| Parameter | Value |
|---|---|
| EAN | 4048879622226 |
| eClass | 27242601 |
| IO-Link | M12 (male) 5-pole, A-coded |
| Valency | 348 nA |
| Accuracy | 0.10% (25 °C) |
| Labeling | Laser labelled |
| Cycle time | min. 2.3 ms |
| Data width | 16 Bit / 2 Byte |
| Port Class | A |
| Protection | IP65/IP67 |
| Data format | Siemens S7 |
| Diagnostics | lower limit, upper limit, over heated, supply over voltage, supply under voltage, defective device, sensor supply over current, overrun |
| lower limit | 2 Byte |
| upper limit | 2 Byte |
| Analog input | M12 (female) 5-pole, A-coded, shielded |
| Input filter | yes, mean value formation, parameterizable N = 0...64 |
| Specification | IO-Link V1.1 |
| Measured value | preset |
| Packaging unit | 1.000 |
| Operating modes | COM2 (38.4 kbit/s) |
| Sensor supply US | 24 V DC (EN 61131-2), max. 200 mA |
| Mean value filter | 1 Byte |
| Operating voltage | 24 V DC (18...30 V DC) |
| Temperature drift | 45 ppm/°K |
| Temperature range | -30...+70 °C (storage temperature -40...+85 °C) |
| country of origin | DE |
| Diagnostic via LED | yes |
| Dimensions H×W×D | 32.3×77.2×15 mm |
| Material (housing) | Plastic |
| Monitoring - limit | yes |
| Current consumption | max. 19 mA |
| Resolution (analog) | 15 Bit + sign |
| Communication status | via LED and IO-Link |
| Input range (analog) | 4...20 mA |
| feed back resistance | yes, permanently |
| Underride and overrun | yes |
| customs tariff number | 85389099 |
| Diagnostic via IO-Link | yes |
| Input resistor (analog) | 232 Ω |
| Over voltage protection | 30 V DC |
| Conversion time (analog) | max. 5 ms |
| Monitoring - temperature | yes |
| Monitoring - over voltage | yes |
| Invers-polarity protection | yes, permanently |
| Monitoring - under voltage | yes |
| Short-circuit and overload | yes |
| Short-circuit protection sensor | yes, permanently |
| Reverse polarity protection module | yes, permanently |
Technical specifications and performance data