Service time: Monday to Friday 9:00-18:00
3VT1710-2EC46-0AA0 - 3VT1710-2EC46-0AA0 SIEMENS circuit breaker 3VT1 standard breaking capacity Icu 25kA, 415V AC 4-pole, line pr..
In Stock Hot Product

3VT1710-2EC46-0AA0

3VT1710-2EC46-0AA0 SIEMENS circuit breaker 3VT1 standard breaking capacity Icu 25kA, 415V AC 4-pole, line pr..

$0.00USD
3265 in stock
Key Specifications
:Value
EAN:4011209761995
UPC:Not available
Depth:80 mm
Supplier Information
SIEMENS
SIEMENS
Products: 367174
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
Value
EAN4011209761995
UPCNot available
Depth80 mm
NotesSucessor:Successor portfolio 3VA; further information via www.siemens.com/3VA
Width100 mm
Height130 mm
Group CodeP360
net weight1.339 kg
Price Group193
● maximum55 °C
● minimum-40 °C
Metal FactorLCP-----
Mounting typefixed mounting
Product Group3749
Product classA: Standard product which is a stock item could be returned within the returns guidelines/period.
Quantity Unit1 Piece
Commodity Code85362090
Product familyNot available
Usage categoryA
Net Weight (kg)1,324 Kg
number of poles4
Product function
Country of originCzech Republic
Operating current
Product component
mounting positionwith vertical mounting surface +/-180° rotatable, with vertical mounting surface +/- 30° tiltable to the front and back
LKZ_FDB/ CatalogIDLV10.1
PLM Effective DateProduct is cancelled since: 01.10.2019
Packaging Quantity1
product brand nameSENTRON
● Trip indicatorNo
Operating frequency
Packaging Dimension97,00 x 147,00 x 112,00
Product Descriptioncircuit breaker 3VT1 standard breaking capacity Icu=25kA, 415V AC 4-pole, line protection trip unit TM, LI In=100A rated current IR=80...100A overload prot. II=500...1000A, short-circuit protection N conductor unprotected without auxiliary release without auxiliary/alarm switch
Product designation3VT1_5 molded case circuit breakers
Protection class IPIP40
● 1 / rated value50 Hz
● 2 / rated value60 Hz
● Voltage triggerNo
● Auxiliary switchNo
Product Lifecycle (PLM)PM410:Product cancellation
● Overload protectionYes
● suitability for usesystem protection
General Product ApprovalDeclaration of Conformity
Rated voltage (EF003977)-
● undervoltage releaseNo
Export Control RegulationsECCN : N / AL : N
Number of poles (EF001391)4
● at 240 V / rated value20 kA
● at 415 V / rated value13 kA
● at 500 V / rated value6 kA
● at 690 V / rated value3 kA
Size of the circuit-breaker3VT1
Standard lead time ex-works15 Day/Days
Surcharge for Raw MaterialsNone
● Ground fault protectionNo
● Phase failure detectionNo
● at 40 °C / rated value100 A
● at 50 °C / rated value91 A
Package size unit of measureMM
Operating frequency / maximum120 1/h
Device construction (EF008240)Built-in device fixed built-in technique
Product Dimensions (W x L x H)Not available
Motor drive optional (EF007386)true
Continuous current / rated value100 A
Insulation voltage / rated value690 V
adjustable pick-up value current
Design of the operating mechanismtoggle handle
Design of the overcurrent releaseTM
Motor drive integrated (EF006697)false
● of thermal overload trip unitadjustable
Type of control element (EF006976)Rocker lever
Ambient temperature / during storage
Degree of protection (IP) (EF005474)IP40
Article Number (Market Facing Number)3VT1710-2EC46-0AA0
Performance class for circuit breakerN
Rated permanent current Iu (EF001389)100.0
With under voltage release (EF007518)false
Ambient temperature / during operation
Surge voltage resistance / rated value8 kV
WEEE (2012/19/EU) Take-Back ObligationYes
With switched-off indicator (EF007006)false
Product extension / optional / motor driveYes
Overload release current setting (EF002336)['80', '100']
Type of the driving mechanism / motor driveNo
● Reference code / acc. to DIN EN 81346-2Q
● reference code / acc. to DIN EN 61346-2Q
Integrated earth fault protection (EF007296)false
● Suitability for use / Disconnecting meansYes
● undervoltage release with leading contactNo
Number of CO contacts / for auxiliary contacts0
Number of NC contacts / for auxiliary contacts0
Number of NO contacts / for auxiliary contacts0
protection function of the overcurrent releaseLI
Complete device with protection unit (EF008906)true
Electrical endurance (switching cycles) / typical6 000
DIN rail (top hat rail) mounting optional (EF008904)true
Mechanical service life (switching cycles) / typical20 000
Maximum short-circuit current breaking capacity (Icu)
Suitable for DIN rail (top hat rail) mounting (EF007250)true
Type of electrical connection / for main current circuitbox terminal
Type of electrical connection of main circuit (EF006819)Frame clamp
Operational short-circuit current breaking capacity (Ics)
Position of connection for main current circuit (EF006671)Front side
Adjustment range undelayed short-circuit release (EF007131)['500', '1000']
● of instantaneous short-circuit trip unit / initial value500 A
● for neutral conductors / Short-circuit and overload proofNo
Number of auxiliary contacts as change-over contact (EF003531)0
Arrangement of electrical connectors / for main current circuitfront side
● of instantaneous short-circuit trip unit / Full-scale value1 000 A
Number of auxiliary contacts as normally open contact (EF001376)0
● of the current-dependent overload release / Full-scale value100 A
Number of auxiliary contacts as normally closed contact (EF001377)0
Adjustment range short-term delayed short-circuit release (EF007129)['-', '-']
Derating temperature / for the rated value of the continuous current40 °C
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz (EF007048)25.0
Compliance with the substance restrictions according to RoHS directiveSince: 01.11.2007
REACH Art. 33 Duty to inform according to the current list of candidatesReach InformationThere is currently no information on SVHC (Substances of Very High Concern http://echa.europa.eu/web/guest/candidate-list-table) from the supply chain and our established procedures for screening our products for Substances of Very High Concern.We compare our products regularly with the information of the upstream users with regard to the substances indicated in the candidate list in accordance with the requirements of the REACH regulation. As soon as we have new findings, our information will be updated accordingly.
Power loss [W] / for rated value of the current / at AC / in hot operating state / per pole3.33 W
adjustable pick-up value current / of the current-dependent overload release / initial value80 A
General Product ApprovalDeclaration of ConformityTest CertificatesotherType Test Certificates/Test ReportMiscellaneousManufacturer DeclarationGeneral Product Approval

Product Description

More details
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top