| Parameter | Value |
|---|---|
| UK Declaration of Conformity | |
| EAN | 4001869429830 |
| EMC | Declaration of Conformity |
| UPC | Not available |
| depth | 70 mm |
| width | 36 mm |
| height | 90 mm |
| Railway | Dangerous Good |
| Group Code | P310 |
| net weight | 200 g |
| ● maximum | 5.4 W |
| ● minimum | 0.75 mm² |
| Confirmation | |
| Date5/5/2022 | |
| Metal Factor | L-A----- |
| Product Group | 5510 |
| Product class | A: Standard product which is a stock item could be returned within the returns guidelines/period. |
| Quantity Unit | 1 Piece |
| Commodity Code | 85362010 |
| Product family | Not available |
| power loss [W] | |
| Net Weight (kg) | 0,197 Kg |
| number of poles | 2 |
| fastening method | DIN rail (REG) |
| Country of origin | Germany |
| mounting position | any |
| LKZ_FDB/ CatalogID | LV10.1 |
| Packaging Quantity | 1 |
| installation depth | 70 mm |
| product brand name | SENTRON |
| Packaging Dimension | 97,00 x 42,00 x 85,00 |
| Product Description | Residual current operated circuit breaker, 2-pole, Type AC, In: 63 A, 100 mA, Un AC: 230 V |
| operational current | |
| product designation | RCCB |
| protection class IP | IP20, if the distribution board is installed, with connected conductors |
| Frequency (EF005455) | 50 Hz |
| overvoltage category | III |
| design of the product | Instantaneous |
| residual current type | AC |
| I2t value / permissible | 110 000 A²·s |
| Product Lifecycle (PLM) | PM300:Active Product |
| ● at AC / rated value | 63 A |
| ● maximum permissible | 75 °C |
| ● minimum permissible | -40 °C |
| Rated current (EF000227) | 63 |
| Rated voltage (EF000228) | 230 |
| Built-in depth (EF000218) | 70.0 |
| Export Control Regulations | ECCN : EAR99 / AL : N |
| Mounting method (EF000003) | DIN rail |
| Number of poles (EF001391) | 2 |
| switching capacity current | |
| Pollution degree (EF002570) | - |
| Standard lead time ex-works | 70 Day/Days |
| Surcharge for Raw Materials | None |
| ● at 40 °C / rated value | 63 A |
| ● at 45 °C / rated value | 63 A |
| ● at 50 °C / rated value | 63 A |
| ● at 55 °C / rated value | 63 A |
| ● at 60 °C / rated value | 63 A |
| ● at 65 °C / rated value | 56.96 A |
| ● at 70 °C / rated value | 48.2 A |
| Package size unit of measure | MM |
| short-circuit current rating | 10 kA |
| number of modular width units | 2 |
| Rated fault current (EF002358) | 0.1 |
| product feature / silicon-free | Yes |
| Leakage current type (EF002560) | AC |
| Selective protection (EF002561) | false |
| position / of power supply cord | top or bottom |
| Surge current capacity (EF002564) | - |
| let-through current / permissible | 7 100 A |
| With interlocking device (EF007385) | true |
| Degree of protection (IP) (EF005474) | IP20 |
| ambient temperature / during storage | |
| tripping fault current / rated value | 100 mA |
| Article Number (Market Facing Number) | 5SV4416-0 |
| Rated insulation voltage Ui (EF001366) | - |
| Short-time delayed tripping (EF003604) | false |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| ambient temperature / during operation | |
| switching function / short-term delayed | No |
| Additional equipment possible (EF008148) | true |
| value range / of the operating frequency | 50 Hz |
| ● according to IEC 61008-1 / rated value | 0.8 kA |
| connectable conductor cross-section / solid | |
| value range / of the supply voltage / at AC | 230/400 V |
| tightening torque / with screw-type terminals | |
| value range / of the supply voltage frequency | 50 Hz |
| Width in number of modular spacings (EF002950) | 2 |
| connectable conductor cross-section / stranded | |
| Ambient temperature during operating (EF007515) | ['-25', '45'] |
| Rated impulse withstand voltage Uimp (EF011980) | - |
| Short-circuit breaking capacity (Icw) (EF002562) | 10.0 |
| supply voltage / for testing equipment / minimum | 100 V |
| Region Specific PriceGroup / Headquarter Price Group | 194 / 1AI |
| mechanical service life (switching cycles) / typical | 10 000 |
| size of installation devices / according to DIN 43880 | 1 |
| product extension / installable / supplementary devices | Yes |
| Connectable conductor cross section solid-core (EF007337) | ['0.75', '35.0'] |
| Connectable conductor cross section multi-wired (EF007343) | ['0.75', '35.0'] |
| short-circuit current / of series fuse / maximum permissible | 80 A |
| Compliance with the substance restrictions according to RoHS directive | Since: 01.06.2006 |
| REACH Art. 33 Duty to inform according to the current list of candidates | Lead CAS-No. 7439-92-1 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):LeadBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.Lead monoxide (lead ... CAS-No. 1317-36-8 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):Lead monoxide (lead oxide)Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. |
| ● for rated value of the current / at AC / in hot operating state / per pole | 2.7 W |
| number of test cycles / for environmental testing / according to IEC 60068-2-30 | 28 |
| General Product ApprovalConfirmationMiscellaneousEMCDeclaration of ConformityTest CertificatesotherUK Declaration of ConformityMiscellaneousMiscellaneousEnvironmental ConfirmationsRailwayDangerous GoodConfirmationVibration and ShockTransport Information | General Product Approval |
Technical specifications and performance data
Installation and operation guide