| Parameter | Value |
|---|---|
| Confirmation | |
| EAN | 4011209912496 |
| UPC | 887621549275 |
| ETIM | 5 |
| IDEA | 4 |
| depth | 124 mm |
| width | 22.5 mm |
| UNSPSC | 15 |
| eClass | 6 |
| height | 92 mm |
| ● top | 40 mm |
| ● left | 0 mm |
| ● right | 0 mm |
| ● solid | 1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²) |
| Group Code | R711 |
| ● bottom | 40 mm |
| Date5/6/2022 | Subject to change without notice© Copyright Siemens 2022 |
| Metal Factor | None |
| Product Group | 5836 |
| Product class | A: Standard product which is a stock item could be returned within the returns guidelines/period. |
| Quantity Unit | 1 Piece |
| ● 1 maximum | 2 000 m |
| ● 2 maximum | 3 000 m; max. +50 °C (no protective separation) |
| ● 3 maximum | 4 000 m; max. +40 °C (no protective separation) |
| Commodity Code | 85389091 |
| Product family | SIMOCODE pro 3UF7 motor management and control devices |
| last modified: | 4/7/2022 |
| Net Weight (kg) | 0,134 Kg |
| Model (EF000010) | Earth fault module |
| fastening method | screw and snap-on mounting |
| number of inputs | 1 |
| required spacing | |
| Country of origin | Germany |
| Test Certificates | Marine / Shipping |
| mounting position | any |
| number of outputs | 0 |
| product component | |
| LKZ_FDB/ CatalogID | CC-IC10 |
| Packaging Quantity | 1 |
| product brand name | SIRIUS |
| ● during storage | -40 ... +80 °C |
| Packaging Dimension | 28,00 x 108,50 x 147,00 |
| Product Description | Ground fault module with analog residual current detection for connection of a residual-current transformer 3UL23, max. 1 ground fault module per, for SIMOCODE pro V basic unit |
| ambient temperature | |
| product designation | ground fault modules |
| protection class IP | IP20 |
| ● during operation | -25 ... +60 °C |
| ● during transport | -40 ... +80 °C |
| consumed active power | 0.1 W |
| response time maximum | 100 ms |
| conducted interference | |
| environmental category | |
| Product Lifecycle (PLM) | PM300:Active Product |
| number of analog inputs | 1 |
| ● at AWG cables solid | 1x (20 ... 14), 2x (20 ... 16) |
| General Product Approval | EMC |
| number of analog outputs | 0 |
| number of digital inputs | 0 |
| Export Control Regulations | AL : N / ECCN : EAR99 |
| ● at AWG cables stranded | 1x (20 ... 12), 2x (20 ... 14) |
| Standard lead time ex-works | 1 Day/Days |
| Surcharge for Raw Materials | None |
| Package size unit of measure | MM |
| Substance Prohibitance (Date) | 05/01/2012 |
| Switching function (EF000189) | - |
| manufacturer's article number | |
| type of current for monitoring | AC and pulse-shaped direct currents (type A) |
| number of semiconductor outputs | 0 |
| Number of binary inputs (EF003817) | 0 |
| Type Test Certificates/Test Report | |
| relative humidity during operation | 5 ... 95 % |
| ● input for thermistor connection | No |
| Degree of protection (IP) (EF005474) | IP20 |
| Number of analogue inputs (EF001994) | 1 |
| ● input for ground fault detection | Yes |
| Article Number (Market Facing Number) | 3UF7510-1AA00-0 |
| EMC immunity according to IEC 60947-1 | corresponds to degree of severity 3 |
| Number of analogue outputs (EF001995) | 0 |
| Voltage type for actuating (EF008242) | - |
| Degree of protection (NEMA) (EF011959) | - |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| Number of electronic outputs (EF006929) | 0 |
| measurable line frequency initial value | 400 Hz |
| ● input for analog temperature sensors | No |
| touch protection against electrical shock | finger-safe |
| ● during storage according to IEC 60721 | 1K6 (no condensation, relative humidity 10 ... 95%), 1C2 (no salt mist), 1S2 (sand must not get into the devices), 1M4 |
| Input for earth fault detection (EF007115) | true |
| Input for thermistor connection (EF007116) | false |
| Number of outputs, with contact (EF006936) | 0 |
| measurable line frequency full-scale value | 16 Hz |
| tightening torque with screw-type terminals | 0.8 ... 1.2 N·m |
| ● due to burst according to IEC 61000-4-4 | 1 kV |
| ● during operation according to IEC 60721 | 3K6 (no formation of ice, no condensation, relative humidity 10 ... 95%), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6 |
| ● during transport according to IEC 60721 | 2K2, 2C1, 2S1, 2M2 |
| shock resistance according to IEC 60068-2-27 | 15g / 11 ms |
| type of connectable conductor cross-sections | |
| ● finely stranded with core end processing | 1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²) |
| installation altitude at height above sea level | |
| vibration resistance according to IEC 60068-2-6 | 1 ... 6 Hz: 15 mm, 6 ... 500 Hz: 2g |
| Input for analogue temperature sensor (EF007114) | false |
| Rated control supply voltage Us at DC (EF003980) | - |
| EMC emitted interference according to IEC 60947-1 | class A |
| ● 1 of residual current transformer connectable | 3UL2302-1A |
| ● 2 of residual current transformer connectable | 3UL2303-1A |
| ● 3 of residual current transformer connectable | 3UL2304-1A |
| ● 4 of residual current transformer connectable | 3UL2305-1A |
| ● 5 of residual current transformer connectable | 3UL2306-1A |
| ● 6 of residual current transformer connectable | 3UL2307-1A |
| electrostatic discharge according to IEC 61000-4-2 | 6 kV contact discharge / 8 kV air discharge |
| number of sensor inputs for ground fault detection | 1 |
| field-based interference according to IEC 61000-4-3 | 10 V/m |
| Region Specific PriceGroup / Headquarter Price Group | 42J / 42J |
| Rated control supply voltage Us at AC 50HZ (EF003978) | - |
| Rated control supply voltage Us at AC 60HZ (EF003979) | - |
| tightening torque [lbf·in] with screw-type terminals | 7 ... 10.3 lbf·in |
| number of outputs as contact-affected switching element | 0 |
| field-bound HF interference emission according to CISPR11 | corresponds to degree of severity A |
| ● due to conductor-earth surge according to IEC 61000-4-5 | 2 kV |
| (electrically) protective separation according to IEC 60947-1 | All circuits with protective separation (double creepage paths and clearances), the information in the "Protective Separation" test report, No. 2668, must be observed. |
| relative measurement deviation of residual current transformer | 2.5 % |
| ● due to high-frequency radiation according to IEC 61000-4-6 | 10 V |
| ● due to conductor-conductor surge according to IEC 61000-4-5 | 1 kV |
| diameter of inlet opening of connectable residual current transformer | 35 ... 210 mm |
| Compliance with the substance restrictions according to RoHS directive | Since: 01.05.2012 |
| REACH Art. 33 Duty to inform according to the current list of candidates | Lead CAS-No. 7439-92-1 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):LeadBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.Lead monoxide (lead ... CAS-No. 1317-36-8 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):Lead monoxide (lead oxide)Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. |
| Type of electrical connection for auxiliary- and control current circuit (EF006979) | Screw connection |
| General Product ApprovalEMCDeclaration of ConformityConfirmationTest CertificatesMarine / ShippingotherType Test Certificates/Test ReportConfirmation | General Product Approval |
Technical specifications and performance data
Installation and operation guide