| Parameter | Value |
|---|---|
| Confirmation | |
| EAN | 4011209628397 |
| UPC | 754554901947 |
| ETIM | 5 |
| IDEA | 4 |
| depth | 124 mm |
| width | 22.5 mm |
| UNSPSC | 14 |
| eClass | 6 |
| height | 92 mm |
| ● top | 40 mm |
| ● left | 0 mm |
| ● right | 0 mm |
| ● solid | 1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²) |
| Group Code | R711 |
| ● bottom | 40 mm |
| Metal Factor | None |
| Date5/10/2022 | Subject to change without notice© Copyright Siemens 2022 |
| Product Group | 5836 |
| Product class | A: Standard product which is a stock item could be returned within the returns guidelines/period. |
| Quantity Unit | 1 Piece |
| ● 1 maximum | 2 000 m |
| ● 2 maximum | 3 000 m; max. +50 °C (no protective separation) |
| ● 3 maximum | 4 000 m; max. +40 °C (no protective separation) |
| Commodity Code | 85371098 |
| Product family | SIMOCODE pro 3UF7 motor management and control devices |
| last modified: | 4/7/2022 |
| Net Weight (kg) | 0,139 Kg |
| Model (EF000010) | Temperature module |
| fastening method | screw and snap-on mounting |
| number of inputs | 3 |
| required spacing | |
| Country of origin | Germany |
| Test Certificates | Marine / Shipping |
| mounting position | any |
| product component | |
| ● initial value | -50 °C |
| LKZ_FDB/ CatalogID | CC-IC10 |
| Packaging Quantity | 1 |
| product brand name | SIRIUS |
| ● during storage | -40 ... +80 °C |
| Packaging Dimension | 28,00 x 108,50 x 147,00 |
| Product Description | Temperature module, 3 inputs for connection of up to 3 temperature sensors, for SIMOCODE pro V basic unit |
| ambient temperature | |
| product designation | temperature module |
| protection class IP | IP20 |
| ● during operation | -25 ... +60 °C |
| ● during transport | -40 ... +80 °C |
| ● full-scale value | 500 °C |
| ● with NTC maximum | 160 °C |
| ● with NTC minimum | 80 °C |
| consumed active power | 0.2 W |
| conducted interference | |
| environmental category | |
| measurable temperature | |
| Product Lifecycle (PLM) | PM300:Active Product |
| number of analog inputs | 3 |
| ● at AWG cables solid | 1x (20 ... 14), 2x (20 ... 16) |
| ● with KTY 84 maximum | 300 °C |
| ● with KTY 84 minimum | -40 °C |
| ● with Pt 100 maximum | 500 °C |
| ● with Pt 100 minimum | -50 °C |
| General Product Approval | EMC |
| number of analog outputs | 0 |
| number of digital inputs | 0 |
| ● with Pt 1000 maximum | 500 °C |
| ● with Pt 1000 minimum | -50 °C |
| temperature drift per °C | 0.05 %/°C |
| Export Control Regulations | AL : N / ECCN : EAR99 |
| ● at AWG cables stranded | 1x (20 ... 12), 2x (20 ... 14) |
| ● open-circuit detection | Yes |
| Standard lead time ex-works | 1 Day/Days |
| Surcharge for Raw Materials | None |
| ● short-circuit detection | Yes |
| ● with KTY 83-110 maximum | 175 °C |
| ● with KTY 83-110 minimum | -50 °C |
| Package size unit of measure | MM |
| Substance Prohibitance (Date) | 05/01/2012 |
| Switching function (EF000189) | - |
| sensor current for Pt 100 typical | 1 mA |
| Number of binary inputs (EF003817) | 0 |
| Type Test Certificates/Test Report | |
| relative humidity during operation | 5 ... 95 % |
| ● input for thermistor connection | No |
| Degree of protection (IP) (EF005474) | IP20 |
| Number of analogue inputs (EF001994) | 3 |
| surge voltage resistance rated value | 4 000 V |
| ● input for ground fault detection | No |
| A/D conversion time at sensor circuit | 500 ms |
| Article Number (Market Facing Number) | 3UF7700-1AA00-0 |
| EMC immunity according to IEC 60947-1 | corresponds to degree of severity 3 |
| Number of analogue outputs (EF001995) | 0 |
| Voltage type for actuating (EF008242) | - |
| Degree of protection (NEMA) (EF011959) | - |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| Number of electronic outputs (EF006929) | - |
| reference code according to IEC 81346-2 | B |
| ● input for analog temperature sensors | Yes |
| touch protection against electrical shock | finger-safe |
| ● during storage according to IEC 60721 | 3K6 (no formation of ice, no condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6 |
| Input for earth fault detection (EF007115) | false |
| Input for thermistor connection (EF007116) | false |
| Number of outputs, with contact (EF006936) | 0 |
| tightening torque with screw-type terminals | 0.8 ... 1.2 N·m |
| ● due to burst according to IEC 61000-4-4 | 1 kV |
| ● during operation according to IEC 60721 | 3K6 (no formation of ice, no condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6 |
| ● during transport according to IEC 60721 | 3K6 (no formation of ice, no condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6 |
| shock resistance according to IEC 60068-2-27 | 15g / 11 ms |
| type of connectable conductor cross-sections | |
| ● finely stranded with core end processing | 1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²) |
| diagnostics function at sensor input with NTC | |
| installation altitude at height above sea level | |
| type of connection technology of sensor circuit | 2-wire or 3-wire connection |
| vibration resistance according to IEC 60068-2-6 | 1 ... 6 Hz: 15 mm, 6 ... 500 Hz: 2g |
| Input for analogue temperature sensor (EF007114) | true |
| Rated control supply voltage Us at DC (EF003980) | ['-', '-'] |
| diagnostics function at sensor input with KTY 84 | |
| diagnostics function at sensor input with Pt 100 | |
| EMC emitted interference according to IEC 60947-1 | class A |
| diagnostics function at sensor input with Pt 1000 | |
| galvanic isolation between inputs and electronics | No |
| field-based interference according to IEC 61000-4-3 | 10 V/m |
| Region Specific PriceGroup / Headquarter Price Group | 42J / 42J |
| diagnostics function at sensor input with KTY 83-110 | |
| Rated control supply voltage Us at AC 50HZ (EF003978) | - |
| Rated control supply voltage Us at AC 60HZ (EF003979) | - |
| tightening torque [lbf·in] with screw-type terminals | 7 ... 10.3 lbf·in |
| number of outputs as contact-affected switching element | 0 |
| sensor current for Pt 1000/KTY 83-110/KTY 84/NTC typical | 0.2 mA |
| ● due to conductor-earth surge according to IEC 61000-4-5 | 2 kV |
| design of the sensor for temperature measurement connectable | PT100 / PT1000 / KTY83-110 / KTY84 / NTC |
| relative temperature-related measurement deviation at 20 °C | 2 % |
| ● due to conductor-conductor surge according to IEC 61000-4-5 | 1 kV |
| Compliance with the substance restrictions according to RoHS directive | Since: 01.05.2012 |
| REACH Art. 33 Duty to inform according to the current list of candidates | Lead CAS-No. 7439-92-1 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):LeadBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.Lead monoxide (lead ... CAS-No. 1317-36-8 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):Lead monoxide (lead oxide)Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. |
| Type of electrical connection for auxiliary- and control current circuit (EF006979) | Screw connection |
| General Product ApprovalEMCDeclaration of ConformityConfirmationTest CertificatesMarine / ShippingotherType Test Certificates/Test ReportConfirmation | General Product Approval |
Technical specifications and performance data
Installation and operation guide