| Parameter | Value |
|---|---|
| GTIN | 4046356501446 |
| Orderkey | 2688080 |
| Catalog page | Page 117 (C-6-2017) |
| Packing unit | 1 pc |
| (Interfaces) | Transient protection supply voltage |
| (Analog outputs) | Analog outputs/functional earth ground 500 V AC 50 Hz 1 min. |
| Country of origin | DE (Germany) |
| Custom tariff number | 85389091 |
| Designation (General) | Axioline F local bus |
| (Axioline potentials) | -10 V ... 10 V |
| (Electrical isolation) | Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g |
| Designation (Interfaces) | Supply for analog modules (UA) |
| No. of channels (General) | 2 |
| Connection method (General) | Bus base module |
| Depth (Key Commercial Data) | 54 mm |
| Supply voltage (Interfaces) | 24 V DC |
| Width (Key Commercial Data) | 53.6 mm |
| (Standards and Regulations) | No hazardous substances above threshold values |
| Height (Key Commercial Data) | 126.1 mm |
| Net weight (Connection data) | 260 g |
| Transmission speed (General) | 100 Mbps |
| Test section (Analog outputs) | 5 V communications power (logic), 24 V supply (I/O) 500 V AC 50 Hz 1 min. |
| Power consumption (Interfaces) | max. 5.64 W (8 current channels, 20 mA output) |
| Mounting type (Connection data) | DIN rail |
| Precision (Axioline potentials) | typ. 0.1 % (of output range final value) |
| Type of protection (Interfaces) | Surge protection of the supply voltage |
| Current consumption (Interfaces) | typ. 110 mA (8 voltage channels, 10 V output) |
| Designation (Ambient conditions) | Axioline F connector |
| Degree of protection (Dimensions) | IP20 |
| Output name (Axioline potentials) | Analog outputs |
| Supply voltage range (Interfaces) | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Data formats (Axioline potentials) | IB IL, S7-compatible |
| D/A resolution (Axioline potentials) | 16 bit |
| Weight per Piece (excluding packing) | 260.000 g |
| Air pressure (operation) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Stripping length (Ambient conditions) | 8 mm |
| China RoHS (Standards and Regulations) | Environmentally friendly use period: unlimited = EFUP-e |
| Connection method (Ambient conditions) | Push-in connection |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| Connection method (Axioline potentials) | Push-in connection |
| Mechanical tests (Electrical isolation) | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g |
| Number of outputs (Axioline potentials) | 8 |
| Protection class (Electrical isolation) | III, IEC 61140, EN 61140, VDE 0140-1 |
| Note on dimensions (Key Commercial Data) | The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715). |
| Type of protection (Axioline potentials) | Short-circuit and overload protection |
| D/A conversion time (Axioline potentials) | 5 µs |
| Dimensional drawing (Key Commercial Data) | |
| Process data update (Axioline potentials) | 300 µs |
| Connection technology (Axioline potentials) | 2-wire |
| Current output signal (Axioline potentials) | 0 mA ... 20 mA |
| Voltage output signal (Axioline potentials) | 0 V ... 5 V |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 60 °C |
| Air pressure (storage/transport) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % (non-condensing) |
| Permissible cable length (Axioline potentials) | max. 250 m |
| Note on weight specifications (Connection data) | with connectors and bus base module |
| Note on the connection method (Ambient conditions) | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
| Protective circuit/component (Axioline potentials) | electronic |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Conductor cross section AWG max. (Ambient conditions) | 16 |
| Conductor cross section AWG min. (Ambient conditions) | 24 |
| Load/output load current output (Axioline potentials) | to 500 Ω |
| Load/output load voltage output (Axioline potentials) | > 2 kΩ |
| Permissible humidity (storage/transport) (Dimensions) | 5 % ... 95 % (non-condensing) |
| Representation of output values (Axioline potentials) | 16 bits (15 bits + sign) |
| Conductor cross section solid max. (Ambient conditions) | 1.5 mm² |
| Conductor cross section solid min. (Ambient conditions) | 0.2 mm² |
| Conductor cross section flexible max. (Ambient conditions) | 1.5 mm² |
| Conductor cross section flexible min. (Ambient conditions) | 0.2 mm² |
| Note regarding the connection technology (Axioline potentials) | shielded, twisted pair |
Technical specifications and performance data