| Parameter | Value |
|---|---|
| GTIN | 4046356933087 |
| Orderkey | 2702068 |
| Catalog page | Page 110 (C-6-2017) |
| Packing unit | 1 pc |
| (Dimensions) | -25 °C ... 50 °C (max. 2 A/channel for any mounting position) |
| Country of origin | DE (Germany) |
| (Digital outputs) | I/O area AC / PE 4 kV Rated surge voltage (basic insulation according to EN 61010-2-201/IEC 61010-2-201) |
| Custom tariff number | 85389091 |
| Designation (General) | Axioline F local bus |
| (Electrical isolation) | IEC 61850-3 Attenuated oscillating waves, EN 61000-4-18/IEC 61000-4-18 1 kV symmetrical, 2.5 kV asymmetrical |
| Protection (Interfaces) | max. 8 A |
| Designation (Interfaces) | Supply for digital output modules (UO) |
| No. of channels (General) | 2 |
| Connection method (General) | Bus base module |
| Depth (Key Commercial Data) | 54 mm |
| Supply voltage (Interfaces) | 230 V AC |
| Width (Key Commercial Data) | 53.6 mm |
| (Standards and Regulations) | No hazardous substances above threshold values |
| Height (Key Commercial Data) | 126.1 mm |
| Net weight (Connection data) | 239 g |
| Transmission speed (General) | 100 Mbps |
| Power consumption (Interfaces) | max. 2024 VA (of which 8 VA internal losses) |
| Test section (Digital outputs) | I/Os / logic 4 kV Rated surge voltage (safe isolation according to EN 61010-2-201/IEC 61010-2-201) |
| Mounting type (Connection data) | DIN rail |
| Type of protection (Interfaces) | Surge protection of the supply voltage |
| Current consumption (Interfaces) | max. 8 A (provide external protection) |
| Designation (Ambient conditions) | Axioline F connector |
| Degree of protection (Dimensions) | IP20 |
| Output name (Axioline potentials) | Digital outputs |
| Supply voltage range (Interfaces) | 12 V AC ... 253 V AC (including all tolerances, including ripple, 50 ... 60 Hz) |
| Output voltage (Axioline potentials) | 230 V AC |
| Weight per Piece (excluding packing) | 239.000 g |
| Air pressure (operation) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Stripping length (Ambient conditions) | 8 mm |
| China RoHS (Standards and Regulations) | Environmentally friendly use period: unlimited = EFUP-e |
| Connection method (Ambient conditions) | Push-in connection |
| Connection method (Axioline potentials) | Push-in connection |
| Mechanical tests (Electrical isolation) | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g |
| Number of outputs (Axioline potentials) | 4 (Triac outputs with zero voltage switch) |
| Note on dimensions (Key Commercial Data) | The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715). |
| Type of protection (Axioline potentials) | External protection required |
| Dimensional drawing (Key Commercial Data) | |
| Nominal load, ohmic (Axioline potentials) | max. 460 W (at nominal voltage) |
| Connection technology (Axioline potentials) | 3-wire |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 60 °C (max. 2 A/channel for wall mounting on horizontal DIN rail; max. 1 A/channel for any mounting position) |
| Nominal output voltage (Axioline potentials) | 230 V AC |
| Air pressure (storage/transport) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % (non-condensing) |
| Note on weight specifications (Connection data) | with connectors and bus base module |
| Note on the connection method (Ambient conditions) | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.When selecting the cables, please note that in the case of a small conductor cross section and high current, the terminal point temperature may be up to 30 K above the ambient temperature. |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Conductor cross section AWG max. (Ambient conditions) | 16 |
| Conductor cross section AWG min. (Ambient conditions) | 20 |
| Permissible humidity (storage/transport) (Dimensions) | 5 % ... 95 % (non-condensing) |
| Developed according to standard (Electrical isolation) | IEC 61850-3 Immunity to magnetic fields, EN 61000-4-8/IEC 61000-4-8 300 A/m continuous, 1000 A/m for 1 s |
| Conductor cross section solid max. (Ambient conditions) | 1.5 mm² |
| Conductor cross section solid min. (Ambient conditions) | 0.5 mm² |
| Maximum output current per module (Axioline potentials) | 8 A AC (provide external protection) |
| Maximum output current per channel (Axioline potentials) | 2 A AC |
| Conductor cross section flexible max. (Ambient conditions) | 1.5 mm² |
| Conductor cross section flexible min. (Ambient conditions) | 0.5 mm² |
Technical specifications and performance data
Installation and operation guide