| Parameter | Value |
|---|---|
| EAN | 4042948862179 |
| UPC | 804766315602 |
| ETIM | 5 |
| IDEA | 4 |
| Width | 184 mm |
| depth | 110 mm |
| Height | 248 mm |
| UNSPSC | 15 |
| eClass | 6 |
| Group Code | P360 |
| Net Weight | 6.9 kg |
| depth [in] | 4.33 in |
| width [in] | 7.24 in |
| height [in] | 9.76 in |
| Metal Factor | LOA----- |
| ● at 240 V | 150 kA |
| ● at 415 V | 110 kA |
| ● at 480 V | 100 kA |
| ● at 600 V | 35 kA |
| ● at 690 V | 6 kA |
| Date5/12/2022 | |
| Miscellaneous | |
| Product Group | 5383 |
| Product class | C: products manufactured / produced to order, which cannot be reused or re-utilised or be returned against credit. |
| Quantity Unit | 1 Piece |
| ● at 40 °C | 600 A |
| ● at 45 °C | 600 A |
| ● at 50 °C | 570 A |
| ● at 55 °C | 540 A |
| ● at 60 °C | 510 A |
| ● at 65 °C | 480 A |
| ● at 70 °C | 450 A |
| Commodity Code | 85362090 |
| Product family | 3VA Molded Case Circuit Breakers up to 1000 A, UL / IEC |
| last modified: | 11/26/2021 |
| Net Weight (kg) | 6,900 Kg |
| Product version | System protection |
| number of poles | 4 |
| product function | |
| Country of origin | Czech Republic |
| Marine / Shipping | other |
| product component | |
| LKZ_FDB/ CatalogID | LV10 |
| Packaging Quantity | 1 |
| product brand name | SENTRON |
| ● trip indicator | No |
| Packaging Dimension | 210,00 x 265,00 x 170,00 |
| Product Description | circuit breaker 3VA6 UL frame 600 breaking capacity class C 100kA @ 480V 4-pole, line protection ETU550, LSI, In=600A overload protection Ir=240A...600A short-circuit protection Isd=0.6..9x In, Ii=1.5..9x In N conductor protection adjustable (OFF, up to 100%) without connection |
| ambient temperature | |
| operational current | |
| product designation | Molded-case circuit breaker |
| ● voltage trigger | No |
| Product Lifecycle (PLM) | PM300:Active Product |
| General Product Approval | EMC |
| Rated voltage (EF003977) | ['600', '600'] |
| power loss [W] / maximum | 151 W |
| ● undervoltage release | No |
| breaking capacity current | |
| Export Control Regulations | AL : N / ECCN : EAR99 |
| Number of poles (EF001391) | 4 |
| ● communication function | Yes |
| Standard lead time ex-works | 20 Day/Days |
| Surcharge for Raw Materials | None |
| rated insulation voltage Ui | 800 V |
| Package size unit of measure | MM |
| ● during storage / maximum | 80 °C |
| ● during storage / minimum | -40 °C |
| Device construction (EF008240) | Built-in device fixed built-in technique |
| ● during operation / maximum | 70 °C |
| ● during operation / minimum | -25 °C |
| ● other measurement function | No |
| Motor drive optional (EF007386) | true |
| ground-fault monitoring version | Without |
| Motor drive integrated (EF006697) | false |
| design of the overcurrent release | ETU550 |
| Type of control element (EF006976) | Rocker lever |
| protection class IP / on the front | IP40 |
| Degree of protection (IP) (EF005474) | IP40 |
| Article Number (Market Facing Number) | 3VA6460-7JP41-0AA0 |
| Rated permanent current Iu (EF001389) | 600.0 |
| With under voltage release (EF007518) | - |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| With switched-off indicator (EF007006) | - |
| reference code / according to IEC 81346-2 | Q |
| product designation / according to UL file | CLAE |
| product extension / optional / motor drive | Yes |
| Adjustable response value current / lg min. | 0.5 s |
| Adjustable response value current / li max. | 5 400 A |
| Adjustable response value current / li min. | 900 A |
| Overload release current setting (EF002336) | ['-', '-'] |
| short-circuit current making capacity (Icm) | |
| Integrated earth fault protection (EF007296) | false |
| Neutral conductors / upgradeable/retrofittable | No |
| number of CO contacts / for auxiliary contacts | 0 |
| protection function of the overcurrent release | LSI |
| Complete device with protection unit (EF008906) | true |
| switching capacity class of the circuit breaker | C |
| electrical endurance (switching cycles) / at 480 V | 4 000 |
| electrical endurance (switching cycles) / at 600 V | 3 500 |
| marking / according to UL 489 / 100%-rated breaker | No |
| DIN rail (top hat rail) mounting optional (EF008904) | true |
| Region Specific PriceGroup / Headquarter Price Group | 12P / 1CB |
| mechanical service life (switching cycles) / typical | 20 000 |
| breaking capacity maximum short-circuit current (Icu) | |
| breaking capacity operating short-circuit current (Ics) | |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | true |
| Type of electrical connection of main circuit (EF006819) | Other |
| type of electrical connection / for main current circuit | Without |
| Ground fault protection / tripping switchable / I2t=ON/OFF | No |
| Position of connection for main current circuit (EF006671) | Other |
| Adjustment range undelayed short-circuit release (EF007131) | ['-', '-'] |
| Number of auxiliary contacts as change-over contact (EF003531) | 0 |
| arrangement of electrical connectors / for main current circuit | Without connection |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Adjustment range short-term delayed short-circuit release (EF007129) | ['-', '-'] |
| Rated short-circuit breaking capacity lcu at 400 V, 50 Hz (EF007048) | 110.0 |
| Electrical endurance (switching cycles) / at AC-1 / at 690 V 50/60 Hz | 3 500 |
| Compliance with the substance restrictions according to RoHS directive | Since: 01.01.2016 |
| REACH Art. 33 Duty to inform according to the current list of candidates | Lead CAS-No. 7439-92-1 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):LeadBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.Lead monoxide (lead ... CAS-No. 1317-36-8 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):Lead monoxide (lead oxide)Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.Silicic acid, lead s... CAS-No. 11120-22-2 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):Silicic acid, lead saltBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. |
| Electrical endurance (switching cycles) / at AC-1 / at 380/415 V 50/60 Hz | 4 000 |
| certificate of suitability / as approval for NAVAL (no combat vessels) / supplement SB | Yes |
| Active power loss / for rated value of the current / at AC / in hot operating state / per pole | 50.33 W |
| design of the load switch / according to UL 489 / Heating, Air Conditioning, and Refrigeration circuit breaker (HACR Type) | Yes |
| General Product ApprovalConfirmationGeneral Product ApprovalEMCDeclaration of ConformityMarine / ShippingMiscellaneousUK Declaration of ConformityMarine / ShippingotherMiscellaneousMiscellaneous | General Product Approval |
Technical specifications and performance data