| Parameter | Value |
|---|---|
| EAN | 4001869451916 |
| UPC | Not available |
| ETIM | 5 |
| Width | 56 mm |
| depth | 280 mm |
| Height | 191 mm |
| eClass | 6 |
| standard | IEC 61643-11: 2011, EN 61643-11: 2012 |
| Group Code | P310 |
| net weight | 3 150 g |
| ● maximum | 800 V |
| Metal Factor | L-B----- |
| TOV behavior | |
| Product Group | 5524 |
| Product class | B: return restricted, please contact your Siemens partner/contact |
| Quantity Unit | 1 Piece |
| signal design | Defect signaling contact |
| Commodity Code | 85363090 |
| Product family | Basic devices |
| design of pole | 1 |
| Net Weight (kg) | 3,646 Kg |
| Product version | Combination surge arresters |
| stripped length | 24 mm |
| fastening method | other |
| protection level | 4.5 kV |
| residual voltage | |
| Country of origin | Germany |
| discharge current | |
| operating voltage | 690 V |
| tightening torque | 8 ... 9 |
| ● Response time | 100 ns |
| LKZ_FDB/ CatalogID | LV10.1 |
| Packaging Quantity | 1 |
| Degree of pollution | 3 |
| Packaging Dimension | 257,00 x 348,00 x 66,00 |
| Product Description | Lightning arrester Type 1, 1-pole, for 2-wire networks (L, pen), UC 800V AC with remote signaling No modular installation device |
| number of SPD ports | 1 |
| product designation | Surge protection device |
| ● finely stranded | 16 ... 50 |
| ● between L and PE | 800 V |
| — at 3 kA / maximum | 2.1 kV |
| — at 5 kA / maximum | 2.2 kV |
| — at 10 kA / maximum | 2.3 kV |
| Product Lifecycle (PLM) | PM300:Active Product |
| ● at TOV test voltage | 1500 V AC (5 s / withstand mode) |
| ● for rigid conductor | 16 ... 50 |
| ● Test Class I, Type 1 | Yes |
| ● Test Class II, Type 2 | Yes |
| Category type 2 (EF004230) | true |
| Export Control Regulations | AL : N / ECCN : N |
| Max. PV-voltage (EF008795) | - |
| Mounting method (EF000003) | Other |
| ● Test Class III, Type 3 | No |
| Standard lead time ex-works | 2 Day/Days |
| Surcharge for Raw Materials | None |
| material / of the enclosure | Aluminum, salt water-resistant |
| type of distribution system | TN-C, IT |
| ● 1 phase / at (8/20) µs | 100 kA |
| Construction size (EF002566) | Other |
| Package size unit of measure | MM |
| continuous operating voltage | |
| Nominal voltage AC (EF004220) | - |
| Nominal voltage DC (EF004221) | - |
| type of electrical connection | Screw terminal |
| ● at TOV test voltage (N-PE) | 1960 V (200 ms / withstand mode) |
| Integrated backup fuse (EF008797) | false |
| leakage current / according to UL | 20 kA |
| net weight [lb] / according to UL | 6.94 lb |
| ● for finely stranded conductor | 16 ... 50 |
| System configuration DC (EF009926) | 0 |
| System configuration IT (EF009927) | 0 |
| System configuration TN (EF009928) | 0 |
| System configuration TT (EF009931) | 0 |
| Signalling at the device (EF004241) | None |
| Voltage protection level (EF003525) | 4500.0 |
| connectable conductor cross-section | |
| designation of the protective paths | L-PE |
| Degree of protection (IP) (EF005474) | IP20 |
| System configuration TN-C (EF009929) | 0 |
| System configuration TN-S (EF009930) | 0 |
| apparent power consumption / maximum | 16 mVA |
| relative humidity / during operation | 5 % ... 95 % |
| ● between L and PE / at (8/20) µs | 100 kA |
| Article Number (Market Facing Number) | 5SD7411-2 |
| Max. continuous voltage AC (EF004198) | - |
| Max. continuous voltage DC (EF004777) | - |
| System configuration other (EF009932) | 0 |
| charge of the flash / at (10/350) µs | |
| System configuration TN-C-S (EF009933) | 0 |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| fuse protection type / for T-connector | 400 A AC (gG) |
| short-circuit rating (SCCR) / at 264 V | 50 kA |
| Voltage protection level L-N (EF004236) | - |
| combustibility class according to UL 94 | V2 |
| follow current extinguishing capability | 50 kA |
| Voltage protection level N-PE (EF008796) | - |
| With remote signalling contact (EF000422) | true |
| ● charge of the flash / between L and PE | 17.5 A·s |
| connection type of remote signaling contact | M3 |
| SPD classification / according to EN 61643-11 | |
| fuse protection type / at V-shaped connection | 125 A AC (gG) |
| type of distribution system / according to UL | 1 |
| Max. discharge surge current (8/20) (EF012274) | - |
| design of the thread / of the connection screw | M6 |
| lightning current peak value / at (10/350) µs | |
| specific energy of the flash / at (10/350) µs | |
| overvoltage category / according to IEC 61010-1 | IV (600V), III (1000V) |
| adjustable response factor / of tripping current | 1.6 |
| Nominal discharge surge current (8/20) (EF004214) | 100.0 |
| protection class IP / at connection all terminals | IP20 |
| tightening torque / for remote signaling contacts | 0.55 N·m |
| — at rated value of discharge current / maximum | 2.7 kV |
| Number of conductors (without earthing) (EF001148) | - |
| Short-circuit breaking capacity (Isccr) (EF012627) | 50.0 |
| ambient temperature / during storage and transport | -40 °C ... 80 °C |
| ● lightning current peak value / between L and PE | 35 kA |
| Region Specific PriceGroup / Headquarter Price Group | 12G / 1BK |
| designation of the protective paths / according to UL | L-G |
| switching function / of the remote signaling contacts | 2 x N/C contacts |
| installation altitude above sea level / according to UL | 13 123 ft |
| type of surge protective device (SPD) / according to UL | 4CA |
| ● for remote signaling contacts / for rigid conductor | 0.2 ... 2.5 |
| AWG number / as coded connectable conductor cross section | 6 ... 1 |
| installation altitude / at height above sea level / maximum | 4 000 m |
| Measured Limiting Voltage (MLV) / between L and Ground (GND) | 4.37 kV |
| operating voltage / of the remote signaling contacts / at AC | 30 ... 30 |
| Max. conductor cross section flexible (fine-strand) (EF008828) | 50.0 |
| operational current / of the remote signaling contacts / at AC | 1 500 mA ... 1.5 A |
| stripped length / of the cable / for remote signaling contacts | 7 mm |
| Max. conductor cross section solid (solid, stranded) (EF008827) | 50.0 |
| response value of the surge voltage / at 6 kV / at (1.2/50) µs | |
| ● for finely stranded conductor / for remote signaling contacts | 0.2 ... 2.5 |
| Compliance with the substance restrictions according to RoHS directive | Since: 01.03.2012 |
| Maximum Continuous Operating Voltage (MCOV) / between L and Ground (GND) | 800 V |
| REACH Art. 33 Duty to inform according to the current list of candidates | Lead CAS-No. 7439-92-1 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):LeadBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.N,N-dimethylacetamid... CAS-No. 127-19-5 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):N,N-dimethylacetamideBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. |
| AWG number / as coded connectable conductor cross section / according to UL / maximum | 1 |
| AWG number / as coded connectable conductor cross section / according to UL / minimum | 6 |
| AWG number / as coded connectable conductor cross section / for remote signaling contacts / maximum | 12 |
| AWG number / as coded connectable conductor cross section / for remote signaling contacts / minimum | 24 |
| AWG number / as coded connectable conductor cross section / for remote signaling contacts / according to UL / maximum | 12 |
| AWG number / as coded connectable conductor cross section / for remote signaling contacts / according to UL / minimum | 24 |
| Ambient temperature / during operation / minimum permissible ... ambient temperature / during operation / maximum permissible | -40 °C ... 80 °C |
Technical specifications and performance data