| Parameter | Value |
|---|---|
| GTIN | 4046356763608 |
| Orderkey | 2701508 |
| (Supply) | max. 2 A (at UA(IO-Link B ports, pin 2 and pin 5)) |
| Catalog page | Page 203 (C-6-2017) |
| Depth (Note) | 38 mm |
| Packing unit | 1 pc |
| Width (Note) | 60 mm |
| Height (Note) | 185 mm |
| (IO-Link inputs) | Short-circuit protection |
| Country of origin | DE (Germany) |
| (Digital outputs) | 24 V supply (actuator supply)/FE 500 V AC 50 Hz 1 min. |
| Custom tariff number | 85176200 |
| Designation (General) | PROFIBUS DP |
| (Electrical isolation) | Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g |
| Designation (Interfaces) | PROFIBUS DP |
| Drill hole spacing (Note) | 198.5 mm |
| No. of channels (General) | 2 |
| Note on dimensions (Note) | The height is 194.5 mm including the mounting plate. With fixing clips pulled out, the height is 212 mm. The depth is 38 mm including the mounting plate (30.5 mm without the mounting plate). |
| Dimensional drawing (Note) | |
| Port type (Digital inputs) | Class A |
| Connection method (General) | M12 fast connection technology |
| Equipment type (Interfaces) | PROFIBUS slave |
| Type of protection (Supply) | Overload protection |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Transmission speed (General) | 9.6 kbps ... 12 Mbps (Automatic baud rate detection) |
| Number of positions (General) | 5 |
| Signal delay (IO-Link inputs) | max. 150 µs (when switched on) |
| (Supply of the IO-Link ports) | Short-circuit protection for the sensor supply |
| Test section (Digital outputs) | 24 V supply (communications power and sensor supply, IO-Link ports)/bus connection 500 V AC 50 Hz 1 min. |
| Transmission physics (General) | PROFIBUS-DP-compliant copper cable |
| Net weight (Ambient conditions) | 710 g |
| Switching rate (IO-Link inputs) | 1 per second, maximum (at nominal inductive load) |
| Number of ports (Digital inputs) | 4 |
| Address area assignment (General) | 1 ... 126, adjustable |
| Degree of protection (Dimensions) | IP65/IP67 |
| Permissible cable length (Supply) | < 20 m |
| Connection method (Digital inputs) | M12 fast connection technology |
| Connection method (IO-Link inputs) | M12 connector, X01 ... X04 have double occupancy |
| Mounting type (Ambient conditions) | Wall mounting or DIN rail mounting; both with mounting plate. |
| Number of outputs (IO-Link inputs) | max. 8 |
| Output description (IO-Link inputs) | IO-Link ports in digital output (DO) mode |
| Type of protection (IO-Link inputs) | Overload protection |
| Nominal load, ohmic (IO-Link inputs) | 3.6 W (160 Ω, at nominal load) |
| Weight per Piece (excluding packing) | 710.000 g |
| Air pressure (operation) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Housing material (Ambient conditions) | Zinc die-cast |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 25; |
| Connection technology (Digital inputs) | 3-wire |
| Connection technology (IO-Link inputs) | 3-wire |
| Designation connection point (General) | Copper cable |
| System-specific protocols (Interfaces) | PROFIBUS protocols DP V1 |
| Behavior with overload (IO-Link inputs) | Shutdown with automatic restart |
| Mechanical tests (Electrical isolation) | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g |
| Nominal output voltage (IO-Link inputs) | 24 V DC |
| Nominal voltage for I/O supply (Supply) | 24 V DC |
| Note on the connection method (General) | B-coded |
| Protection class (Electrical isolation) | III, IEC 61140, EN 61140, VDE 0140-1 |
| Input name (Supply of the IO-Link ports) | Digital inputs at pin 2 for type A ports |
| Nominal load, inductive (IO-Link inputs) | 3.6 VA (0.8 H, 160 Ω, at nominal load) |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 60 °C |
| Air pressure (storage/transport) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Input frequency (Supply of the IO-Link ports) | 0.5 kHz |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % |
| Utilization restriction (Key Commercial Data) | 1 |
| Designation (System limits of the bus coupler) | Actuators (UA) |
| Number of inputs (Supply of the IO-Link ports) | max. 8 (EN 61131-2 type 1) |
| Connection method (Supply of the IO-Link ports) | M12 connector, X01 ... X04 have double occupancy |
| Input filter time (Supply of the IO-Link ports) | < 1000 µs |
| Nominal current for every IO-Link port (Supply) | max. 150 mA (at C/Q (pin 4), maximum of 1.6 A over all 8 IO-Link C/Q and L+ cables) |
| Type of protection (Supply of the IO-Link ports) | Overload protection |
| Output current when switched off (IO-Link inputs) | max. 300 µA |
| Output voltage when switched off (IO-Link inputs) | max. 1 V |
| Supply voltage (System limits of the bus coupler) | 24 V DC |
| Maximum output current per device (IO-Link inputs) | 1.2 A |
| Total sensor current (Supply of the IO-Link ports) | max. 1.6 A (from L+/L-) |
| Connection technology (Supply of the IO-Link ports) | 3-wire |
| Maximum output current per channel (IO-Link inputs) | 150 mA |
| Nominal input current (Supply of the IO-Link ports) | typ. 3 mA |
| Ambient temperature (storage/transport) (Dimensions) | -25 °C ... 85 °C |
| Connection method (System limits of the bus coupler) | M12 connector (T-coded) |
| Permissible humidity (storage/transport) (Dimensions) | 5 % ... 95 % |
| Current consumption (System limits of the bus coupler) | typ. 30 mA ±15 % (at 24 V DC) |
| Description of the input (Supply of the IO-Link ports) | IO-Link ports in digital input (DI) mode |
| Number of positions (System limits of the bus coupler) | 4 |
| Nominal input voltage UIN (Supply of the IO-Link ports) | 24 V DC |
| Sensor current per channel (Supply of the IO-Link ports) | max. 200 mA (from L+/L-) |
| Nominal input current at UIN (Supply of the IO-Link ports) | typ. 3 mA |
| Input voltage range "0" signal (Supply of the IO-Link ports) | -0.3 V DC ... 5 V DC |
| Input voltage range "1" signal (Supply of the IO-Link ports) | 15 V DC ... 30 V DC |
| Nominal supply voltage range (System limits of the bus coupler) | 18 V DC ... 31.2 V DC (including all tolerances, including ripple) |
| Limitation of the voltage induced on circuit interruption (IO-Link inputs) | -15 V DC |
Technical specifications and performance data