| Parameter | Value |
|---|---|
| Special Test Certificate | |
| EAN | 4011209912533 |
| UPC | 195125228887 |
| ETIM | 5 |
| IDEA | 4 |
| depth | 91 mm |
| width | 22.5 mm |
| ● 1 | 30 mA ... 40 A |
| ● 2 | 30 mA ... 40 A |
| UNSPSC | 15 |
| eClass | 6 |
| height | 102 mm |
| ● solid | 1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²) |
| Group Code | R711 |
| data volume | |
| — upwards | 0 mm |
| ● at 24 V | 1 A |
| Metal Factor | LAO----- |
| — forwards | 0 mm |
| ● at 125 V | 0.2 A |
| ● at 250 V | 0.1 A |
| ● stranded | 20 ... 14 |
| Date5/14/2022 | Subject to change without notice© Copyright Siemens 2022 |
| Product Group | 5885 |
| Product class | A: Standard product which is a stock item could be returned within the returns guidelines/period. |
| Quantity Unit | 1 Piece |
| — backwards | 0 mm |
| — downwards | 0 mm |
| Commodity Code | 85364900 |
| Product family | Residual-current monitoring relays |
| last modified: | 12/1/2021 |
| Net Weight (kg) | 0,147 Kg |
| type of voltage | DC |
| — at the side | 0 mm |
| ● rated value | 300 V |
| Depth (EF000049) | 91.0 |
| Width (EF000008) | 22.5 |
| fastening method | screw and snap-on mounting onto 35 mm standard mounting rail |
| product function | for three-phase supplies |
| required spacing | |
| ● error memory | Yes |
| Country of origin | Czech Republic |
| Height (EF000040) | 102.0 |
| mounting position | any |
| ● initial value | 0.85 |
| LKZ_FDB/ CatalogID | CC-IC10 |
| Packaging Quantity | 1 |
| galvanic isolation | |
| insulation voltage | |
| measurable current | 10 mA ... 43 A |
| product brand name | SIRIUS |
| ● during storage | -40 ... +85 °C |
| ● external reset | Yes |
| ● for live parts | |
| Function (EF000030) | For three-phase supply system |
| Packaging Dimension | 98,00 x 33,00 x 111,00 |
| Product Description | Digital monitoring relay for residual current monitoring with residual-current transformer 3UL23 for IO-Link Setting range 0.03 A to 40 A separate for warning threshold and switch-off value ON delay and tripping delay 0 to 999.9 s Shutdown hysteresis up to 50% Warning hysteresis 5% fixed Width 22.5mm, 2 change-over contacts with or without fault buffer screw terminal |
| ambient temperature | |
| degree of pollution | 3 |
| product designation | Residual current monitoring relay with digital setting |
| protection class IP | IP20 |
| ● of the terminal | IP20 |
| ● during operation | -25 ... +60 °C |
| ● during transport | -40 ... +85 °C |
| ● full-scale value | 1.1 |
| ● of the enclosure | IP20 |
| IO-Link transfer rate | COM2 (38,4 kBaud) |
| design of the display | LCD |
| number of CO contacts | |
| ● delayed switching | 2 |
| conducted interference | |
| ● for grounded parts | |
| Product Lifecycle (PLM) | PM300:Active Product |
| ● at AWG cables solid | 2x (20 ... 14) |
| ● between the outputs | Yes |
| General Product Approval | EMC |
| Manufacturer Declaration | Confirmation |
| Rated voltage (EF003977) | ['24', '24'] |
| product type designation | 3UG4 |
| relative repeat accuracy | 1 % |
| ● at 250 V at 50/60 Hz | 3 A |
| ● at 400 V at 50/60 Hz | 0 A |
| Declaration of Conformity | Test Certificates |
| measurable line frequency | 16 ... 400 Hz |
| temperature drift per °C | 0.1 %/°C |
| Export Control Regulations | AL : N / ECCN : EAR99 |
| Rated frequency (EF001663) | ['16', '400'] |
| ● at AWG cables stranded | 2x (20 ... 14) |
| ● for auxiliary contacts | 2 |
| Standard lead time ex-works | 2 Day/Days |
| Surcharge for Raw Materials | None |
| accuracy of digital display | +/-1 digit |
| relative metering precision | 5 % |
| Package size unit of measure | MM |
| control supply voltage at DC | |
| ● between input and output | Yes |
| ● residual current display | Yes |
| Substance Prohibitance (Date) | 02/14/2013 |
| operating voltage rated value | 24 ... 24 V |
| type of electrical connection | screw-type terminals |
| adjustable response delay time | 0 ... 999.9 s |
| type of current for monitoring | AC |
| ● with side-by-side mounting | |
| adjustable operating delay time | 0 ... 999.9 s |
| operating frequency rated value | 16 ... 400 Hz |
| With detachable clamps (EF003340) | true |
| ● overcurrent detection 1 phase | Yes |
| design of the electrical isolation | galvanic isolation |
| ● undercurrent detection 1 phase | No |
| connectable conductor cross-section | |
| operational current at 17 V minimum | 5 mA |
| Response value amperage 1 (EF008204) | ['30.0', '40000.0'] |
| Response value amperage 2 (EF008205) | ['30.0', '40000.0'] |
| surge voltage resistance rated value | 4 kV |
| Article Number (Market Facing Number) | 3UG4825-1CA40 |
| Voltage type for actuating (EF008242) | DC |
| ampacity of the output relay at AC-15 | |
| ampacity of the output relay at DC-13 | |
| Error registration possible (EF003423) | true |
| Type of electric connection (EF003961) | Screw connection |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| protocol is supported IO-Link protocol | Yes |
| number of NC contacts delayed switching | 0 |
| number of NO contacts delayed switching | 0 |
| reference code according to IEC 81346-2 | K |
| adjustable current response value current | |
| — with degree of pollution 3 rated value | 300 V |
| Indication of difference current (EF003424) | true |
| tightening torque with screw-type terminals | 0.8 ... 1.2 N·m |
| ● due to burst according to IEC 61000-4-4 | 2 kV |
| adjustable response delay time when starting | 0 ... 999.9 s |
| number of NC contacts for auxiliary contacts | 0 |
| number of NO contacts for auxiliary contacts | 0 |
| shock resistance according to IEC 60068-2-27 | sinusoidal half-wave 15g / 11 ms |
| type of connectable conductor cross-sections | |
| ● finely stranded with core end processing | 1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²) |
| type of voltage of the control supply voltage | DC |
| operating frequency with 3RT2 contactor maximum | 5 000 1/h |
| vibration resistance according to IEC 60068-2-6 | 1 ... 6 Hz: 15 mm, 6 ... 500 Hz: 2g |
| Rated control supply voltage Us at DC (EF003980) | ['24', '24'] |
| ampacity of the semiconductor output in SIO mode | 200 mA |
| ● between the voltage supply and other circuits | No |
| electrostatic discharge according to IEC 61000-4-2 | 4 kV contact discharge / 8 kV air discharge |
| mechanical service life (switching cycles) typical | 10 000 000 |
| field-based interference according to IEC 61000-4-3 | 10 V/m |
| type of voltage supply via input/output link master | Yes |
| Max. permitted delay-on energization time (EF008189) | 999.9 |
| Number of contacts as change-over contact (EF008257) | 2 |
| Region Specific PriceGroup / Headquarter Price Group | 41H / 41H |
| buffering time in the event of power failure minimum | 10 ms |
| ● adjustable open/closed-circuit current principle | Yes |
| Min. adjustable delay-on energization time (EF008190) | 0.0 |
| Rated control supply voltage Us at AC 50HZ (EF003978) | - |
| Rated control supply voltage Us at AC 60HZ (EF003979) | - |
| Number of contacts as normally open contact (EF008256) | 0 |
| AWG number as coded connectable conductor cross section | |
| installation altitude at height above sea level maximum | 2 000 m |
| ● for overvoltage category III according to IEC 60664 | |
| Number of contacts as normally closed contact (EF008255) | 0 |
| ● due to conductor-earth surge according to IEC 61000-4-5 | 2 kV |
| continuous current of the DIAZED fuse link of the output relay | 4 A |
| thermal current of the switching element with contacts maximum | 5 A |
| operating range factor control supply voltage rated value at DC | |
| ● due to conductor-conductor surge according to IEC 61000-4-5 | 1 kV |
| electrical endurance (switching cycles) at AC-15 at 230 V typical | 100 000 |
| point-to-point cycle time between master and IO-Link device minimum | 10 ms |
| ● of the address range of the inputs with cyclical transfer total | 4 byte |
| ● of the address range of the outputs with cyclical transfer total | 2 byte |
| Compliance with the substance restrictions according to RoHS directive | Since: 14.02.2013 |
| product component removable terminal for auxiliary and control circuit | Yes |
| REACH Art. 33 Duty to inform according to the current list of candidates | Reach InformationThere is currently no information on SVHC (Substances of Very High Concern http://echa.europa.eu/web/guest/candidate-list-table) from the supply chain and our established procedures for screening our products for Substances of Very High Concern.We compare our products regularly with the information of the upstream users with regard to the substances indicated in the candidate list in accordance with the requirements of the REACH regulation. As soon as we have new findings, our information will be updated accordingly. |
| General Product ApprovalEMCManufacturer DeclarationConfirmationDeclaration of ConformityTest CertificatesMarine / ShippingotherRailwaySpecial Test CertificateType Test Certificates/Test ReportConfirmationVibration and Shock | General Product Approval |
Technical specifications and performance data
Installation and operation guide