| Parameter | Value |
|---|---|
| Value | |
| EAN | 4025515152743 |
| UPC | 040892600230 |
| Input | 1-phase AC or DC |
| Notes | For this product a successor is available6EP3321-6SB00-0AY0This product is a Spare Part, please visit the Spares & Service section for more informationIf you need assistance please contact our local Siemens office |
| Output | Controlled, isolated DC voltage |
| CE mark | Yes |
| ● top | 20 mm |
| — Note | with natural convection |
| ● Note | +55 ... +70 °C: Derating 2%/K |
| ● left | 0 mm |
| Successor | 6EP3321-6SB00-0AY0 |
| ● at DC | 110 ... 300 V |
| ● right | 0 mm |
| Group Code | R315 |
| I²t, max. | 0.8 A²·s |
| ● Output | +, -: 2 screw terminals each for 0.5 ... 2.5 mm² |
| ● bottom | 20 mm |
| CB approval | Yes |
| Connections | |
| FM approval | Class I, Div. 2, Group ABCD, T4 |
| Price Group | 5ZT |
| ● maximum | 3.6 A |
| Installation | Snaps onto DIN rail EN 60715 35x7.5/15 |
| Metal Factor | None |
| Current range | 0 ... 1.9 A |
| Input current | |
| Input voltage | |
| Product Group | 4741 |
| Product class | A: Standard product which is a stock item could be returned within the returns guidelines/period. |
| Quantity Unit | 1 Piece |
| ● Auxiliary | - |
| Commodity Code | 85044090 |
| MTBF at 40 °C | 3 593 503 h |
| Noise immunity | EN 61000-6-2 |
| Product family | Not available |
| Status display | Green LED for output voltage OK |
| Mains buffering | at Vin = 187 V |
| Marine approval | ABS, GL |
| Net Weight (kg) | 0,170 Kg |
| On/off behavior | No overshoot of Vout (soft start) |
| Weight, approx. | 0.17 kg |
| Adjustment range | 10.5 ... 16.1 V |
| Depth (EF000049) | 52.6 |
| Protection class | Class II (without protective conductor) |
| Rated line range | 47 ... 63 Hz |
| Required spacing | |
| Voltage range AC | 85 ... 264 V |
| Wide-range input | Yes |
| Width (EF000008) | 54.0 |
| ● Supply input | L, N: 1 screw terminal each for 0.5 ... 2.5 mm2 single-core/finely stranded |
| Country of origin | Austria |
| Height (EF000040) | 90.0 |
| Other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
| Galvanic isolation | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 |
| LKZ_FDB/ CatalogID | KT10-PH |
| PLM Effective Date | Product is cancelled since: 13.12.2018 |
| Packaging Quantity | 1 |
| Voltage rise, typ. | 10 ms |
| ● during storage | -40 ... +85 °C |
| Ambient temperature | |
| Packaging Dimension | 7,00 x 9,00 x 5,80 |
| Product Description | LOGO!Power 12 V/1.9 A Stabilized power supply input: 100-240 V AC (DC 110-300 V) output: 12 V/1.9 A; |
| Startup delay, max. | 0.5 s |
| Emitted interference | EN 55022 Class B |
| Explosion protection | ATEX (EX) II 3G Ex nA IIC T3; cCSAus (CSA C22.2 No. 213-M1987, ANSI/ISA-12.12.01-2007) Class I, Div. 2, Group ABCD, T4 |
| ● during operation | -20 ... +70 °C |
| ● during transport | -40 ... +85 °C |
| Connection technology | screw-type terminals |
| Rated voltage Vout DC | 12 V |
| Stabilized (EF005302) | - |
| Successor Description | LOGO!POWER 12 V / 1.9 A Stabilized power supply input: 100-240 V AC output: 12 V DC/ 1.9 A |
| UL/cUL (CSA) approval | cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File E151273, NEC class 2 (acc. to UL 1310) |
| Built-in incoming fuse | internal |
| Depth of the enclosure | 52.6 mm |
| Output voltage setting | via potentiometer |
| Overvoltage resistance | 2.3 × Vin rated, 1.3 ms |
| Rated line frequency 1 | 50 Hz |
| Rated line frequency 2 | 60 Hz |
| Width of the enclosure | 54 mm |
| Height of the enclosure | 90 mm |
| Power output (EF003034) | 23.0 |
| Product Lifecycle (PLM) | PM410:Product cancellation |
| Current limitation, typ. | 2.8 A |
| Short-circuit protection | Constant current characteristic |
| Built-in width (EF000846) | 54.0 |
| Built-in height (EF000332) | 130.0 |
| Export Control Regulations | ECCN : N / AL : N |
| Modular version (EF001126) | true |
| Total tolerance, static ± | 3 % |
| Primary/secondary isolation | Yes |
| Standard lead time ex-works | On request |
| Supply harmonics limitation | not applicable |
| Surcharge for Raw Materials | None |
| Package size unit of measure | CM |
| Power consumption (EF000346) | - |
| Output overvoltage protection | Yes, according to EN 60950-1 |
| Rated voltage value Vin rated | 100 ... 240 V |
| Supplied active power typical | 23 W |
| Product Dimensions (W x L x H) | Not available |
| Rated current value Iout rated | 1.9 A |
| Short-circuit-proof (EF007332) | true |
| Static load balancing, approx. | 1.5 % |
| Degree of protection (EN 60529) | IP20 |
| Residual ripple peak-peak, max. | 200 mV |
| Residual ripple peak-peak, typ. | 10 mV |
| Max. output current 1 (EF008284) | 1.9 |
| Max. output current 2 (EF008285) | - |
| Max. output current 3 (EF008286) | - |
| Overload/short-circuit indicator | - |
| ● at rated input voltage 120 V | 0.53 A |
| ● at rated input voltage 230 V | 0.3 A |
| Rail mounting possible (EF003972) | - |
| Wall mounting possible (EF003973) | - |
| Static mains compensation, approx. | 0.1 % |
| Direct mounting possible (EF005689) | false |
| Mains buffering at Iout rated, min. | 40 ms; at Vin = 187 V |
| Degree of protection (IP) (EF005474) | IP20 |
| Humidity class according to EN 60721 | Climate class 3K3, 5 … 95% no condensation |
| Output voltage stabilized (EF003092) | - |
| Article Number (Market Facing Number) | 6EP1321-1SH03 |
| Rated supply voltage at DC (EF007078) | - |
| SIL according to IEC 61508 (EF009889) | - |
| Degree of protection (NEMA) (EF011959) | - |
| Load step setting time 10 to 90%, typ. | 1 ms |
| Load step setting time 90 to 10%, typ. | 1 ms |
| Type of electric connection (EF003961) | Screw connection |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| 1st secondary output voltage (EF006792) | ['12', '12'] |
| 2nd secondary output voltage (EF006797) | - |
| 3rd secondary output voltage (EF006800) | - |
| Secondary voltage adjustable (EF007002) | true |
| Enduring short circuit current RMS value | |
| Suitable for safety functions (EF001597) | - |
| Nominal value output current 1 (EF009396) | 1.9 |
| Nominal value output current 2 (EF009397) | - |
| Nominal value output current 3 (EF009398) | - |
| Nominal value output voltage 1 (EF009393) | - |
| Nominal value output voltage 2 (EF009394) | - |
| Nominal value output voltage 3 (EF009395) | - |
| Voltage type of supply voltage (EF002991) | AC/DC |
| Product function output voltage adjustable | Yes |
| Property of the output Short-circuit proof | Yes |
| Spikes peak-peak, max. (bandwidth: 20 MHz) | 300 mV |
| Spikes peak-peak, typ. (bandwidth: 20 MHz) | 20 mV |
| Switch-on current limiting (+25 °C), max. | 25 A |
| Parallel switching for enhanced performance | Yes |
| Rated supply voltage at AC 50 Hz (EF007076) | ['240', '240'] |
| Rated supply voltage at AC 60 Hz (EF007077) | ['100', '100'] |
| Efficiency at Vout rated, Iout rated, approx. | 80 % |
| Power loss at Vout rated, Iout rated, approx. | 5 W |
| Protection in the mains power input (IEC 898) | Recommended miniature circuit breaker: from 6 A characteristic B or from 2 A characteristic C |
| Width in number of modular spacings (EF002950) | - |
| Power loss [W] during no-load operation maximum | 1.8 W |
| Dynamic mains compensation (Vin rated ±15 %), max. | 0.2 % |
| Dynamic load smoothing (Iout: 10/90/10 %), Uout ± typ. | 3 % |
| Performance level according to EN ISO 13849-1 (EF007399) | - |
| Numbers of parallel switchable units for enhanced performance | 2 |
| Product feature of the enclosure housing for side-by-side mounting | Yes |
| Compliance with the substance restrictions according to RoHS directive | Since: 01.07.2006 |
| REACH Art. 33 Duty to inform according to the current list of candidates | Lead CAS-No. 7439-92-1 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):LeadBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. |
Technical specifications and performance data
Installation and operation guide