| Parameter | Value |
|---|---|
| GTIN | 4017918959678 |
| Orderkey | 2736686 |
| Catalog page | Page 232 (C-6-2017) |
| Packing unit | 1 pc |
| (Output data) | 2 kV AC (routine test) |
| Country of origin | TH (Thailand) |
| Custom tariff number | 85044030 |
| (Ambient conditions) | > 80 ms (230 V AC) |
| Screw thread (General) | M3 |
| Efficiency (Output data) | > 86 % (for 230 V AC and nominal values) |
| Net weight (Output data) | 0.75 kg |
| Output power (Input data) | 72 W |
| (Connection data, output) | UL/C-UL Recognized UL 60950-1 |
| Stripping length (General) | 9 mm |
| Connection method (General) | Pluggable spring-cage connection |
| Depth (Key Commercial Data) | 125 mm |
| Width (Key Commercial Data) | 55 mm |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Height (Key Commercial Data) | 145 mm |
| Residual ripple (Input data) | < 30 mVPP |
| Input fuse (Ambient conditions) | 5 A (slow-blow, internal) |
| Mounting position (Output data) | horizontal DIN rail NS 35, EN 60715 |
| Signal (Connection data, output) | 1 kV (Test Level 2 - asymmetrical) |
| Connection in series (Input data) | yes |
| Degree of protection (Dimensions) | IP20 |
| Output voltage range (Input data) | 28 V DC ... 30 V DC |
| Voltage (Connection data, output) | 10 V (Test Level 3) |
| Comments (Connection data, output) | Criterion B |
| Degree of protection (Output data) | IP20 |
| Typical response time (Input data) | < 0.5 s |
| Assembly instructions (Output data) | alignable: horizontally 0 mm, vertically 50 mm |
| Connection in parallel (Input data) | No |
| Nominal output voltage (Input data) | 30.1 V DC ±1.5 % |
| Mains buffering (Ambient conditions) | > 20 ms (120 V AC) |
| Weight per Piece (excluding packing) | 750.000 g |
| Screw thread (Connection data, input) | M3 |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 25; |
| UL approvals (Connection data, output) | UL/C-UL listed UL 508 |
| AC frequency range (Ambient conditions) | 45 Hz ... 65 Hz |
| Frequency range DC (Ambient conditions) | 0 Hz |
| Operating voltage display (Output data) | LED |
| Current consumption (Ambient conditions) | approx. 1 A (120 V AC) |
| MTBF (IEC 61709, SN 29500) (Output data) | > 500000 h |
| Noise immunity (Connection data, output) | EN 61000-6-2:2005 |
| Nominal output current (IN) (Input data) | 2.4 A |
| Frequency range (Connection data, output) | 0.15 MHz ... 80 MHz |
| Inrush surge current (Ambient conditions) | < 15 A (typical) |
| Power loss nominal load max. (Input data) | 11 W |
| Conductor cross section AWG max. (General) | 14 |
| Conductor cross section AWG min. (General) | 24 |
| Connection method (Connection data, input) | Spring-cage connection |
| Contact discharge (Connection data, output) | 4 kV (Test Level 2) |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
| Conductor cross section solid max. (General) | 2.5 mm² |
| Conductor cross section solid min. (General) | 0.2 mm² |
| Insulation voltage input/output (Output data) | 4 kV AC (type test) |
| Test field strength (Connection data, output) | 3 V/m |
| Nominal power consumption (Ambient conditions) | 72 W |
| Conductor cross section flexible max. (General) | 2.5 mm² |
| Conductor cross section flexible min. (General) | 0.2 mm² |
| Low Voltage Directive (Connection data, output) | Conformance with LV directive 2006/95/EC |
| Standards/regulations (Connection data, output) | EN 61000-4-6 |
| Nominal input voltage range (Ambient conditions) | 100 V AC ... 240 V AC |
| Peak switching voltages nominal load (Input data) | < 50 mVPP |
| Standard - Safe isolation (Connection data, output) | DIN VDE 0100-410 |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Depth with alternative assembly (Key Commercial Data) | 58 mm |
| Width with alternative assembly (Key Commercial Data) | 122 mm |
| Height with alternative assembly (Key Commercial Data) | 145 mm |
| Standard - Electrical safety (Connection data, output) | EN 60950-1/VDE 0805 (SELV) |
| Electromagnetic compatibility (Connection data, output) | Conformance with EMC Directive 2004/108/EC |
| Choice of suitable circuit breakers (Ambient conditions) | 6 A ... 16 A (Characteristics B, C, D, K) |
| Conductor cross section AWG max. (Connection data, input) | 12 |
| Conductor cross section AWG min. (Connection data, input) | 24 |
| Connection in acc. with standard (Connection data, output) | CUL |
| Conductor cross section solid max. (Connection data, input) | 2.5 mm² |
| Conductor cross section solid min. (Connection data, input) | 0.2 mm² |
| Max. permissible relative humidity (operation) (Dimensions) | 95 % (at 25 °C, non-condensing) |
| Maximum power dissipation in no-load condition (Input data) | 3 W |
| Standard - Safety of transformers (Connection data, output) | EN 61558-2-17 |
| Conductor cross section flexible max. (Connection data, input) | 2.5 mm² |
| Conductor cross section flexible min. (Connection data, input) | 0.2 mm² |
| Standard – Limitation of mains harmonic currents (Connection data, output) | EN 61000-3-2 |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations (Connection data, output) | EN 50178/VDE 0160 (PELV) |
Technical specifications and performance data