| Parameter | Value |
|---|---|
| VersionClassificationeClass627-13-08-05eClass7.127-13-08-05eClass827-13-08-05eClass927-13-08-05eClass9.127-13-08-05ETIM5EC000941ETIM6EC000941ETIM7EC000941ETIM8EC000941 | |
| EAN | 4001869340616 |
| UPC | Not available |
| ETIM | 5 |
| eClass | 6 |
| Group Code | P310 |
| Metal Factor | L-P----- |
| Product Group | 5524 |
| Product class | B: return restricted, please contact your Siemens partner/contact |
| Quantity Unit | 1 Piece |
| Commodity Code | 85363090 |
| Product family | Basic devices |
| Net Weight (kg) | 0,372 Kg |
| Country of origin | Germany |
| LKZ_FDB/ CatalogID | LV10.1 |
| Packaging Quantity | 1 |
| Packaging Dimension | 95,00 x 57,00 x 83,00 |
| Product Description | Surge arrester Type 2 Requirement class C, UC 350V Pluggable protective modules 3-pole, 3+0 circuit for TNC systems with remote display |
| Product Lifecycle (PLM) | PM300:Active Product |
| Category type 2 (EF004230) | true |
| Export Control Regulations | AL : N / ECCN : N |
| Max. PV-voltage (EF008795) | - |
| Mounting method (EF000003) | DIN rail (top hat rail) 35 mm |
| Standard lead time ex-works | 5 Day/Days |
| Surcharge for Raw Materials | None |
| Construction size (EF002566) | 3 modular spacing |
| Package size unit of measure | MM |
| Nominal voltage AC (EF004220) | - |
| Nominal voltage DC (EF004221) | - |
| Integrated backup fuse (EF008797) | false |
| System configuration DC (EF009926) | 0 |
| System configuration IT (EF009927) | 0 |
| System configuration TN (EF009928) | 0 |
| System configuration TT (EF009931) | 0 |
| Signalling at the device (EF004241) | Optic |
| Voltage protection level (EF003525) | 1400.0 |
| Degree of protection (IP) (EF005474) | IP20 |
| System configuration TN-C (EF009929) | 1 |
| System configuration TN-S (EF009930) | 0 |
| Article Number (Market Facing Number) | 5SD7463-1 |
| Max. continuous voltage AC (EF004198) | 350 |
| Max. continuous voltage DC (EF004777) | - |
| System configuration other (EF009932) | 0 |
| System configuration TN-C-S (EF009933) | 0 |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| Voltage protection level L-N (EF004236) | - |
| Voltage protection level N-PE (EF008796) | - |
| With remote signalling contact (EF000422) | true |
| Max. discharge surge current (8/20) (EF012274) | - |
| Nominal discharge surge current (8/20) (EF004214) | 40.0 |
| Number of conductors (without earthing) (EF001148) | - |
| Short-circuit breaking capacity (Isccr) (EF012627) | 25.0 |
| Region Specific PriceGroup / Headquarter Price Group | 12G / 1BK |
| Max. conductor cross section flexible (fine-strand) (EF008828) | 25.0 |
| Max. conductor cross section solid (solid, stranded) (EF008827) | 35.0 |
| Compliance with the substance restrictions according to RoHS directive | Since: 01.07.2006 |
| REACH Art. 33 Duty to inform according to the current list of candidates | Lead CAS-No. 7439-92-1 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):LeadBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. |
Technical specifications and performance data
Installation and operation guide