| Parameter | Value |
|---|---|
| max. 1 per second (with inductive load) | |
| Type | block modular |
| Depth | 54 mm |
| Width | 35 mm |
| Height | 129.9 mm |
| Load min. | 10 kΩ |
| Output name | Digital outputs |
| Current draw | max. 60 mA |
| Product type | I/O component |
| Signal delay | max. 100 µs (when switched on) |
| Mounting type | DIN rail mounting |
| Output voltage | 24 V DC |
| Product family | Axioline F |
| Supply voltage | 5 V DC (via bus base module) |
| Connection name | Axioline F connector |
| Article revision | 02 |
| Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
| Stripping length | 8 mm |
| Connection method | Bus base module |
| Mounting position | any (no temperature derating) |
| Number of outputs | 16 |
| Scope of delivery | including bus base module and Axioline F connectors |
| Input address area | 0 Byte |
| Nominal load, lamp | max. 12 W (at nominal voltage) |
| Note on dimensions | The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715). |
| Protective circuit | Short-circuit protection, overload protection of the outputs; electronic |
| Transmission speed | 100 Mbps |
| Dimensional drawing | |
| Nominal load, ohmic | max. 12 W (48 Ω, with nominal voltage) |
| Note on application | Only for industrial use |
| Output address area | 2 Byte |
| Switching frequency | max. 10000 per second (with at least 50 mA load current) |
| Degree of protection | IP20 |
| Number of interfaces | 2 |
| Overvoltage category | II (IEC 60664-1, EN 60664-1) |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Connection technology | 2-conductor |
| Overcurrent shut-down | as of 0.7 A |
| Behavior with overload | Shutdown with automatic restart |
| Nominal output voltage | 24 V DC |
| Nominal load, inductive | max. 12 VA (1.2 H, 48 Ω, with nominal voltage) |
| Required parameter data | 1 Byte |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Conductor cross section AWG | 24 ... 16 |
| Required configuration data | 6 Byte |
| Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
| Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
| Conductor cross section, rigid | 0.2 mm² ... 1.5 mm² |
| Ambient temperature (operation) | -25 °C ... 60 °C |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Behavior with inductive overload | Output can be destroyed |
| Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
| Output current when switched off | max. 300 µA |
| Output voltage when switched off | max. 1 V |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
| Conductor cross section, flexible | 0.2 mm² ... 1.5 mm² |
| Maximum output current per module | 8 A (provide external protection) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
| Reverse voltage resistance to short pulses | limited protection up to 0.5 A for 1 s |
| Maximum power dissipation for nominal condition | 1.6 W |
| Test voltage: 24 V supply (I/O) / functional ground | 500 V AC, 50 Hz, 1 min. |
| Limitation of the voltage induced on circuit interruption | -32.8 V ... -15 V |
| Output current with ground connection interrupt when switched off | < 1 mA |
| Test voltage: 5 V supply of the local bus (UBus) / functional ground | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 5 V supply of the local bus (UBus) / 24 V supply (I/Os) | 500 V AC, 50 Hz, 1 min. |