| Parameter | Value |
|---|---|
| PL | X0, X1, X2, X3 up to e, X7 (PIN 3) up to d |
| MRP | yes |
| PFH | IEC 62061: 4.8E-9 1/h; IEC 61508: 7.8E-10 1/h |
| SIL | X0, X1, X2, X3 up to 3, X7 (PIN 3) up to 2 |
| Type | for 3-wire sensors or mechanical switches, PNP, IO-Link Devices |
| PIN 2 | Input/Output (port X4, X5); Input (port X6) |
| PIN 4 | Input/Output (port X4, X5); Input (port X6, X7) |
| SIL CL | up to 3 |
| IO-Link | 2× Master |
| Category | X0, X1, X2, X3 up to 4, X7 (PIN 3) up to 3 |
| Fieldbus | Ethernet 10/100 Mbit/s; Push Pull RJ45 Data connector |
| I/O ports | M12, 5-pole, A-coded |
| Addressing | DCP |
| Port Class | 1× Class A; 1× Class B (galvanically separated) |
| Protection | IP67 |
| Service life | 20 years |
| Shared Device | yes, for 2 controls |
| Specification | IO-Link Master V1.1.2 |
| Mounting method | 2-hole screw mounting |
| Operating modes | COM1; COM2; COM3 (automatic) |
| Actuator warning | per channel via LED and BUS |
| Sensor supply US | 24 V DC (EN 61131-2), max. 700 mA (M12 female), short-circuit and overload protected |
| Temperature range | -20...+60 °C (storage temperature -40...+85 °C) |
| Actuator supply UA | 24 V DC (EN 61131-2), max. 8 A |
| Diagnostic via BUS | per module and channel |
| Diagnostic via LED | per module and channel |
| Dimensions H×W×D | 102×63×225 mm |
| Transfer parameters | 32 Byte (In) 32 Byte (Out) per IO-Link port |
| Communication status | via LED |
| Cross-link detection | Sensor/Actuator |
| Wire break detection | yes |
| PROFINET Netload Class | III |
| Monitoring - no voltage | yes |
| Monitoring - under voltage | yes |
| Short-circuit and overload | yes |
| Switching current per output | max. 2 A (short-circuit and overload protected) |
| Sensor-system/actuator supply | Push Pull Power connector, max. 16 A |
| Product article number of manufacturer | 5551001 |
Technical specifications and performance data