| Parameter | Value |
|---|---|
| Confirmation | |
| EAN | 4011209628373 |
| UPC | 754554901923 |
| ETIM | 5 |
| IDEA | 4 |
| depth | 124 mm |
| width | 22.5 mm |
| UNSPSC | 14 |
| eClass | 6 |
| height | 92 mm |
| ● top | 40 mm |
| ● left | 0 mm |
| ● right | 0 mm |
| ● solid | 1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²) |
| Group Code | R711 |
| ● bottom | 40 mm |
| Date5/6/2022 | Subject to change without notice© Copyright Siemens 2022 |
| Metal Factor | None |
| ● at input | shield recommended up to 30 m and/or when exiting control cabinet, shield required from 30 m |
| Product Group | 5836 |
| Product class | A: Standard product which is a stock item could be returned within the returns guidelines/period. |
| Quantity Unit | 1 Piece |
| ● 1 maximum | 2 000 m |
| ● 2 maximum | 3 000 m; max. +50 °C (no protective separation) |
| ● 3 maximum | 4 000 m; max. +40 °C (no protective separation) |
| ● at output | shield recommended up to 30 m and/or when exiting control cabinet, shield required from 30 m |
| Commodity Code | 85389091 |
| Product family | SIMOCODE pro 3UF7 motor management and control devices |
| last modified: | 4/7/2022 |
| output voltage | 30 V |
| type of shield | |
| Net Weight (kg) | 0,138 Kg |
| Model (EF000010) | Analogue module |
| fastening method | screw and snap-on mounting |
| input resistance | 50 Ω |
| number of inputs | 2 |
| required spacing | |
| Country of origin | Germany |
| Test Certificates | Marine / Shipping |
| mounting position | any |
| number of outputs | 1 |
| product component | |
| LKZ_FDB/ CatalogID | CC-IC10 |
| Packaging Quantity | 1 |
| galvanic isolation | |
| product brand name | SIRIUS |
| ● during storage | -40 ... +80 °C |
| Packaging Dimension | 28,00 x 108,50 x 147,00 |
| Product Description | Analog module, 2 inputs (passive) and 1 output, for analog signals 0/4...20 mA for SIMOCODE pro V basic unit |
| ambient temperature | |
| product designation | analog modules |
| protection class IP | IP20 |
| ● during operation | -25 ... +60 °C |
| ● during transport | -40 ... +80 °C |
| consumed active power | 0.9 W |
| conducted interference | |
| environmental category | |
| Product Lifecycle (PLM) | PM300:Active Product |
| number of analog inputs | 2 |
| ● at AWG cables solid | 1x (20 ... 14), 2x (20 ... 16) |
| General Product Approval | EMC |
| number of analog outputs | 1 |
| number of digital inputs | 0 |
| Export Control Regulations | AL : N / ECCN : EAR99 |
| ● at AWG cables stranded | 1x (20 ... 12), 2x (20 ... 14) |
| Standard lead time ex-works | 1 Day/Days |
| Surcharge for Raw Materials | None |
| Package size unit of measure | MM |
| Substance Prohibitance (Date) | 05/01/2012 |
| Switching function (EF000189) | - |
| type of connection technology | 2-wire connection |
| A/D resolution at analog output | 12 bit |
| number of semiconductor outputs | 0 |
| A/D resolution at the analog input | 12 bit |
| Number of binary inputs (EF003817) | 0 |
| Type Test Certificates/Test Report | |
| relative humidity during operation | 5 ... 95 % |
| ● between inputs and electronics | No |
| ● between output and electronics | No |
| ● input for thermistor connection | No |
| D/A conversion time at analog output | 25 ms |
| Degree of protection (IP) (EF005474) | IP20 |
| Number of analogue inputs (EF001994) | 2 |
| output load at analog output maximum | 500 Ω |
| surge voltage resistance rated value | 4 000 V |
| ● input for ground fault detection | No |
| Article Number (Market Facing Number) | 3UF7400-1AA00-0 |
| EMC immunity according to IEC 60947-1 | corresponds to degree of severity 3 |
| Number of analogue outputs (EF001995) | 1 |
| Voltage type for actuating (EF008242) | - |
| type of voltage of the output voltage | DC |
| Degree of protection (NEMA) (EF011959) | - |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| A/D conversion time at the analog input | 150 ms |
| Number of electronic outputs (EF006929) | 0 |
| reference code according to IEC 81346-2 | B |
| relative symmetrical measuring accuracy | 1 % |
| ● input for analog temperature sensors | No |
| touch protection against electrical shock | finger-safe |
| ● during storage according to IEC 60721 | 1K6 (no condensation, relative humidity 10 ... 95%), 1C2 (no salt mist), 1S2 (sand must not get into the devices), 1M4 |
| Input for earth fault detection (EF007115) | false |
| Input for thermistor connection (EF007116) | false |
| Number of outputs, with contact (EF006936) | 0 |
| measuring range of current parameterizable | 0/4 mA ... 20 mA |
| property of the output short-circuit proof | Yes |
| tightening torque with screw-type terminals | 0.8 ... 1.2 N·m |
| ● due to burst according to IEC 61000-4-4 | 1 kV |
| ● during operation according to IEC 60721 | 3K6 (no formation of ice, no condensation, relative humidity 10 ... 95%), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6 |
| ● during transport according to IEC 60721 | 2K2, 2C1, 2S1, 2M2 |
| shock resistance according to IEC 60068-2-27 | 15g / 11 ms |
| type of connectable conductor cross-sections | |
| ● finely stranded with core end processing | 1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²) |
| value range of output current parameterizable | 0/4 mA ... 20 mA |
| relative symmetrical accuracy of output signal | 1 % |
| installation altitude at height above sea level | |
| vibration resistance according to IEC 60068-2-6 | 1 ... 6 Hz: 15 mm, 6 ... 500 Hz: 2g |
| Input for analogue temperature sensor (EF007114) | false |
| Rated control supply voltage Us at DC (EF003980) | ['-', '-'] |
| EMC emitted interference according to IEC 60947-1 | class A |
| field-based interference according to IEC 61000-4-3 | 10 V/m |
| Region Specific PriceGroup / Headquarter Price Group | 42J / 42J |
| Rated control supply voltage Us at AC 50HZ (EF003978) | - |
| Rated control supply voltage Us at AC 60HZ (EF003979) | - |
| tightening torque [lbf·in] with screw-type terminals | 7 ... 10.3 lbf·in |
| input current as destruction limit maximum permissible | 40 mA |
| number of outputs as contact-affected switching element | 0 |
| ● due to conductor-earth surge according to IEC 61000-4-5 | 2 kV |
| diagnostics function at the analog input open-circuit detection | Yes |
| ● due to conductor-conductor surge according to IEC 61000-4-5 | 1 kV |
| Compliance with the substance restrictions according to RoHS directive | Since: 01.05.2012 |
| REACH Art. 33 Duty to inform according to the current list of candidates | Lead titanium zircon... CAS-No. 12626-81-2 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):Lead titanium zirconium oxideBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.Lead CAS-No. 7439-92-1 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):LeadBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.Lead monoxide (lead ... CAS-No. 1317-36-8 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):Lead monoxide (lead oxide)Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.2-methyl-1-(4-methyl... CAS-No. 71868-10-5 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):2-methyl-1-(4-methylthiophenyl)-2-morpholinopropan-1-oneBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. |
| Type of electrical connection for auxiliary- and control current circuit (EF006979) | Screw connection |
| General Product ApprovalEMCDeclaration of ConformityConfirmationTest CertificatesMarine / ShippingotherType Test Certificates/Test ReportConfirmation | General Product Approval |
Technical specifications and performance data
Installation and operation guide