| Parameter | Value |
|---|---|
| IO-Link | M12 (male) 3-pole, A-coded |
| Valency | 0.1 °C |
| Accuracy | Typ K: <0.10 %Typ N: <0.10 %Typ J: <0.10 %Typ E: <0.10 %TYP R: <0.15 % |
| Labeling | Laser labelled |
| Cycle time | min. 2.3 ms (≥ 10ms) |
| Data width | 16 Bit / 2 Byte |
| Port Class | A |
| Protection | IP65/IP67 |
| Data format | Siemens S7 |
| Diagnostics | lower limit, upper limit, over heated, supply over voltage, supply under voltage, defective device |
| lower limit | 2 Byte |
| upper limit | 2 Byte |
| Analog input | M12 (female) 4-pole, A-coded |
| Input filter | yes, mean value formation, parameterizable N = 0...64 |
| Specification | IO-Link V1.1 |
| Measured value | Type K,Type N,Type J,Type E,Type R |
| Operating modes | COM2 (38.4 kbit/s) |
| Sensor supply US | 24 V DC (EN 61131-2), max. 200 mA |
| Mean value filter | 1 Byte |
| Operating voltage | 24 V DC (18...30 V DC) |
| Temperature drift | 20 ppm/K |
| Temperature range | -30...+70 °C (storage temperature -40...+85 °C) |
| Diagnostic via LED | yes |
| Dimensions H×W×D | 32.3×77.2×15 mm |
| Material (housing) | Plastic |
| Monitoring - limit | yes |
| Resolution (analog) | 24 Bit |
| Communication status | via LED and IO-Link |
| Input range (analog) | Type K:-200°C...1372°C,Type N: -200°C…1300°C,Type J: -210°C…1200°C,Type E: -200°C…1000°C,Type R: -50°C…1768°C |
| feed back resistance | yes, permanently |
| Underride and overrun | yes |
| Diagnostic via IO-Link | yes |
| Input resistor (analog) | >2 MΩ |
| Over voltage protection | 30 V DC |
| Monitoring - temperature | yes |
| Monitoring - over voltage | yes |
| Invers-polarity protection | yes, permanently |
| Monitoring - under voltage | yes |
| Short-circuit and overload | yes |
| Short-circuit protection sensor | yes, permanently |
| Reverse polarity protection module | yes, permanently |
| Product article number of manufacturer | 5000-00501-1400001 |
Technical specifications and performance data
Installation and operation guide