702264 |
| (General) | max. 280 mA |
| Catalog page | Page 301 (C-6-2017) |
| Packing unit | 1 pc |
| (Interfaces) | max. 6 A (Total current of all outputs according to CULUS) |
| Country of origin | DE (Germany) |
| Custom tariff number | 85389091 |
| Designation (General) | Supply for digital output modules (UO) |
| Output name (Interfaces) | Digital outputs |
| Supply voltage (General) | 24 V DC |
| Depth (Key Commercial Data) | 54 mm |
| Output current (Interfaces) | max. 2 A (per channel) |
| Output voltage (Interfaces) | 24 V DC |
| Width (Key Commercial Data) | 53.6 mm |
| (Standards and Regulations) | No hazardous substances above threshold values |
| Height (Key Commercial Data) | 126.1 mm |
| Net weight (Digital outputs) | 222 g |
| Type of protection (General) | Protection against polarity reversal, EMC protective circuit, undervoltage detection |
| Current consumption (General) | typ. 25 mA (all outputs set; power supply by UOwith 30.2 V DC; without power supply to the actuator) |
| Category (Axioline potentials) | max. 4 (two channel; dependent in parameterization and wiring) |
| Connection method (Interfaces) | Direct plug-in technology |
| Number of outputs (Interfaces) | 4 (with two-channel assignment) |
| Supply voltage range (General) | 19.2 V DC ... 30.2 V DC (including all tolerances, including ripple) |
| Mounting type (Digital outputs) | DIN rail |
| Type of protection (Interfaces) | Overload protection, freewheeling circuit for inductive loads,Discharge circuit for accelerated discharge of capacitive loads |
| Designation (Ambient conditions) | Axioline F local bus |
| Degree of protection (Dimensions) | IP20 |
| Designation (Axioline potentials) | EN 62061 |
| Connection technology (Interfaces) | 2, 3-wire |
| No. of channels (Ambient conditions) | 1 |
| Weight per Piece (excluding packing) | 222.000 g |
| Air pressure (operation) (Dimensions) | 70 kPa ... 108 kPa (up to 3000 m above sea level) |
| China RoHS (Standards and Regulations) | Environmentally friendly use period: unlimited = EFUP-e |
| Connection method (Ambient conditions) | Bus base module |
| Note on dimensions (Key Commercial Data) | Housing dimensions |
| Dimensional drawing (Key Commercial Data) | |
| Ambient temperature (operation) (Dimensions) | -35 °C ... 60 °C (Mounting position: any) |
| Performance level (PL) (Axioline potentials) | max. e (two channel; dependent in parameterization and wiring) |
| Air pressure (storage/transport) (Dimensions) | 66 kPa ... 108 kPa (up to 3500 m above sea level) |
| Permissible humidity (operation) (Dimensions) | 10 % ... 75 % (on average, 85% infrequently, non-condensing) |
| Maximum output current per channel (Interfaces) | 2 A |
| Note on weight specifications (Digital outputs) | with connectors and bus base module |
| Safety Integrity Level (SIL) (Axioline potentials) | max. 3 (two channel; dependent in parameterization and wiring) |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Permissible humidity (storage/transport) (Dimensions) | 10 % ... 75 % (non-condensing) |
| Protection class (Safety-related characteristic data) | III, IEC 61140, EN 61140, VDE 0140-1 |
| Maximum output current per module / terminal block (Interfaces) | 8 A |
| Safety Integrity Level Claim Limit (SIL CL) (Axioline potentials) | max. 3 (two channel; dependent in parameterization and wiring) |
Technical specifications and performance data