| Parameter | Value |
|---|---|
| EAN | 4042949437697 |
| EMC | Declaration of Conformity |
| UPC | 804766981197 |
| ETIM | 7 |
| IDEA | 4 |
| depth | 120 mm |
| other | Dangerous Good |
| width | 210 mm |
| UNSPSC | 15 |
| eClass | 12 |
| height | 328 mm |
| Group Code | P360 |
| Net Weight | 12.76 kg |
| depth [in] | 4.72 in |
| width [in] | 8.27 in |
| height [in] | 12.91 in |
| ● maximum | 600 A |
| ● minimum | 240 A |
| Confirmation | |
| Metal Factor | LPB----- |
| ● at 240 V | 200 kA |
| ● at 415 V | 110 kA |
| ● at 480 V | 100 kA |
| ● at 600 V | 50 kA |
| ● at 690 V | 35 kA |
| Date8/25/2023 | Subject to change without notice© Copyright Siemens 2023 |
| Product Group | 5383 |
| Product class | C: products manufactured / produced to order, which cannot be reused or re-utilised or be returned against credit. |
| Quantity Unit | 1 Piece |
| ● at 40 °C | 600 A |
| ● at 45 °C | 600 A |
| ● at 50 °C | 600 A |
| ● at 55 °C | 600 A |
| ● at 60 °C | 600 A |
| ● at 65 °C | 555 A |
| ● at 70 °C | 510 A |
| Commodity Code | 85362090 |
| Product family | 3VA Molded Case Circuit Breakers up to 2000 A, UL / IEC |
| last modified: | 8/14/2023 |
| Net Weight (kg) | 12,760 Kg |
| number of poles | 3 |
| product function | |
| Country of origin | Mexico |
| product component | |
| ● initial value | 120 A |
| LKZ_FDB/ CatalogID | LV10 |
| Packaging Quantity | 1 |
| product brand name | SENTRON |
| ● trip indicator | No |
| Packaging Dimension | 250,00 x 360,00 x 180,00 |
| Product Description | Circuit breaker 3VA6 UL Frame 800 breaking capacity class C 100kA @ 480 V 3-pole, Line protection ETU860, LSIG, In=600A overload protection, 100% rated Ir=240A ...600A Short-circuit protection Isd=0.6..12x In, Ii=1.5..12x In N conductor protection optionally with external CT up to 160% Ground-fault protection Ig=0.2... 1 x In, tg=0.05-0.8s |
| ambient temperature | |
| operational current | |
| product designation | Molded-case circuit breaker |
| ● voltage trigger | No |
| ● full-scale value | 600 A |
| design of the product | System protection |
| Product Lifecycle (PLM) | PM300:Active Product |
| power loss [W] / maximum | 151 W |
| ● undervoltage release | No |
| current breaking capacity | |
| Export Control Regulations | AL : N / ECCN : EAR99 |
| ● communication function | Yes |
| Standard lead time ex-works | 25 Day/Days |
| Surcharge for Raw Materials | None |
| Package size unit of measure | MM |
| ● during storage / maximum | 80 °C |
| ● during storage / minimum | -40 °C |
| ● during operation / maximum | 70 °C |
| ● during operation / minimum | -25 °C |
| ● other measurement function | Yes |
| ground-fault monitoring version | Summation current formation L-conductor |
| insulation voltage / rated value | 800 V |
| design of the overcurrent release | ETU860 |
| protection class IP / on the front | IP40 |
| design of the N-conductor protection | adjustable OFF; 20% to 160% |
| Article Number (Market Facing Number) | 3VA6560-7KQ32-2AA0 |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| operating voltage / at AC / rated value | 690 V |
| product function / grounding protection | Yes |
| reference code / according to IEC 81346-2 | Q |
| product designation / according to UL file | CMAE |
| product extension / optional / motor drive | No |
| short-circuit current making capacity (Icm) | |
| number of CO contacts / for auxiliary contacts | 0 |
| protection function of the overcurrent release | LSIG |
| switching capacity class of the circuit breaker | C |
| adjustable setting current (InN) / for N-tripping | |
| electrical endurance (operating cycles) / at 480 V | 5 100 |
| electrical endurance (operating cycles) / at 600 V | 3 500 |
| marking / according to UL 489 / 100%-rated breaker | Yes |
| Region Specific PriceGroup / Headquarter Price Group | 12P / 1CB |
| mechanical service life (operating cycles) / typical | 10 000 |
| maximum short-circuit current breaking capacity (Icu) | |
| operating short-circuit current breaking capacity (Ics) | |
| type of electrical connection / for main current circuit | nut keeper kit on both ends |
| adjustable delay time / of S-trip / with I2t characteristic | 0.5 s |
| electrical endurance (operating cycles) / at AC-1 / at 690 V | 3 500 |
| adjustable response value setting current (Ii) / for I-tripping | |
| arrangement of electrical connectors / for main current circuit | Front connection |
| electrical endurance (operating cycles) / at AC-1 / at 380/415 V | 5 100 |
| total break time / for G-tripping / with standard characteristic | |
| Compliance with the substance restrictions according to RoHS directive | Since: 09.07.2019 |
| REACH Art. 33 Duty to inform according to the current list of candidates | Lead CAS-No. 7439-92-1 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):LeadBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.Lead monoxide (lead ... CAS-No. 1317-36-8 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):Lead monoxide (lead oxide)Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.Silicic acid, lead s... CAS-No. 11120-22-2 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):Silicic acid, lead saltBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.Perfluorobutane sulfonic ... > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):Perfluorobutane sulfonic acid (PFBS) and its saltsBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. |
| adjustable current response value current / of instantaneous short-circuit trip unit | |
| adjustable response value delay time (tg) / for G-tripping / with I0t characteristic | |
| adjustable response value delay time (tg) / for G-tripping / with I2t characteristic | |
| adjustable response value delay time (tr) / for L-tripping / with I2t characteristic | |
| adjustable response value delay time (tsd) / for S-tripping / with I0t characteristic | |
| adjustable response value delay time (tsd) / for S-tripping / with I2t characteristic | |
| adjustable response value setting current (Isd) / of S-trip / with I0t characteristic | |
| adjustable response value setting current (Isd) / of S-trip / with I2t characteristic | |
| certificate of suitability / as approval for NAVAL (no combat vessels) / supplement SB | Yes |
| adjustable response value setting current (Ir) / of the L-trip / with I2t characteristic | |
| adjustable current response value current / for G-tripping / with standard characteristic | |
| adjustable response value setting current (Ig) / for G-tripping / with I2t characteristic | |
| type of connectable conductor cross-sections / for flat-bar terminal connection / maximum | 50 x 28 mm |
| type of connectable conductor cross-sections / for flat-bar terminal connection / minimum | 20 x 4 mm |
| power loss [W] / for rated value of the current / at AC / in hot operating state / per pole | 50.33 W |
| product feature / for neutral conductors / upgradable/retrofittable / short-circuit and overload proof | Yes |
| design of the load switch / according to UL 489 / Heating, Air Conditioning, and Refrigeration circuit breaker (HACR Type) | Yes |
| General Product ApprovalConfirmationMiscellaneousEMCDeclaration of ConformityTest CertificatesMarine / ShippingType Test Certificates/Test ReportotherDangerous GoodConfirmationMiscellaneousMiscellaneousTransport Information | General Product Approval |
Technical specifications and performance data