| Parameter | Value |
|---|---|
| EAN | 4001869524580 |
| UPC | Not available |
| ETIM | 5 |
| Notes | Sucessor:7KM5412-6BA00-1EA2 - The replacement device has more features |
| depth | 147.9 mm |
| width | 96 mm |
| UNSPSC | 14 |
| eClass | 6 |
| height | 96 mm |
| Group Code | P360 |
| net weight | 807 g |
| ● maximum | 831 V |
| ● minimum | 1 % |
| Confirmation | |
| Metal Factor | None |
| Date5/12/2022 | Subject to change without notice© Copyright Siemens 2022 |
| Product Group | 5311 |
| Product class | B: return restricted, please contact your Siemens partner/contact |
| Quantity Unit | 1 Piece |
| voltage curve | Sinusoidal or distorted |
| Commodity Code | 90303100 |
| Product family | SENTRON 7KM PAC Measuring Devices |
| number of keys | 4 |
| output current | |
| pulse duration | |
| Net Weight (kg) | 0,854 Kg |
| product function | |
| ● set at 50 Hz | No |
| ● set to 60 Hz | No |
| Country of origin | India |
| mounting position | vertical |
| ● initial value | 45 Hz |
| LKZ_FDB/ CatalogID | LV10.1 |
| PLM Effective Date | Product phase-out since: 14.10.2021 |
| Packaging Quantity | 1 |
| installation depth | 102.9 mm |
| measurable current | |
| product brand name | SENTRON |
| Packaging Dimension | 140,00 x 112,00 x 155,00 |
| Product Description | SENTRON, measuring device, 7KM PAC5100, LCD, L-L: 690 V, L-N: 400 V, 10 A, 3-phase, Modbus TCP, apparent/active/ reactive energy / cos phi, harmonics: 2. - 40., THD, class 0.5 acc to IEC61557- 12 or cl. 0.5S acc. to IEC62053-22, wide-range pwr sup. unit AC/DC, screw terminals |
| degree of pollution | 2 |
| measuring procedure | |
| product designation | 7KM PAC5100 |
| Voltmeter (EF006560) | false |
| width of the display | 72 mm |
| ● full-scale value | 65 Hz |
| design of the display | LCD |
| design of the product | compact |
| height of the display | 54 mm |
| digital output version | Continuous output, pulse output |
| Ampere meter (EF006555) | false |
| Product Lifecycle (PLM) | PM400:Phase Out Started |
| ● 1 at AC rated value | 5 A |
| ● 2 at AC rated value | 5 A |
| ● current measurement | Yes |
| ● voltage measurement | Yes |
| General Product Approval | Declaration of Conformity |
| Pulse counter (EF006559) | false |
| number of digital inputs | 0 |
| product type designation | Measuring instrument |
| type of switching output | solid state |
| measurable line frequency | |
| number of digital outputs | 2 |
| suitability for operation | Installation in stationary control panels in closed rooms |
| ● frequency measurement | Yes |
| Export Control Regulations | AL : N / ECCN : EAR99 |
| Frequency meter (EF006558) | false |
| design of the power supply | Wide-range power supply |
| Standard lead time ex-works | 2 Day/Days |
| Surcharge for Raw Materials | None |
| display contrast adjustable | Yes |
| ● for current measurement | TRMS |
| ● for voltage measurement | TRMS |
| Blind power meter (EF006556) | false |
| Package size unit of measure | MM |
| ● active power measurement | Yes |
| type of electrical connection | |
| adjustable time period minimum | 50 ms |
| ● reactive power measurement | Yes |
| size of Power Monitoring Device | size 96 |
| protection class IP on the front | IP40 |
| type of measured value detection | complete |
| relative measurable current at AC | |
| ● for measured variable current | +/- 0,2 % |
| ● for measured variable voltage | +/- 0,2 % |
| ● for neutral conductor current | 0.0 % to 10.0 % (from Vrated, Irated) |
| ambient temperature during storage | |
| ambient temperature during operation | |
| Article Number (Market Facing Number) | 7KM5212-6BA00-1EA2 |
| type of voltage of the supply voltage | AC/DC |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| With rotational speed meter (EF006557) | false |
| color of the background of the display | white |
| measuring category for digital signals | Cat. III |
| fastening method standard rail mounting | No |
| ● for measured variable active energy | Cl. 0.5 acc. to... IEC62053-22 |
| ● for measured variable output factor | +/- 0,5 % |
| reference condition for metering accuracy | according to IEC 62053-22, IEC 62053-23, IEC 62586-1, Class S, IEC 61000-4-30, IEC 61000-4-7, IEC 61000-4-15 |
| ● at the measurement inputs for current | screw-type terminals |
| ● at the measurement inputs for voltage | screw-type terminals |
| ● for measured variable reactive energy | Class 2 according to IEC61557-12 and/or IEC62053-23 |
| internal resistance at the digital outputs | 35 Ω |
| measuring category for current measurement | CATIII |
| measuring category for voltage measurement | CATIII |
| property of the output short-circuit proof | Yes |
| illuminance of display backlight adjustable | Yes |
| operating mode for measured value detection | |
| type of connectable conductor cross-sections | |
| ● at digital output for signal <1> maximum | 300 mA |
| Effective power measurement device (EF006561) | false |
| switching frequency at digital output maximum | 10 Hz |
| zero point suppression for current measurement | 0 ... 10 % |
| number of interfaces according to Fast Ethernet | 1 |
| ● at the measurement inputs for voltage solid | 2.5 mm² |
| formula for relative total measurement inaccuracy | |
| operating resource protection class when installed | safety class II |
| Region Specific PriceGroup / Headquarter Price Group | 15N / 1DD |
| national language on the display screen is supported | de, en |
| type of electrical connection at the digital outputs | screw-type terminals |
| installation altitude at height above sea level maximum | 2 000 m |
| certificate of suitability as EC Declaration of Conformity | EN 61000-6-2 and EN 61000-6-4 for EMC guideline |
| measurable supply voltage between the line conductors at AC | |
| type of electrical connection of the fast Ethernet interface | RJ45 (8P8C) |
| operating voltage as output voltage at DC maximum permissible | 250 V |
| ● at the measurement inputs for current at AWG cables solid | Screw connection |
| ● at the measurement inputs for voltage at AWG cables solid | Screw connection |
| current measuring range extension with external current transformers | yes |
| voltage measuring range extension with external voltage transformers | yes |
| Compliance with the substance restrictions according to RoHS directive | Since: 14.05.2015 |
| measurable supply voltage between (PE)N and L at AC maximum rated value | 400 V |
| REACH Art. 33 Duty to inform according to the current list of candidates | Reach InformationThere is currently no information on SVHC (Substances of Very High Concern http://echa.europa.eu/web/guest/candidate-list-table) from the supply chain and our established procedures for screening our products for Substances of Very High Concern.We compare our products regularly with the information of the upstream users with regard to the substances indicated in the candidate list in accordance with the requirements of the REACH regulation. As soon as we have new findings, our information will be updated accordingly. |
| relative humidity at 25 °C without condensation during operation maximum | 95 % |
| time-controlled reduction of the illuminance of display backlight possible | Yes |
| operating mode for measured value detection automatic line frequency detection | Yes |
| measurable supply voltage between the line conductors at AC maximum rated value | 690 V |
| line conductors and neutral conductors internal resistance for voltage measurement | 6 MΩ |
| ● at the measurement inputs for voltage finely stranded with core end processing | 2.5 mm² |
| General Product ApprovalDeclaration of ConformityotherDangerous GoodConfirmationUK Declaration of ConformityMiscellaneousDangerous Goods Information | General Product Approval |
Technical specifications and performance data