| Parameter | Value |
|---|---|
| EAN | 4001869427652 |
| UPC | Not available |
| ETIM | 5 |
| Width | 71.2 mm |
| depth | 77.5 mm |
| Height | 98.7 mm |
| eClass | 6 |
| standard | IEC 61643-11: 2011, EN 61643-11: 2012 |
| Group Code | P310 |
| net weight | 641 g |
| Accessories | 3 x 5SD7418-3 + 1 x 5SD7418-2 |
| ● maximum | 335 V |
| Metal Factor | L-P----- |
| TOV behavior | |
| Product Group | 5524 |
| Product class | C: products manufactured / produced to order, which cannot be reused or re-utilised or be returned against credit. |
| Quantity Unit | 1 Piece |
| signal design | Optical, remote signaling contact |
| Commodity Code | 85363090 |
| Product family | Basic devices |
| design of pole | 3+N/PE |
| Net Weight (kg) | 0,682 Kg |
| Product version | Combination surge arresters |
| stripped length | 16 mm |
| fastening method | DIN rail NS 35 |
| protection level | |
| residual voltage | |
| Country of origin | Germany |
| discharge current | |
| operating voltage | 230 V |
| tightening torque | 4.3 ... 4.7 |
| LKZ_FDB/ CatalogID | LV10.1 |
| Packaging Quantity | 1 |
| shock acceleration | 30 gn |
| Degree of pollution | 2 |
| Packaging Dimension | 29,00 x 113,00 x 82,00 |
| Product Description | Lightning conductor T1/T2, UN 240/400 V, UC 335/264 V A.C., pluggable protective modules, 3+1 circuit (TN-S, TT), Width 72 mm with remote signaling |
| number of SPD ports | 1 |
| product designation | Surge protection device |
| ● between L and N | 39 |
| ● between N and L | 1.2 kV |
| ● finely stranded | 1.5 ... 25 |
| ● between L and PE | 39 |
| ● between N and PE | 264 V |
| — at 3 kA / maximum | 0.9 kV |
| — at 5 kA / maximum | 1 kV |
| size of surge arrester | 4 TE |
| — at 10 kA / maximum | 1.1 kV |
| Product Lifecycle (PLM) | PM300:Active Product |
| ● between L and (PE)N | 335 V |
| ● for rigid conductor | 1.5 ... 35 |
| ● Test Class I, Type 1 | Yes |
| ● Test Class II, Type 2 | Yes |
| Category type 2 (EF004230) | true |
| Export Control Regulations | AL : N / ECCN : N |
| Max. PV-voltage (EF008795) | - |
| Mounting method (EF000003) | DIN rail (top hat rail) 35 mm |
| ● Test Class III, Type 3 | No |
| Standard lead time ex-works | 2 Day/Days |
| Surcharge for Raw Materials | None |
| material / of the enclosure | PA 6.6 / PBT |
| type of distribution system | TT, TN-S |
| Construction size (EF002566) | 4 modular spacing |
| Package size unit of measure | MM |
| continuous operating voltage | |
| Nominal voltage AC (EF004220) | - |
| Nominal voltage DC (EF004221) | - |
| type of electrical connection | Screw terminal |
| ● at TOV test voltage (L-N) | 415 V AC (5 s / withstand mode) |
| ● between PE and N and/or L | 1.7 kV |
| ● at TOV test voltage (N-PE) | 1200 V (200 ms / withstand mode) |
| Integrated backup fuse (EF008797) | false |
| ● for finely stranded conductor | 1.5 ... 25 |
| System configuration DC (EF009926) | 0 |
| System configuration IT (EF009927) | 0 |
| System configuration TN (EF009928) | 0 |
| System configuration TT (EF009931) | 0 |
| Signalling at the device (EF004241) | Optic |
| Voltage protection level (EF003525) | - |
| connectable conductor cross-section | |
| designation of the protective paths | L-N, L-PE, N-PE |
| ● between L and N / at (8/20) µs | 50 kA |
| Degree of protection (IP) (EF005474) | IP20 |
| System configuration TN-C (EF009929) | 0 |
| System configuration TN-S (EF009930) | 0 |
| apparent power consumption / maximum | 810 mVA |
| relative humidity / during operation | 5 % ... 95 % |
| ● between L and PE / at (8/20) µs | 50 kA |
| ● between N and PE / at (8/20) µs | 50 kA |
| ● response time / between N and PE | 100 ns |
| Article Number (Market Facing Number) | 5SD7414-3 |
| Max. continuous voltage AC (EF004198) | - |
| Max. continuous voltage DC (EF004777) | - |
| System configuration other (EF009932) | 0 |
| charge of the flash / at (10/350) µs | |
| System configuration TN-C-S (EF009933) | 0 |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| fuse protection type / for T-connector | 160 A AC (gG) |
| short-circuit rating (SCCR) / at 264 V | 25 kA |
| Voltage protection level L-N (EF004236) | 1.2 |
| combustibility class according to UL 94 | V0 |
| follow current extinguishing capability | |
| total discharge current / at (8/20) µs | 50 kA |
| ● between L and (PE)N / at (8/20) µs | 12.5 kA |
| ● response time / between L and (PE)N | 25 ns |
| Voltage protection level N-PE (EF008796) | 1.7 |
| With remote signalling contact (EF000422) | true |
| ● charge of the flash / between L and N | 6.25 A·s |
| ● charge of the flash / between L and PE | 6.25 A·s |
| ● charge of the flash / between N and PE | 25 A·s |
| connection type of remote signaling contact | M2 |
| SPD classification / according to EN 61643-11 | |
| fuse protection type / at V-shaped connection | 80 A AC (gG) |
| Max. discharge surge current (8/20) (EF012274) | - |
| design of the thread / of the connection screw | M5 |
| lightning current peak value / at (10/350) µs | |
| specific energy of the flash / at (10/350) µs | |
| overvoltage category / according to IEC 61010-1 | III |
| adjustable response factor / of tripping current | 1.6 |
| Nominal discharge surge current (8/20) (EF004214) | - |
| protection class IP / at connection all terminals | IP20 |
| tightening torque / for remote signaling contacts | 0.25 N·m |
| total lightning impulse current / at (10/350) µs | 50 kA |
| — at rated value of discharge current / maximum | 1.2 kV |
| Number of conductors (without earthing) (EF001148) | - |
| Short-circuit breaking capacity (Isccr) (EF012627) | 25.0 |
| ambient temperature / during storage and transport | -40 °C ... 80 °C |
| ● lightning current peak value / between L and N | 12.5 kA |
| ● lightning current peak value / between L and PE | 12.5 kA |
| ● lightning current peak value / between N and PE | 50 kA |
| Region Specific PriceGroup / Headquarter Price Group | 12G / 1BK |
| switching function / of the remote signaling contacts | PDT contact |
| ● for remote signaling contacts / for rigid conductor | 0.14 ... 1.5 |
| AWG number / as coded connectable conductor cross section | 15 ... 2 |
| installation altitude / at height above sea level / maximum | 2 000 m |
| operating voltage / of the remote signaling contacts / at AC | 5 ... 250 |
| Max. conductor cross section flexible (fine-strand) (EF008828) | 25.0 |
| operational current / of the remote signaling contacts / at AC | 5 mA ... 1.5 A |
| stripped length / of the cable / for remote signaling contacts | 7 mm |
| Max. conductor cross section solid (solid, stranded) (EF008827) | 35.0 |
| response value of the surge voltage / at 6 kV / at (1.2/50) µs | |
| ● for finely stranded conductor / for remote signaling contacts | 0.14 ... 1.5 |
| Compliance with the substance restrictions according to RoHS directive | Since: 01.05.2010 |
| REACH Art. 33 Duty to inform according to the current list of candidates | Lead CAS-No. 7439-92-1 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):LeadBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. |
| vibrational acceleration / at 5 Hz ... 500 Hz / limited to 2,5 h / per axis | 7.5 gn |
| AWG number / as coded connectable conductor cross section / for remote signaling contacts / maximum | 16 |
| AWG number / as coded connectable conductor cross section / for remote signaling contacts / minimum | 28 |
| Ambient temperature / during operation / minimum permissible ... ambient temperature / during operation / maximum permissible | -40 °C ... 80 °C |
Technical specifications and performance data
Installation and operation guide