| Parameter | Value |
|---|---|
| GTIN | 4055626356280 |
| Orderkey | 2404267 |
| Depth (Note) | 75 mm |
| Packing unit | 1 pc |
| Width (Note) | 45 mm |
| (Dimensions) | > 55 °C ... 60 °C (only in conjunction with an Axioline F power module AXL F PWR 1H (order number 2688297)) |
| Height (Note) | 126.93 mm |
| (General data) | Eclipse |
| Country of origin | DE (Germany) |
| (Data interfaces) | min. 16 ms (64 devices) |
| Shock (Dimensions) | 30g, 11 ms period, half-sine shock pulse, according to IEC 60068-2-27 |
| Custom tariff number | 85371091 |
| RAM (Control system) | 512 Mbyte DDR3 SDRAM |
| (Ambient conditions) | Manufacturer-specific |
| Weight (Power supply) | 215 g |
| Shock (Mechanical design) | 30g, 11 ms period, half-sine shock pulse, according to IEC 60068-2-27 |
| Supply voltage (PROFINET) | 24 V DC |
| Number (Fieldbus function) | 2 |
| Processor (Control system) | ARM®Cortex®-A9 2x 800 MHz |
| (IEC 61131 runtime system) | max. 4096 Bit (Output) |
| Mass storage (General data) | 16 Mbyte |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Interface (Fieldbus function) | Ethernet |
| Program memory (General data) | 8 Mbyte |
| Realtime clock (General data) | Yes |
| Update rate (Data interfaces) | min. 1 ms (4 devices) |
| Safety function (Power supply) | No |
| Engineering tool (General data) | PLCnext Engineer |
| Specification (Data interfaces) | Version 2.3 |
| Supply voltage range (PROFINET) | 19.2 V DC ... 30 V DC |
| Degree of protection (Dimensions) | IP20 |
| Device function (Data interfaces) | PROFINET controller, PROFINET device |
| Operating system (Control system) | Linux |
| Diagnostics display (Power supply) | No |
| Immunity to EF (Mechanical design) | Noise immunity test in accordance with EN 61000-6-2 Electromagnetic fields EN 61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m |
| Vibration (operation) (Dimensions) | 5g |
| Immunity to ESD (Mechanical design) | Noise immunity test in accordance with EN 61000-6-2 Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2 Criterion B, 6 kV contact discharge, 8 kV air discharge |
| Max. current consumption (PROFINET) | 442 mA (with 1 A at UBusfor the I/Os and UL= 24 V) |
| Controller redundancy (Power supply) | No |
| Weight per Piece (excluding packing) | 387.000 g |
| Air pressure (operation) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Connection method (Fieldbus function) | RJ45 socket |
| Engineering tool (Ambient conditions) | PLCnext Engineer |
| Immunity to burst (Mechanical design) | Noise immunity test in accordance with EN 61000-6-2 Fast transients (burst) EN 61000-4-4/IEC 61000-4-4 Criterion B, 2 kV |
| Immunity to surge (Mechanical design) | Noise immunity test in accordance with EN 61000-6-2 Transient overvoltage (surge) EN 61000-4-5/IEC 61000-4-5 Criterion B, DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical), fieldbus cable shield: ±1 kV |
| Retentive mass storage (General data) | 48 kByte (NVRAM) |
| Shock (operation) (Mechanical design) | 10g (Bump endurance test according to EN 60068-2-29) |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Designation (IEC 61131 runtime system) | |
| Transmission speed (Fieldbus function) | 10/100 Mbps (full duplex) |
| Typical current consumption (PROFINET) | 200 mA (without I/Os and UL= 24 V) |
| Interference emission (Mechanical design) | Noise emission test as per EN 61000-6-4 Class A |
| Vibration (operation) (Mechanical design) | 5g |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 60 °C up to 2000 m above mean sea level (observe derating) |
| Air pressure (storage/transport) (Dimensions) | 58 kPa ... 106 kPa (up to 4500 m above mean sea level) |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % (according to DIN EN 61131-2) |
| Utilization restriction (Key Commercial Data) | EMC: class A product, see manufacturer's declaration in the download area |
| Amount of process data (IEC 61131 runtime system) | max. 8192 Bit (per station) |
| Electromagnetic compatibility (Mechanical design) | Conformance with EMC Directive 2014/30/EU |
| Vibration (storage/transport) (Mechanical design) | 5g |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Programming languages supported (Ambient conditions) | Programming in acc. with IEC 61131-3 |
| Permissible humidity (storage/transport) (Dimensions) | 5 % ... 95 % (according to DIN EN 61131-2) |
| Immunity to conducted interference (Mechanical design) | Noise immunity test in accordance with EN 61000-6-2 Conducted interference EN 61000-4-6/IEC 61000-4-6 Criterion A; Test voltage 10 V |
| Number of supported devices (IEC 61131 runtime system) | max. 63 (per station) |
| Number of local bus devices that can be connected (IEC 61131 runtime system) | max. 63 (observe current consumption) |
Technical specifications and performance data