| Parameter | Value |
|---|---|
| Value | |
| EAN | 4042948821060 |
| UPC | 804766430169 |
| ETIM | 4 |
| Depth | 70 mm |
| Width | 101.6 mm |
| Height | 130 mm |
| UNSPSC | 15 |
| eClass | 6 |
| Depth [in] | 2.8 in |
| Group Code | P360 |
| Net weight | 1.2 kg |
| Width [in] | 4 in |
| Height [in] | 5.1 in |
| Price Group | 12P |
| Metal Factor | LBO----- |
| ● at 240 V | 85 kA |
| ● at 415 V | 55 kA |
| ● at 440 V | 36 kA |
| ● at 500 V | 10 kA |
| ● at 690 V | 10 kA |
| Product Group | 5375 |
| Product class | C: products manufactured / produced to order, which cannot be reused or re-utilised or be returned against credit. |
| Quantity Unit | 1 Piece |
| ● at 40 °C | 100 A |
| ● at 45 °C | 100 A |
| ● at 50 °C | 100 A |
| ● at 55 °C | 98 A |
| ● at 60 °C | 96 A |
| ● at 65 °C | 94 A |
| ● at 70 °C | 91 A |
| Commodity Code | 85362090 |
| Product family | 3VA Molded Case Circuit Breakers up to 1600 A, IEC |
| last modified: | 07/18/2020 |
| Net Weight (kg) | 1,288 Kg |
| Number of poles | 4 |
| Product version | Line protection |
| Product function | |
| Country of origin | Czech Republic |
| Operating current | |
| Shipping Approval | other |
| LKZ_FDB/ CatalogID | LV10.1 |
| Packaging Quantity | 1 |
| Product brand name | SENTRON |
| Ambient temperature | |
| Packaging Dimension | 119,00 x 150,00 x 116,00 |
| Product Description | circuit breaker 3VA1 IEC frame 160 breaking capacity class M Icu=55kA @ 415V 4-pole, line protection TM240, ATAM, In=100A overload protection Ir=70A...100A short-circuit protection Ii=5...10 x In N conductor unprotected clamp connection |
| Product designation | Molded case circuit breaker |
| Product Lifecycle (PLM) | PM300:Active Product |
| General Product Approval | EMC |
| Power loss [W] / maximum | 25 W |
| Rated voltage (EF003977) | ['690', '690'] |
| Declaration of Conformity | Test Certificates |
| Export Control Regulations | AL : N / ECCN : EAR99 |
| Number of poles (EF001391) | 4 |
| ● communication function | No |
| Rated continuous current Iu | 100 A |
| Rated insulation voltage Ui | 800 V |
| Standard lead time ex-works | 5 Day/Days |
| Surcharge for Raw Materials | None |
| Package size unit of measure | MM |
| ● during storage / maximum | 80 °C |
| ● during storage / minimum | -40 °C |
| Device construction (EF008240) | Built-in device fixed built-in technique |
| Product Dimensions (W x L x H) | Not available |
| ● during operation / maximum | 70 °C |
| ● during operation / minimum | -25 °C |
| ● other measurement function | No |
| Ground fault monitoring version | Without |
| Motor drive optional (EF007386) | true |
| Design of the overcurrent release | TM240 |
| Motor drive integrated (EF006697) | false |
| Design of short-circuit protection | For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter |
| Protection class IP / on the front | IP40 |
| Type of control element (EF006976) | Rocker lever |
| Degree of protection (IP) (EF005474) | IP40 |
| Design of the N-conductor protection | Without |
| Article Number (Market Facing Number) | 3VA1110-5EF46-0AA0 |
| Rated permanent current Iu (EF001389) | 100.0 |
| With under voltage release (EF007518) | - |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| With switched-off indicator (EF007006) | - |
| Reference code / acc. to DIN EN 81346-2 | Q |
| Max. rated operational voltage Ue with DC | 600 V |
| Product extension / optional / motor drive | Yes |
| Adjustable response value current / lg min. | 70 A |
| Adjustable response value current / li max. | 1 000 A |
| Adjustable response value current / li min. | 500 A |
| Overload release current setting (EF002336) | ['70', '100'] |
| Short-circuit current making capacity (Icm) | |
| Integrated earth fault protection (EF007296) | false |
| Neutral conductors / upgradeable/retrofittable | No |
| Number of CO contacts / for auxiliary contacts | 0 |
| protection function of the overcurrent release | LI |
| Complete device with protection unit (EF008906) | true |
| Switching capacity class of the circuit breaker | M |
| Max. rated operational current of the frame size | 160 A |
| Max. rated operational voltage Ue with AC 50/60Hz | 690 V |
| DIN rail (top hat rail) mounting optional (EF008904) | true |
| Mechanical service life (switching cycles) / typical | 20 000 |
| Maximum short-circuit current breaking capacity (Icu) | |
| Short-term delayed / tripping switchable / I2t=ON/OFF | No |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | true |
| Type of electrical connection of main circuit (EF006819) | Frame clamp |
| Operational short-circuit current breaking capacity (Ics) | |
| Ground fault protection / tripping switchable / I2t=ON/OFF | No |
| Position of connection for main current circuit (EF006671) | Front side |
| Adjustment range undelayed short-circuit release (EF007131) | ['500', '1000'] |
| Number of auxiliary contacts as change-over contact (EF003531) | 0 |
| Arrangement of electrical connectors / for main current circuit | Front terminal |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Adjustment range short-term delayed short-circuit release (EF007129) | ['-', '-'] |
| Rated short-circuit breaking capacity lcu at 400 V, 50 Hz (EF007048) | 55.0 |
| Electrical endurance (switching cycles) / at AC-1 / at 690 V 50/60 Hz | 8 000 |
| Compliance with the substance restrictions according to RoHS directive | Since: 01.04.2014 |
| REACH Art. 33 Duty to inform according to the current list of candidates | Lead CAS-No. 7439-92-1 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):LeadBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. |
| Electrical endurance (switching cycles) / at AC-1 / at 380/415 V 50/60 Hz | 8 000 |
| Type of connectable conductor cross-section, round conductor terminal, stranded | 1 x (1.5 - 70 mm²) |
| Active power loss / for rated value of the current / at AC / in hot operating state / per pole | 8.33 W |
| General Product ApprovalEMCMiscellaneousKCDeclaration of ConformityTest CertificatesShipping ApprovalType Test Certificates/Test ReportMiscellaneousSpecial Test CertificateShipping ApprovalotherCCS / China Classification SocietyManufacturer DeclarationMiscellaneous | General Product Approval |
Technical specifications and performance data
Installation and operation guide