| Parameter | Value |
|---|---|
| 8 (for 1-channel assignment) | |
| Type | modular |
| Depth | 54 mm |
| Width | 53.6 mm |
| Height | 126.1 mm |
| pluggable | yes |
| Input name | Digital inputs |
| Application | Functional safety |
| Cable length | max. 1000 m (200 m from the clock output to the safe input (total based on forward and return path)) |
| Current draw | max. 310 mA |
| Product type | I/O component |
| Input voltage | 24 V DC (via clock outputs T1 and T2 or external supply) |
| Mounting type | DIN rail mounting |
| Product family | Axioline F |
| Supply voltage | 5 V DC (via bus base module) |
| Connection name | Axioline F connector |
| Article revision | 12 |
| Number of inputs | 4 (for 2-channel assignment) |
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
| Connection method | Bus base module |
| Input filter time | 1.5 ms |
| Input address area | 5 Byte |
| Note on dimensions | Housing dimensions |
| Protective circuit | Protection against polarity reversal, EMC protective circuit, undervoltage detection |
| Dimensional drawing | |
| Input voltage range | -3 V DC ... 30 V DC |
| Note on application | Only for industrial use |
| Output address area | 5 Byte |
| Transmission medium | Copper |
| Degree of protection | IP20 |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Connection technology | 2-, 3-, 4-conductor |
| Required parameter data | 22 Byte ((I-and F-parameters)) |
| Air pressure (operation) | 70 kPa ... 108 kPa (up to 3000 m above sea level) |
| Description of the input | IEC 61131-2 type 3 |
| Nominal input voltage UIN | 24 V DC |
| Conductor cross section AWG | 24 ... 16 |
| Required configuration data | 10 Byte |
| Nominal input current at UIN | typ. 4.2 mA |
| Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
| Conductor cross section, rigid | 0.2 mm² ... 1.5 mm² |
| Ambient temperature (operation) | -35 °C ... 60 °C (Mounting position: any) |
| Air pressure (storage/transport) | 66 kPa ... 108 kPa (up to 3500 m above sea level) |
| Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
| Permissible humidity (operation) | 10 % ... 75 % (on average, 85% infrequently, non-condensing) |
| Conductor cross section, flexible | 0.2 mm² ... 1.5 mm² |
| Typical input current per channel | 4.2 mA |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (storage/transport) | 10 % ... 75 % (non-condensing) |
| Maximum power dissipation for nominal condition | 2 W |
Technical specifications and performance data