| Parameter | Value |
|---|---|
| VersionClassificationeClass627-13-08-05eClass7.127-13-08-05eClass827-13-08-05eClass927-13-08-05eClass9.127-13-08-05ETIM5EC000941ETIM6EC000941ETIM7EC000941ETIM8EC000941 | |
| EAN | 4001869340609 |
| UPC | Not available |
| ETIM | 5 |
| eClass | 6 |
| Group Code | P310 |
| Metal Factor | L-P----- |
| Product Group | 5524 |
| Product class | B: return restricted, please contact your Siemens partner/contact |
| Quantity Unit | 1 Piece |
| Commodity Code | 85363090 |
| Product family | Basic devices |
| Net Weight (kg) | 0,361 Kg |
| Country of origin | Germany |
| LKZ_FDB/ CatalogID | LV10.1 |
| Packaging Quantity | 1 |
| Packaging Dimension | 95,00 x 57,00 x 83,00 |
| Product Description | Surge arrester Type 2 Requirement class C, UC 350V Pluggable protective modules 3-pole, 3+0 circuit for TNC systems |
| Product Lifecycle (PLM) | PM300:Active Product |
| Category type 2 (EF004230) | true |
| Export Control Regulations | AL : N / ECCN : N |
| Max. PV-voltage (EF008795) | - |
| Mounting method (EF000003) | DIN rail (top hat rail) 35 mm |
| Standard lead time ex-works | 2 Day/Days |
| Surcharge for Raw Materials | None |
| Construction size (EF002566) | 3 modular spacing |
| Package size unit of measure | MM |
| Nominal voltage AC (EF004220) | - |
| Nominal voltage DC (EF004221) | - |
| Integrated backup fuse (EF008797) | false |
| System configuration DC (EF009926) | 0 |
| System configuration IT (EF009927) | 0 |
| System configuration TN (EF009928) | 0 |
| System configuration TT (EF009931) | 0 |
| Signalling at the device (EF004241) | None |
| Voltage protection level (EF003525) | 1400.0 |
| Degree of protection (IP) (EF005474) | IP20 |
| System configuration TN-C (EF009929) | 1 |
| System configuration TN-S (EF009930) | 0 |
| Article Number (Market Facing Number) | 5SD7463-0 |
| Max. continuous voltage AC (EF004198) | 350 |
| Max. continuous voltage DC (EF004777) | - |
| System configuration other (EF009932) | 0 |
| System configuration TN-C-S (EF009933) | 0 |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| Voltage protection level L-N (EF004236) | - |
| Voltage protection level N-PE (EF008796) | - |
| With remote signalling contact (EF000422) | false |
| Max. discharge surge current (8/20) (EF012274) | - |
| Nominal discharge surge current (8/20) (EF004214) | 40.0 |
| Number of conductors (without earthing) (EF001148) | - |
| Short-circuit breaking capacity (Isccr) (EF012627) | 25.0 |
| Region Specific PriceGroup / Headquarter Price Group | 12G / 1BK |
| Max. conductor cross section flexible (fine-strand) (EF008828) | 25.0 |
| Max. conductor cross section solid (solid, stranded) (EF008827) | 35.0 |
| Compliance with the substance restrictions according to RoHS directive | Since: 01.07.2006 |
| REACH Art. 33 Duty to inform according to the current list of candidates | Reach InformationThere is currently no information on SVHC (Substances of Very High Concern http://echa.europa.eu/web/guest/candidate-list-table) from the supply chain and our established procedures for screening our products for Substances of Very High Concern.We compare our products regularly with the information of the upstream users with regard to the substances indicated in the candidate list in accordance with the requirements of the REACH regulation. As soon as we have new findings, our information will be updated accordingly. |
Technical specifications and performance data