| Parameter | Value |
|---|---|
| VersionClassificationeClass627-37-92-08eClass7.127-37-92-08eClass827-37-92-08eClass927-37-16-92eClass9.127-37-16-92ETIM5EC002586ETIM6EC002586ETIM7EC002586ETIM8EC002586 | |
| EAN | 4047621064710 |
| UPC | 804766977244 |
| ETIM | 5 |
| depth | 141.6 mm |
| width | 22.5 mm |
| ● 1 | -8 ... +8 A |
| ● 2 | -8 ... +8 A |
| eClass | 6 |
| height | 100 mm |
| ● note | 0.5 A 125 V AC, with resistive load up to 40 °C |
| — solid | 1x (0,5 ... 4 mm²), 2x (0,5 ... 2,5 mm²) |
| Group Code | R711 |
| — upwards | 50 mm |
| ● at 24 V | 1 A |
| Confirmation | |
| Date5/3/2022 | Subject to change without notice© Copyright Siemens 2022 |
| Metal Factor | LAO----- |
| — forwards | 0 mm |
| — stranded | 1x (0,5 ... 4 mm²), 2x (0,5 ... 2,5 mm²) |
| Product Group | 4K62 |
| Product class | A: Standard product which is a stock item could be returned within the returns guidelines/period. |
| Quantity Unit | 1 Piece |
| — backwards | 0 mm |
| — downwards | 50 mm |
| Commodity Code | 85364900 |
| Product family | DC load monitoring |
| last modified: | 1/12/2021 |
| ● auto-RESET | Yes |
| Net Weight (kg) | 0,255 Kg |
| — at the side | 0 mm |
| fastening method | screw and snap-on mounting onto 35 mm standard mounting rail |
| product function | DC load monitoring relay |
| required spacing | |
| ● manual RESET | Yes |
| Country of origin | Germany |
| mounting position | any |
| tightening torque | |
| ● when starting | 0 ... 999 s |
| LKZ_FDB/ CatalogID | CC-IC10 |
| Packaging Quantity | 1 |
| galvanic isolation | |
| insulation voltage | |
| measurable current | -8 ... +8 A |
| product brand name | SIRIUS |
| ● during storage | -40 ... +80 °C |
| ● for live parts | |
| Packaging Dimension | 110,00 x 180,00 x 35,00 |
| Product Description | DC load monitoring relay for PROFINET, max. 2x8 A / 1x16 A DC, max. 800 V Width: 22.5 mm Monitoring for violation of upper and lower limit of current, voltage and power; Energy consumption counter, energy recovery counter, switching cycle counter, operating hours counter, warning and alarm thresholds, automatic or manual reset, ON delay 0-999.0 sec, OFF delay 0-999.0 sec, automatic reclosing delay 0-999.0 sec Supply voltage: 24 V DC 1 changeover contact, screw terminal |
| ambient temperature | |
| product designation | DC load monitoring relay |
| protection class IP | IP20 |
| ● during operation | -25 ... +60 °C |
| ● during transport | -40 ... +80 °C |
| design of the product | for PROFINET |
| protocol is supported | |
| response time maximum | 100 ms |
| ● for main contacts | |
| conducted interference | |
| power loss [W] maximum | 3 W |
| ● for grounded parts | |
| Product Lifecycle (PLM) | PM300:Active Product |
| General Product Approval | Declaration of Conformity |
| adjustable voltage range | 0 ... 800 V |
| measurable voltage at DC | 0 ... 800 V |
| product type designation | 3UG5 |
| ● PROFINET IO protocol | Yes |
| Declaration of Conformity | |
| PROFINET conformity class | A |
| Export Control Regulations | AL : N / ECCN : EAR99 |
| certificate of suitability | CE |
| ● for auxiliary contacts | |
| Standard lead time ex-works | 20 Day/Days |
| Surcharge for Raw Materials | None |
| Package size unit of measure | MM |
| ● between input and output | Yes |
| ● overcurrent detection DC | Yes |
| ● overvoltage detection DC | Yes |
| Substance Prohibitance (Date) | 05/31/2019 |
| electromagnetic compatibility | IEC 60947-1 / IEC 61000-6-2 / IEC 61000-6-4 |
| type of electrical connection | screw-type terminals |
| ● undercurrent detection DC | Yes |
| ● undervoltage detection DC | Yes |
| adjustable response delay time | |
| type of current for monitoring | DC |
| type of voltage for monitoring | DC |
| ● with side-by-side mounting | |
| design of the electrical isolation | Protective separation |
| interface design 1 RJ45 (Ethernet) | Yes |
| supply voltage 1 at DC rated value | 24 V |
| ● at AWG cables for main contacts | 1x (20 ... 12), 2x (20 ... 14) |
| number of ports at the 1st interface | 1 |
| surge voltage resistance rated value | 6 kV |
| Article Number (Market Facing Number) | 3UG5461-1AA40 |
| EMC immunity according to IEC 60947-1 | ambience A (industrial sector) |
| ampacity of the output relay at DC-13 | |
| type of voltage of the supply voltage | DC |
| ● Address Resolution Protocol (ARP) | Yes |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| service for open IE communication LLDP | Yes |
| reference code according to IEC 81346-2 | K |
| ● with lower or upper limit violation | 0 ... 999 s |
| network load class according to PROFINET | 1 |
| ● at AWG cables for auxiliary contacts | 1x (20 ... 12), 2x (20 ... 14) |
| adjustable current response value current | |
| transmission mode for Industrial Ethernet | PROFINET with 100 Mbps full duplex (100BASE-TX) |
| ● between control and auxiliary circuit | 24 V |
| number of interfaces according to PROFINET | 1 |
| ● between auxiliary and auxiliary circuit | 24 V |
| ● due to burst according to IEC 61000-4-4 | 2 kV |
| internal resistance of the measuring circuit | 10 mΩ |
| number of CO contacts for auxiliary contacts | 1 |
| shock resistance according to IEC 60068-2-27 | sinusoidal half-wave 15g / 11 ms |
| type of connectable conductor cross-sections | |
| — finely stranded with core end processing | 1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²) |
| maximum permissible voltage for safe isolation | |
| design of the interface Fast Ethernet interface | Yes |
| vibration resistance according to IEC 60068-2-6 | 1 ... 6 Hz: 15 mm, 6 ... 500 Hz: 2g |
| ● for main contacts with screw-type terminals | 0.6 ... 0.8 N·m |
| EMC emitted interference according to IEC 60947-1 | ambience A (industrial sector) |
| ● between the voltage supply and other circuits | Yes |
| electrostatic discharge according to IEC 61000-4-2 | 6 kV contact discharge / 8 kV air discharge |
| mechanical service life (switching cycles) typical | 10 000 000 |
| relative temperature-related measurement deviation | 0.5 % |
| field-based interference according to IEC 61000-4-3 | 10 V/m |
| Region Specific PriceGroup / Headquarter Price Group | 41H / 41H |
| ● for auxiliary contacts with screw-type terminals | 0.6 ... 0.8 N·m |
| product component removable terminal for main circuit | Yes |
| installation altitude at height above sea level maximum | 2 000 m |
| operating range factor supply voltage rated value at DC | 0.85 ... 1.15 |
| product function at the 1st interface PROFINET IO device | Yes |
| product function at the Ethernet interface Autocrossover | Yes |
| ampacity for overcurrent duration < 1 s maximum permissible | 1 A |
| ● due to conductor-earth surge according to IEC 61000-4-5 | 2 kV |
| continuous current of the DIAZED fuse link of the output relay | 2 A |
| thermal current of the switching element with contacts maximum | 1 A |
| ● due to conductor-conductor surge according to IEC 61000-4-5 | 1 kV |
| electrical endurance (switching cycles) for relay outputs maximum | 100 000 |
| Compliance with the substance restrictions according to RoHS directive | Since: 31.05.2019 |
| product component removable terminal for auxiliary and control circuit | Yes |
| REACH Art. 33 Duty to inform according to the current list of candidates | Lead CAS-No. 7439-92-1 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):LeadBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.Lead monoxide (lead ... CAS-No. 1317-36-8 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):Lead monoxide (lead oxide)Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.2-methyl-1-(4-methyl... CAS-No. 71868-10-5 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):2-methyl-1-(4-methylthiophenyl)-2-morpholinopropan-1-oneBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. |
| ● for overvoltage category II according to IEC 60664 with degree of pollution 3 rated value | 800 V |
| ● for overvoltage category III according to IEC 60664 with degree of pollution 3 rated value | 600 V |
| ● of the auxiliary and control circuit for overvoltage category III according to IEC 60664 with degree of pollution 3 rated value | 30 V |
| General Product ApprovalDeclaration of ConformityTest CertificatesotherConfirmationType Test Certificates/Test ReportConfirmationotherDeclaration of Conformity | General Product Approval |
Technical specifications and performance data
Installation and operation guide