| Parameter | Value |
|---|---|
| Customs Tariff Number: | 85364900 |
| Minimum Order Quantity: | 1 piece |
| Standards: (Dimensions) | Devices complying with international standards IEC 947-1 / 947-4-1, and European standards EN 60 947-1 / 60 947-4-1. Electromagnetic compatibility (EMC) acc. to amendment A11 to IEC 947-1; EN 60 947-1 and amendment 2 to IEC 947-4-1 |
| RoHS Status: (Technical) | Following EU Directive 2002/95/EC August 18, 2005 and amendment |
| Operate Time: (Dimensions) | Between Coil Energization and NO Contact Closing 8 ... 21 msBetween Coil De-energization and NO Contact Opening 4 ... 11 ms |
| Terminal Type: (Dimensions) | Screw Terminals |
| Coil Consumption: (Dimensions) | Average Holding Value 50 / 60 Hz 12 V·AAverage Holding Value 50 / 60 Hz 3 WAverage Pull-in Value 50 Hz 125 V·AAverage Pull-in Value 60 Hz 120 V·A |
| BV Certificate: (Environmental) | BV_2634H07559D0 |
| CB Certificate: (Environmental) | CB_FR_602227A |
| Climatic Withstand: (Technical) | acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II |
| ETIM 4: (Container Information) | EC000066 - Magnet contactor, AC-switching |
| ETIM 5: (Container Information) | EC000066 - Magnet contactor, AC-switching |
| ETIM 6: (Container Information) | EC000066 - Power contactor, AC switching |
| ETIM 7: (Container Information) | EC000066 - Power contactor, AC switching |
| LR Certificate: (Environmental) | LRS_9830011E4 |
| UL Certificate: (Environmental) | UL_071301E39231 |
| UNSPSC: (Container Information) | 39121529 |
| CCC Certificate: (Environmental) | CCC_2013010304615752CCC_2004010309133982 |
| CSA Certificate: (Environmental) | CSA_1033838_LR056745 |
| DNV Certificate: (Environmental) | DNV-GL_TAE00000TX |
| EAC Certificate: (Environmental) | EAC_RU C-FR ME77 B01010 |
| GOST Certificate: (Environmental) | GOST_POCCFRME77B07175 |
| RINA Certificate: (Environmental) | RINA_ELE128713XG001 |
| RMRS Certificate: (Environmental) | RMRS_0507015250 |
| Rated Frequency (f): (Dimensions) | Supply Circuit 50 HzSupply Circuit 60 Hz |
| RoHS Information: (Environmental) | 1SBD350054R1000 |
| Degree of Protection: (Dimensions) | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
| LOVAG Certificate: (Environmental) | LOVAG_FR97008 |
| DNV GL Certificate: (Environmental) | DNV-GL_TAE00000TX |
| Ambient Air Temperature: (Technical) | Close to Contactor Fitted with Thermal O/L Relay -25 ... +55 °CClose to Contactor for Storage -60 ... +80 °CClose to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... +55 °CClose to Contactor without Thermal O/L Relay (Uc) -40 ... +70 °C |
| Instructions and Manuals: (Ordering) | FPTC407722P0001 |
| Product Net Width: (Popular Downloads) | 54 mm |
| Maximum Breaking Capacity: (Dimensions) | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 820 Acos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 340 A |
| Product Net Height: (Popular Downloads) | 90 mm |
| Product Net Weight: (Popular Downloads) | 0.71 kg |
| Rated Operational Voltage: (Dimensions) | Main Circuit 690 V |
| Number of Main Contacts NC: (Dimensions) | 0 |
| Number of Main Contacts NO: (Dimensions) | 3 |
| Instructions and Manuals: (Environmental) | FPTC407722P0001 |
| Environmental Information: (Environmental) | 1SBD250005E1002 |
| Rated Insulation Voltage (Ui): (Dimensions) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 Vacc. to UL/CSA 600 V |
| Data Sheet, Technical Information: (Ordering) | 1SBC100122C0202_Ch02 |
| Number of Auxiliary Contacts NC: (Dimensions) | 0 |
| Number of Auxiliary Contacts NO: (Dimensions) | 1 |
| Connecting Capacity Main Circuit: (Dimensions) | Flexible with Cable End 2.5 ... 10 mm²Rigid Cable 2.5 ... 16 mm² |
| Short-Circuit Protective Devices: (Dimensions) | Auxiliary Circuit - gG Type Fuses 10 AgG Type Fuses 63 A |
| Declaration of Conformity - CE: (Environmental) | 1SBD250801U1000 |
| Product Net Depth / Length: (Popular Downloads) | 108.3 mm |
| Rated Operational Power AC-3 (Pe): (Dimensions) | (220 / 230 / 240 V) 9 kW(380 / 400 V) 15 kW(415 V) 15 kW(440 V) 18.5 kW(500 V) 18.5 kW(690 V) 18.5 kW |
| Rated Control Circuit Voltage (Uc): (Dimensions) | 50 Hz 110 V60 Hz 110 ... 120 V |
| Rated Operational Current AC-1 (Ie): (Dimensions) | (690 V) 40 °C 55 A(690 V) 55 °C 55 A(690 V) 70 °C 39 A |
| Rated Operational Current AC-3 (Ie): (Dimensions) | (220 / 230 / 240 V) 55 °C 33 A(380 / 400 V) 55 °C 32 A(415 V) 55 °C 32 A(440 V) 55 °C 32 A(500 V) 55 °C 28 A(690 V) 55 °C 21 A |
| Rated Operational Current AC-15 (Ie): (Dimensions) | (220 / 240 V) 4 A(24 / 127 V) 6 A(380 / 440 V) 3 A(500 V) 2 A(690 V) 2 A |
| Rated Operational Current DC-13 (Ie): (Dimensions) | (125 V) 1.1 / 138 A(24 V) 6 / 144 A(250 V) 0.55 / 138 A(48 V) 2.8 / 134 A(72 V) 2 / 144 A |
| Connecting Capacity Auxiliary Circuit: (Dimensions) | Flexible with Cable End 0.75 ... 2.5 mm²Rigid Cable 1 ... 4 mm² |
| Maximum Operating Altitude Permissible: (Technical) | 3000 m |
| Object Classification Code: (Container Information) | Q |
| Maximum Electrical Switching Frequency: (Dimensions) | AC-1 600 cycles per hourAC-2 / AC-4 300 cycles per hourAC-3 1200 cycles per hour |
| Maximum Mechanical Switching Frequency: (Dimensions) | 3600 cycles per hour |
| Rated Impulse Withstand Voltage (Uimp): (Dimensions) | 8 kV |
| Resistance to Shock acc. to IEC 60068-2-27: (Technical) | Shock Direction: A 20 gClosed, Shock Direction: B1 10 gOpen, Shock Direction: B1 5 gShock Direction: B2 15 gShock Direction: C1 20 gShock Direction: C2 20 g |
| Conventional Free-air Thermal Current (Ith): (Dimensions) | acc. to IEC 60947-4-1, Open Contactors q = 40 °C 65 Aacc. to IEC 60947-5-1, q = 40 °C 16 A |
| Rated Making Capacity AC-3 acc. to IEC 60947-4-1: (Dimensions) | 10 x Ie AC-3 |
| Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1: (Dimensions) | 8 x Ie AC-3 |
| Package Level 1 EAN: (Certificates and Declarations (Document Number)) | 3471522071842 |
| Package Level 1 Units: (Certificates and Declarations (Document Number)) | 1 piece |
| Package Level 1 Width: (Certificates and Declarations (Document Number)) | 101 mm |
| Package Level 2 Units: (Certificates and Declarations (Document Number)) | 63 piece |
| Package Level 3 Units: (Certificates and Declarations (Document Number)) | 576 piece |
| Package Level 1 Height: (Certificates and Declarations (Document Number)) | 61 mm |
| Connecting terminals (delivered in open position) Main poles: (Dimensions) | M 5 (+,-) pozidriv 2 screw with 2x (5.6x6.5 mm) connector |
| Package Level 1 Gross Weight: (Certificates and Declarations (Document Number)) | 0.71 kg |
| Package Level 2 Gross Weight: (Certificates and Declarations (Document Number)) | 44.73 kg |
| Package Level 1 Depth / Length: (Certificates and Declarations (Document Number)) | 115 mm |
Technical specifications and performance data
Installation and operation guide