| Parameter | Value |
|---|---|
| GTIN | 4046356932486 |
| Orderkey | 2702053 |
| Catalog page | Page 109 (C-6-2017) |
| Packing unit | 1 pc |
| (Interfaces) | Polarity reversal protection of the supply voltage |
| Country of origin | DE (Germany) |
| (Digital outputs) | 24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min. |
| Custom tariff number | 85389091 |
| Designation (General) | Axioline F local bus |
| (Electrical isolation) | Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g |
| Protection (Interfaces) | max. 16 A (polarity reversal protection up to 5 A) |
| Designation (Interfaces) | Supply for digital output modules (UO) |
| No. of channels (General) | 2 |
| Connection method (General) | Bus base module |
| Depth (Key Commercial Data) | 54 mm |
| Supply voltage (Interfaces) | 24 V DC |
| Width (Key Commercial Data) | 53.6 mm |
| (Standards and Regulations) | No hazardous substances above threshold values |
| Height (Key Commercial Data) | 129.9 mm |
| Net weight (Connection data) | 260 g |
| Transmission speed (General) | 100 Mbps |
| Caption (Key Commercial Data) | Dimensions |
| Power consumption (Interfaces) | max. 480 W (of which 1.8 W internal losses) |
| Test section (Digital outputs) | 5 V communications power (logic), 24 V supply (I/O) 500 V AC 50 Hz 1 min. |
| Mounting type (Connection data) | DIN rail |
| Type of protection (Interfaces) | Surge protection of the supply voltage |
| Current consumption (Interfaces) | max. 16 A (Provide external protection; if the total current of 8 A is exceeded, connect the supply at the power connector parallel via both terminal points.) |
| Designation (Ambient conditions) | Axioline F connector |
| Degree of protection (Dimensions) | IP20 |
| Output name (Axioline potentials) | Digital outputs |
| Supply voltage range (Interfaces) | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Output voltage (Axioline potentials) | 24 V |
| Weight per Piece (excluding packing) | 260.000 g |
| Air pressure (operation) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Stripping length (Ambient conditions) | 8 mm |
| China RoHS (Standards and Regulations) | Environmentally friendly use period: unlimited = EFUP-e |
| Connection method (Ambient conditions) | Push-in connection |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| Connection method (Axioline potentials) | Push-in connection |
| Mechanical tests (Electrical isolation) | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g |
| Number of outputs (Axioline potentials) | 64 |
| Protection class (Electrical isolation) | III, IEC 61140, EN 61140, VDE 0140-1 |
| Nominal load, lamp (Axioline potentials) | max. 12 W (at nominal voltage) |
| Note on dimensions (Key Commercial Data) | The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715). |
| Type of protection (Axioline potentials) | Short-circuit protection, overload protection of the outputs |
| Dimensional drawing (Key Commercial Data) | |
| Nominal load, ohmic (Axioline potentials) | max. 12 W (48 Ω, with nominal voltage) |
| Connection technology (Axioline potentials) | 1-wire |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 60 °C |
| Nominal output voltage (Axioline potentials) | 24 V DC |
| Air pressure (storage/transport) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Nominal load, inductive (Axioline potentials) | max. 12 VA (1.2 H, 48 Ω, with nominal voltage) |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % (non-condensing) |
| Note on weight specifications (Connection data) | with connectors and bus base module |
| Note on the connection method (Ambient conditions) | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Conductor cross section AWG max. (Ambient conditions) | 16 |
| Conductor cross section AWG min. (Ambient conditions) | 24 |
| Permissible humidity (storage/transport) (Dimensions) | 5 % ... 95 % (non-condensing) |
| Conductor cross section solid max. (Ambient conditions) | 1.5 mm² |
| Conductor cross section solid min. (Ambient conditions) | 0.2 mm² |
| Maximum output current per module (Axioline potentials) | 16 A (provide external protection) |
| Maximum output current per channel (Axioline potentials) | 500 mA |
| Conductor cross section flexible max. (Ambient conditions) | 1.5 mm² |
| Conductor cross section flexible min. (Ambient conditions) | 0.2 mm² |
Technical specifications and performance data
Installation and operation guide