| Parameter | Value |
|---|---|
| two channels | |
| Note | The data apply for DALI bus 1 and DALI bus 2, respectively. |
| Type | block modular |
| Depth | 54 mm |
| Width | 35 mm |
| Height | 126.1 mm |
| Designation | DALI |
| Current draw | max. 65 mA |
| Product type | I/O component |
| Mounting type | DIN rail mounting |
| Output current | 230 mA (guaranteed) |
| Product family | Axioline F |
| Supply voltage | typ. 16 V DC (Bus voltage) |
| Connection name | Axioline F connector |
| No. of channels | 2 (DALI 1, DALI 2) |
| Article revision | 04 |
| Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
| Stripping length | 8 mm |
| Connection method | Bus base module |
| Mounting position | any (no temperature derating) |
| Scope of delivery | including bus base module and Axioline F connectors |
| Input address area | 8 Byte |
| Note on dimensions | The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715). |
| Protective circuit | Surge protection; electronic (35 V, 0.5 s) |
| Special properties | Single client |
| Transmission speed | 100 Mbps |
| Type of protection | Bus protected up to 250 V AC, maximum |
| Dimensional drawing | |
| Note on application | Only for industrial use |
| Output address area | 8 Byte |
| Degree of protection | IP20 |
| Number of interfaces | 2 |
| Overvoltage category | II (IEC 60664-1, EN 60664-1) |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Current carrying capacity | max. 195 mA (Bus load, see derating) |
| Conductor cross section AWG | 24 ... 16 |
| Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
| Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
| Conductor cross section, rigid | 0.2 mm² ... 1.5 mm² |
| Ambient temperature (operation) | -25 °C ... 60 °C |
| Test voltage: DALI 1 / DALI 2 | 500 V AC, 50 Hz, 1 min. |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
| Conductor cross section, flexible | 0.2 mm² ... 1.5 mm² |
| Output current with short-circuit | max. 250 mA |
| Test voltage: DALI/functional ground | 1.5 kV AC, 50 Hz, 1 min. |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
| Test voltage: DALI/24 V supply (periphery) | 1.5 kV AC, 50 Hz, 1 min. |
| Test voltage: 24 V supply (I/O) / functional ground | 500 V AC, 50 Hz, 1 min. |
| Test voltage: DALI / 5 V supply of the local bus (UBus) | 1.5 kV AC, 50 Hz, 1 min. |
| Test voltage: 5 V supply of the local bus (UBus) / functional ground | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 5 V supply of the local bus (UBus) / 24 V supply (I/Os) | 500 V AC, 50 Hz, 1 min. |
Technical specifications and performance data
Installation and operation guide