Service time: Monday to Friday 9:00-18:00
5SD7414-3 - 5SD7414-3 SIEMENS Lightning conductor T1/T2, UN 240/400 V, UC 335/264 V A.C., pluggable protective modules, ..
In Stock Hot Product

5SD7414-3

5SD7414-3 SIEMENS Lightning conductor T1/T2, UN 240/400 V, UC 335/264 V A.C., pluggable protective modules, ..

$0.00USD
3217 in stock
Key Specifications
:
EAN:4001869427652
UPC:Not available
ETIM:5
Supplier Information
SIEMENS
SIEMENS
Products: 367174
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
EAN4001869427652
UPCNot available
ETIM5
Width71.2 mm
depth77.5 mm
Height98.7 mm
eClass6
standardIEC 61643-11: 2011, EN 61643-11: 2012
Group CodeP310
net weight641 g
Accessories3 x 5SD7418-3 + 1 x 5SD7418-2
● maximum335 V
Metal FactorL-P-----
TOV behavior
Product Group5524
Product classC: products manufactured / produced to order, which cannot be reused or re-utilised or be returned against credit.
Quantity Unit1 Piece
signal designOptical, remote signaling contact
Commodity Code85363090
Product familyBasic devices
design of pole3+N/PE
Net Weight (kg)0,682 Kg
Product versionCombination surge arresters
stripped length16 mm
fastening methodDIN rail NS 35
protection level
residual voltage
Country of originGermany
discharge current
operating voltage230 V
tightening torque4.3 ... 4.7
LKZ_FDB/ CatalogIDLV10.1
Packaging Quantity1
shock acceleration30 gn
Degree of pollution2
Packaging Dimension29,00 x 113,00 x 82,00
Product DescriptionLightning conductor T1/T2, UN 240/400 V, UC 335/264 V A.C., pluggable protective modules, 3+1 circuit (TN-S, TT), Width 72 mm with remote signaling
number of SPD ports1
product designationSurge protection device
● between L and N39
● between N and L1.2 kV
● finely stranded1.5 ... 25
● between L and PE39
● between N and PE264 V
— at 3 kA / maximum0.9 kV
— at 5 kA / maximum1 kV
size of surge arrester4 TE
— at 10 kA / maximum1.1 kV
Product Lifecycle (PLM)PM300:Active Product
● between L and (PE)N335 V
● for rigid conductor1.5 ... 35
● Test Class I, Type 1Yes
● Test Class II, Type 2Yes
Category type 2 (EF004230)true
Export Control RegulationsAL : N / ECCN : N
Max. PV-voltage (EF008795)-
Mounting method (EF000003)DIN rail (top hat rail) 35 mm
● Test Class III, Type 3No
Standard lead time ex-works2 Day/Days
Surcharge for Raw MaterialsNone
material / of the enclosurePA 6.6 / PBT
type of distribution systemTT, TN-S
Construction size (EF002566)4 modular spacing
Package size unit of measureMM
continuous operating voltage
Nominal voltage AC (EF004220)-
Nominal voltage DC (EF004221)-
type of electrical connectionScrew terminal
● at TOV test voltage (L-N)415 V AC (5 s / withstand mode)
● between PE and N and/or L1.7 kV
● at TOV test voltage (N-PE)1200 V (200 ms / withstand mode)
Integrated backup fuse (EF008797)false
● for finely stranded conductor1.5 ... 25
System configuration DC (EF009926)0
System configuration IT (EF009927)0
System configuration TN (EF009928)0
System configuration TT (EF009931)0
Signalling at the device (EF004241)Optic
Voltage protection level (EF003525)-
connectable conductor cross-section
designation of the protective pathsL-N, L-PE, N-PE
● between L and N / at (8/20) µs50 kA
Degree of protection (IP) (EF005474)IP20
System configuration TN-C (EF009929)0
System configuration TN-S (EF009930)0
apparent power consumption / maximum810 mVA
relative humidity / during operation5 % ... 95 %
● between L and PE / at (8/20) µs50 kA
● between N and PE / at (8/20) µs50 kA
● response time / between N and PE100 ns
Article Number (Market Facing Number)5SD7414-3
Max. continuous voltage AC (EF004198)-
Max. continuous voltage DC (EF004777)-
System configuration other (EF009932)0
charge of the flash / at (10/350) µs
System configuration TN-C-S (EF009933)0
WEEE (2012/19/EU) Take-Back ObligationYes
fuse protection type / for T-connector160 A AC (gG)
short-circuit rating (SCCR) / at 264 V25 kA
Voltage protection level L-N (EF004236)1.2
combustibility class according to UL 94V0
follow current extinguishing capability
total discharge current / at (8/20) µs50 kA
● between L and (PE)N / at (8/20) µs12.5 kA
● response time / between L and (PE)N25 ns
Voltage protection level N-PE (EF008796)1.7
With remote signalling contact (EF000422)true
● charge of the flash / between L and N6.25 A·s
● charge of the flash / between L and PE6.25 A·s
● charge of the flash / between N and PE25 A·s
connection type of remote signaling contactM2
SPD classification / according to EN 61643-11
fuse protection type / at V-shaped connection80 A AC (gG)
Max. discharge surge current (8/20) (EF012274)-
design of the thread / of the connection screwM5
lightning current peak value / at (10/350) µs
specific energy of the flash / at (10/350) µs
overvoltage category / according to IEC 61010-1III
adjustable response factor / of tripping current1.6
Nominal discharge surge current (8/20) (EF004214)-
protection class IP / at connection all terminalsIP20
tightening torque / for remote signaling contacts0.25 N·m
total lightning impulse current / at (10/350) µs50 kA
— at rated value of discharge current / maximum1.2 kV
Number of conductors (without earthing) (EF001148)-
Short-circuit breaking capacity (Isccr) (EF012627)25.0
ambient temperature / during storage and transport-40 °C ... 80 °C
● lightning current peak value / between L and N12.5 kA
● lightning current peak value / between L and PE12.5 kA
● lightning current peak value / between N and PE50 kA
Region Specific PriceGroup / Headquarter Price Group12G / 1BK
switching function / of the remote signaling contactsPDT contact
● for remote signaling contacts / for rigid conductor0.14 ... 1.5
AWG number / as coded connectable conductor cross section15 ... 2
installation altitude / at height above sea level / maximum2 000 m
operating voltage / of the remote signaling contacts / at AC5 ... 250
Max. conductor cross section flexible (fine-strand) (EF008828)25.0
operational current / of the remote signaling contacts / at AC5 mA ... 1.5 A
stripped length / of the cable / for remote signaling contacts7 mm
Max. conductor cross section solid (solid, stranded) (EF008827)35.0
response value of the surge voltage / at 6 kV / at (1.2/50) µs
● for finely stranded conductor / for remote signaling contacts0.14 ... 1.5
Compliance with the substance restrictions according to RoHS directiveSince: 01.05.2010
REACH Art. 33 Duty to inform according to the current list of candidatesLead CAS-No. 7439-92-1 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):LeadBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.
vibrational acceleration / at 5 Hz ... 500 Hz / limited to 2,5 h / per axis7.5 gn
AWG number / as coded connectable conductor cross section / for remote signaling contacts / maximum16
AWG number / as coded connectable conductor cross section / for remote signaling contacts / minimum28
Ambient temperature / during operation / minimum permissible ... ambient temperature / during operation / maximum permissible-40 °C ... 80 °C

Product Description

3-POLE SURGE DISCHARGER, FOR TN-C NETWORK SYSTEMS, 50 KA (WITH REMOTE WARNING). Manufactured to order. Non-Cancelable Non-Returnable.
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Technical Details

Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top