| Parameter | Value |
|---|---|
| GTIN | 4055626279671 |
| Orderkey | 2702658 |
| Depth (Note) | 20 mm |
| Packing unit | 1 pc |
| Width (Note) | 60 mm |
| Height (Note) | 141 mm |
| Country of origin | DE (Germany) |
| Custom tariff number | 85176200 |
| (Ambient conditions) | Polarity reversal protection of the inputs |
| Test section (General) | 24 V supply/FE 500 V AC 50 Hz 1 min. |
| (Electrical isolation) | Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g |
| Note on dimensions (Note) | The height is 170 mm including fixing clips. The depth is 30 mm including the connector. |
| Dimensional drawing (Note) | |
| Net weight (Digital inputs) | 299 g |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Mounting type (Digital inputs) | Wall mounting |
| Degree of protection (Dimensions) | IP65/IP67 |
| Housing material (Digital inputs) | Pocan® |
| Weight per Piece (excluding packing) | 299.000 g |
| Air pressure (operation) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Number of inputs (Ambient conditions) | 8 |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Connection method (Ambient conditions) | M12 connector |
| Input filter time (Ambient conditions) | 1 ms |
| Mechanical tests (Electrical isolation) | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g |
| Protection class (Electrical isolation) | III, IEC 61140, EN 61140, VDE 0140-1 |
| Type of protection (Ambient conditions) | Overload protection, short-circuit protection of sensor supply |
| Connection technology (Ambient conditions) | 4-wire |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 60 °C |
| Air pressure (storage/transport) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Description of the input (Ambient conditions) | EN 61131-2 types 1 and 3 |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % |
| Utilization restriction (Key Commercial Data) | EMC: class A product, see manufacturer's declaration in the download area |
| Nominal input current at UIN (Ambient conditions) | typ. 2.4 mA |
| Input voltage range "0" signal (Ambient conditions) | -3 V ... 5 V DC |
| Input voltage range "1" signal (Ambient conditions) | 11 V DC ... 30 V DC |
| Ambient temperature (storage/transport) (Dimensions) | -25 °C ... 70 °C |
| Permissible humidity (storage/transport) (Dimensions) | 5 % ... 95 % |
Technical specifications and performance data