| Parameter | Value |
|---|---|
| Miscellaneous | |
| EAN | 4001869500652 |
| UPC | Not available |
| ETIM | 5 |
| depth | 70 mm |
| width | 72 mm |
| UNSPSC | 15 |
| eClass | 6 |
| height | 90 mm |
| Group Code | P310 |
| net weight | 350 g |
| ● maximum | 5.4 W |
| ● minimum | 0.75 mm² |
| Confirmation | |
| Date5/2/2022 | |
| Metal Factor | L-A----- |
| Product Group | 5511 |
| Product class | A: Standard product which is a stock item could be returned within the returns guidelines/period. |
| Quantity Unit | 1 Piece |
| Commodity Code | 85362010 |
| Product family | RCCBs |
| power loss [W] | |
| supply voltage | |
| Net Weight (kg) | 0,376 Kg |
| number of poles | 4 |
| fastening method | DIN rail (REG) |
| Country of origin | Germany |
| mounting position | any |
| LKZ_FDB/ CatalogID | LV10.1 |
| Packaging Quantity | 1 |
| installation depth | 70 mm |
| product brand name | SENTRON |
| product variations | With thermal overload protection |
| Packaging Dimension | 97,00 x 78,00 x 85,00 |
| Product Description | Residual current operated circuit breaker, 4-pole, Type A, selective, In: 40 A, 100 mA, Un AC: 400 V, with thermal overload protection |
| operating frequency | 50/60 Hz |
| operational current | |
| product designation | RCCB |
| protection class IP | IP20, if the distribution board is installed, with connected conductors |
| overvoltage category | III |
| design of the product | Selective |
| residual current type | A |
| I2t value / permissible | 58 000 A²·s |
| Product Lifecycle (PLM) | PM300:Active Product |
| ● at AC / rated value | 400 V |
| ● maximum permissible | 75 °C |
| ● minimum permissible | -40 °C |
| General Product Approval | Declaration of Conformity |
| Declaration of Conformity | Test Certificates |
| Export Control Regulations | AL : N / ECCN : EAR99 |
| switching capacity current | |
| Standard lead time ex-works | 70 Day/Days |
| Surcharge for Raw Materials | None |
| ● at 40 °C / rated value | 40 A |
| ● at 45 °C / rated value | 40 A |
| ● at 50 °C / rated value | 40 A |
| ● at 55 °C / rated value | 40 A |
| ● at 60 °C / rated value | 40 A |
| ● at 65 °C / rated value | 40 A |
| ● at 70 °C / rated value | 40 A |
| Package size unit of measure | MM |
| short-circuit current rating | 10 kA |
| number of modular width units | 4 |
| product feature / silicon-free | Yes |
| position / of power supply cord | top or bottom |
| let-through current / permissible | 5 200 A |
| ● for testing equipment / minimum | 100 V |
| ambient temperature / during storage | |
| tripping fault current / rated value | 100 mA |
| Article Number (Market Facing Number) | 5SV3444-8LA |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| ambient temperature / during operation | |
| supply voltage frequency / rated value | 50 Hz |
| surge current resistance / rated value | 5 kA |
| switching function / short-term delayed | No |
| value range / of the operating frequency | 50/60 Hz |
| ● according to IEC 61008-1 / rated value | 0.8 kA |
| connectable conductor cross-section / solid | |
| value range / of the supply voltage / at AC | 230/400 V |
| tightening torque / with screw-type terminals | |
| value range / of the supply voltage frequency | 50 Hz |
| connectable conductor cross-section / stranded | |
| Region Specific PriceGroup / Headquarter Price Group | 11C / 1AH |
| mechanical service life (switching cycles) / typical | 10 000 |
| size of installation devices / according to DIN 43880 | 1 |
| product extension / installable / supplementary devices | Yes |
| short-circuit current / of series fuse / maximum permissible | 100 A |
| Compliance with the substance restrictions according to RoHS directive | Since: 01.01.2014 |
| REACH Art. 33 Duty to inform according to the current list of candidates | Lead CAS-No. 7439-92-1 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):LeadBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.Silicic acid, lead s... CAS-No. 11120-22-2 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):Silicic acid, lead saltBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.Lead monoxide (lead ... CAS-No. 1317-36-8 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):Lead monoxide (lead oxide)Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.2-methyl-1-(4-methyl... CAS-No. 71868-10-5 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):2-methyl-1-(4-methylthiophenyl)-2-morpholinopropan-1-oneBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. |
| ● for rated value of the current / at AC / in hot operating state / per pole | 1.8 W |
| number of test cycles / for environmental testing / according to IEC 60068-2-30 | 28 |
| General Product ApprovalDeclaration of ConformityConfirmationMiscellaneousUK Declaration of ConformityDeclaration of ConformityTest CertificatesotherRailwayDangerous GoodMiscellaneousMiscellaneousConfirmationVibration and ShockTransport Information | General Product Approval |
Technical specifications and performance data
Installation and operation guide