| Parameter | Value |
|---|---|
| GTIN | 4046356763554 |
| Orderkey | 2701503 |
| (Supply) | max. 2 A (at UA(IO-Link B ports, pin 2 and pin 5)) |
| Catalog page | Page 203 (C-6-2017) |
| Depth (Note) | 30.5 mm |
| Packing unit | 1 pc |
| Width (Note) | 60 mm |
| Height (Note) | 185 mm |
| (IO-Link inputs) | Short-circuit protection |
| Country of origin | DE (Germany) |
| (Digital outputs) | 24 V supply (actuator supply)/FE 500 V AC 50 Hz 1 min. |
| Custom tariff number | 85176200 |
| Designation (General) | PROFIBUS DP |
| (Electrical isolation) | Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g |
| Designation (Interfaces) | PROFIBUS DP |
| Drill hole spacing (Note) | 198.5 mm |
| No. of channels (General) | 2 |
| Note on dimensions (Note) | The height is 212 mm including fixing clips. |
| Dimensional drawing (Note) | |
| Port type (Digital inputs) | Class A |
| Connection method (General) | M12 fast connection technology |
| Equipment type (Interfaces) | PROFIBUS slave |
| Type of protection (Supply) | Overload protection |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Transmission speed (General) | 9.6 kbps ... 12 Mbps (Automatic baud rate detection) |
| Number of positions (General) | 5 |
| Signal delay (IO-Link inputs) | max. 150 µs (when switched on) |
| (Supply of the IO-Link ports) | Short-circuit protection for the sensor supply |
| Test section (Digital outputs) | 24 V supply (communications power and sensor supply, IO-Link ports)/bus connection 500 V AC 50 Hz 1 min. |
| Transmission physics (General) | PROFIBUS-DP-compliant copper cable |
| Net weight (Ambient conditions) | 552 g |
| Switching rate (IO-Link inputs) | 1 per second, maximum (at nominal inductive load) |
| Number of ports (Digital inputs) | 4 |
| Address area assignment (General) | 1 ... 126, adjustable |
| Degree of protection (Dimensions) | IP65/IP67 |
| Permissible cable length (Supply) | < 20 m |
| Connection method (Digital inputs) | M12 fast connection technology |
| Connection method (IO-Link inputs) | M12 connector, X01 ... X04 have double occupancy |
| Mounting type (Ambient conditions) | Wall mounting |
| Number of outputs (IO-Link inputs) | max. 8 |
| Output description (IO-Link inputs) | IO-Link ports in digital output (DO) mode |
| Type of protection (IO-Link inputs) | Overload protection |
| Nominal load, ohmic (IO-Link inputs) | 3.6 W (160 Ω, at nominal load) |
| Weight per Piece (excluding packing) | 552.000 g |
| Air pressure (operation) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Housing material (Ambient conditions) | Pocan® |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 25; |
| Connection technology (Digital inputs) | 3-wire |
| Connection technology (IO-Link inputs) | 3-wire |
| Designation connection point (General) | Copper cable |
| System-specific protocols (Interfaces) | PROFIBUS protocols DP V1 |
| Behavior with overload (IO-Link inputs) | Shutdown with automatic restart |
| Mechanical tests (Electrical isolation) | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g |
| Nominal output voltage (IO-Link inputs) | 24 V DC |
| Nominal voltage for I/O supply (Supply) | 24 V DC |
| Note on the connection method (General) | B-coded |
| Protection class (Electrical isolation) | III, IEC 61140, EN 61140, VDE 0140-1 |
| Input name (Supply of the IO-Link ports) | Digital inputs at pin 2 for type A ports |
| Nominal load, inductive (IO-Link inputs) | 3.6 VA (0.8 H, 160 Ω, at nominal load) |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 60 °C |
| Air pressure (storage/transport) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Input frequency (Supply of the IO-Link ports) | 0.5 kHz |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % |
| Utilization restriction (Key Commercial Data) | 1 |
| Designation (System limits of the bus coupler) | Actuators (UA) |
| Number of inputs (Supply of the IO-Link ports) | max. 8 (EN 61131-2 type 1) |
| Connection method (Supply of the IO-Link ports) | M12 connector, X01 ... X04 have double occupancy |
| Input filter time (Supply of the IO-Link ports) | < 1000 µs |
| Nominal current for every IO-Link port (Supply) | max. 150 mA (at C/Q (pin 4), maximum of 1.6 A over all 8 IO-Link C/Q and L+ cables) |
| Type of protection (Supply of the IO-Link ports) | Overload protection |
| Output current when switched off (IO-Link inputs) | max. 300 µA |
| Output voltage when switched off (IO-Link inputs) | max. 1 V |
| Supply voltage (System limits of the bus coupler) | 24 V DC |
| Maximum output current per device (IO-Link inputs) | 1.2 A |
| Total sensor current (Supply of the IO-Link ports) | max. 1.6 A (from L+/L-) |
| Connection technology (Supply of the IO-Link ports) | 3-wire |
| Maximum output current per channel (IO-Link inputs) | 150 mA |
| Nominal input current (Supply of the IO-Link ports) | typ. 3 mA |
| Ambient temperature (storage/transport) (Dimensions) | -25 °C ... 85 °C |
| Connection method (System limits of the bus coupler) | M12 connector (T-coded) |
| Permissible humidity (storage/transport) (Dimensions) | 5 % ... 95 % |
| Current consumption (System limits of the bus coupler) | typ. 30 mA ±15 % (at 24 V DC) |
| Description of the input (Supply of the IO-Link ports) | IO-Link ports in digital input (DI) mode |
| Number of positions (System limits of the bus coupler) | 4 |
| Nominal input voltage UIN (Supply of the IO-Link ports) | 24 V DC |
| Sensor current per channel (Supply of the IO-Link ports) | max. 200 mA (from L+/L-) |
| Nominal input current at UIN (Supply of the IO-Link ports) | typ. 3 mA |
| Input voltage range "0" signal (Supply of the IO-Link ports) | -0.3 V DC ... 5 V DC |
| Input voltage range "1" signal (Supply of the IO-Link ports) | 15 V DC ... 30 V DC |
| Nominal supply voltage range (System limits of the bus coupler) | 18 V DC ... 31.2 V DC (including all tolerances, including ripple) |
| Limitation of the voltage induced on circuit interruption (IO-Link inputs) | -15 V DC |
Technical specifications and performance data
Installation and operation guide