| Parameter | Value |
|---|---|
| GTIN | 4046356763790 |
| Orderkey | 2701531 |
| (Supply) | Short-circuit protection for the sensor supply |
| Catalog page | Page 193 (C-6-2017) |
| Depth (Note) | 38 mm |
| Packing unit | 1 pc |
| Width (Note) | 60 mm |
| (Interfaces) | Logical addressing |
| Height (Note) | 185 mm |
| (Digital inputs) | Short-circuit protection |
| Country of origin | DE (Germany) |
| (Digital outputs) | 24 V supply (actuator supply)/FE 500 V AC 50 Hz 1 min. |
| Input name (Supply) | Digital inputs at pin 2 for type A ports |
| Custom tariff number | 85176200 |
| Designation (General) | EtherCAT® |
| (Electrical isolation) | Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g |
| Designation (Interfaces) | EtherCAT® |
| Input frequency (Supply) | 0.5 kHz |
| Drill hole spacing (Note) | 198.5 mm |
| No. of channels (General) | 2 |
| Note on dimensions (Note) | The height is 194.5 mm including the mounting plate. With fixing clips pulled out, the height is 212 mm. The depth is 38 mm including the mounting plate (30.5 mm without the mounting plate). |
| Number of inputs (Supply) | max. 8 (EN 61131-2 type 1) |
| Connection method (Supply) | M12 connector, X01 ... X04 have double occupancy |
| Dimensional drawing (Note) | |
| Input filter time (Supply) | < 1000 µs |
| Specification (Interfaces) | ETG.1000 V1.02 |
| Connection method (General) | M12 fast connection technology |
| Equipment type (Interfaces) | EtherCAT®slave |
| Type of protection (Supply) | Overload protection |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Transmission speed (General) | 100 Mbps (with auto negotiation) |
| Number of positions (General) | 4 |
| Signal delay (Digital inputs) | max. 150 µs (when switched on) |
| Total sensor current (Supply) | max. 1.6 A (from L+/L-) |
| Connection technology (Supply) | 3-wire |
| Nominal input current (Supply) | typ. 3 mA |
| Test section (Digital outputs) | 24 V supply (communications power and sensor supply, IO-Link ports)/bus connection (Ethernet 1) 500 V AC 50 Hz 1 min. |
| Net weight (Ambient conditions) | 726.9 g |
| Switching rate (Digital inputs) | 1 per second, maximum (at nominal inductive load) |
| Type of addressing (Interfaces) | Auto-increment addressing |
| Degree of protection (Dimensions) | IP65/IP67 |
| Description of the input (Supply) | IO-Link ports in digital input (DI) mode |
| Connection method (Digital inputs) | M12 connector, X01 ... X04 have double occupancy |
| Mounting type (Ambient conditions) | Wall mounting or DIN rail mounting; both with mounting plate. |
| Nominal input voltage UIN (Supply) | 24 V DC |
| Number of outputs (Digital inputs) | max. 8 |
| Output description (Digital inputs) | IO-Link ports in digital output (DO) mode |
| Sensor current per channel (Supply) | max. 200 mA (from L+/L-) |
| Type of protection (Digital inputs) | Overload protection |
| Nominal load, ohmic (Digital inputs) | 3.6 W (160 Ω, at nominal load) |
| Weight per Piece (excluding packing) | 726.900 g |
| Air pressure (operation) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Housing material (Ambient conditions) | Zinc die-cast |
| Nominal input current at UIN (Supply) | typ. 3 mA |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 25; |
| Connection technology (Digital inputs) | 3-wire |
| Designation connection point (General) | Copper cable |
| System-specific protocols (Interfaces) | Mailbox protocols CANopen®over EtherCAT® |
| Behavior with overload (Digital inputs) | Shutdown with automatic restart |
| Input voltage range "0" signal (Supply) | -0.3 V DC ... 5 V DC |
| Input voltage range "1" signal (Supply) | 15 V DC ... 30 V DC |
| Mechanical tests (Electrical isolation) | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g |
| Nominal output voltage (Digital inputs) | 24 V DC |
| Note on the connection method (General) | D-coded |
| Protection class (Electrical isolation) | III, IEC 61140, EN 61140, VDE 0140-1 |
| Nominal load, inductive (Digital inputs) | 3.6 VA (0.8 H, 160 Ω, at nominal load) |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 60 °C |
| Air pressure (storage/transport) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % |
| Utilization restriction (Key Commercial Data) | 1 |
| Designation (System limits of the bus coupler) | Actuators (UA) |
| Output current when switched off (Digital inputs) | max. 300 µA |
| Output voltage when switched off (Digital inputs) | max. 1 V |
| Supply voltage (System limits of the bus coupler) | 24 V DC |
| Maximum output current per device (Digital inputs) | 1.2 A |
| Maximum output current per channel (Digital inputs) | 150 mA |
| Ambient temperature (storage/transport) (Dimensions) | -25 °C ... 85 °C |
| Connection method (System limits of the bus coupler) | M12 connector (T-coded) |
| Permissible humidity (storage/transport) (Dimensions) | 5 % ... 95 % |
| Current consumption (System limits of the bus coupler) | typ. 28 mA ±15 % (at 24 V DC) |
| Number of positions (System limits of the bus coupler) | 4 |
| Nominal supply voltage range (System limits of the bus coupler) | 18 V DC ... 31.2 V DC (including all tolerances, including ripple) |
| Limitation of the voltage induced on circuit interruption (Digital inputs) | -15 V DC |
Technical specifications and performance data