| Parameter | Value |
|---|---|
| GTIN | 4046356729789 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2701222 |
| Packing unit | 1 pc |
| (Dimensions) | -40 °C ... 70 °C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.) |
| (Digital inputs) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Country of origin | DE (Germany) |
| (Inline potentials) | Polarity reversal protection of the supply voltage |
| Custom tariff number | 85389091 |
| Designation (General) | Service |
| No. of channels (General) | 2 |
| China RoHS (Digital inputs) | Environmentally Friendly Use Period = 50 |
| Connection method (General) | Micro USB type B |
| Depth (Key Commercial Data) | 74 mm |
| REACh SVHC (Digital inputs) | Lead 7439-92-1 |
| Width (Key Commercial Data) | 45 mm |
| Height (Key Commercial Data) | 126.1 mm |
| Transmission speed (General) | 100 Mbps |
| Transmission physics (General) | Ethernet in RJ45 twisted pair |
| Designation (Inline potentials) | Axioline F local bus supply (UBus) |
| Net weight (Ambient conditions) | 222 g |
| Degree of protection (Dimensions) | IP20 |
| Mounting type (Ambient conditions) | DIN rail mounting |
| Supply voltage (Inline potentials) | 5 V DC (via bus base module) |
| Weight per Piece (excluding packing) | 222.000 g |
| Air pressure (operation) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Power consumption (Inline potentials) | max. 13.7 W (with 2 A load at UBusfor the I/Os) |
| Power supply unit (Inline potentials) | 2 A |
| (Power supply for module electronics) | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Type of protection (Inline potentials) | Surge protection of the supply voltage |
| Current consumption (Inline potentials) | max. 570 mA (with 2 A at UBusfor the I/Os and UL= 24 V) |
| Note on dimensions (Key Commercial Data) | The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715). |
| Number of supported devices (Interfaces) | max. 63 (per station) |
| Supply voltage range (Inline potentials) | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Dimensional drawing (Key Commercial Data) | |
| Connection technology (Axioline potentials) | Push-in connection |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 60 °C (Mounting position: wall mounting on horizontal DIN rail) |
| Air pressure (storage/transport) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % (non-condensing) |
| Note on weight specifications (Ambient conditions) | with connector and bus base module |
| Supply voltage (Power supply for module electronics) | 24 V DC |
| Permissible humidity (storage/transport) (Dimensions) | 5 % ... 95 % (non-condensing) |
| Supply voltage range (System limits of the bus coupler) | |
| Supply voltage range (Power supply for module electronics) | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Number of local bus devices that can be connected (Interfaces) | max. 63 |
Technical specifications and performance data
Installation and operation guide