| Parameter | Value |
|---|---|
| EAN | 4011209780828 |
| UPC | 040892789867 |
| ETIM | 5 |
| IDEA | 4 |
| depth | 124 mm |
| width | 45 mm |
| UNSPSC | 14 |
| eClass | 6 |
| height | 106 mm |
| ● top | 40 mm |
| category | |
| ● left | 0 mm |
| ● right | 0 mm |
| ● solid | 1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²) |
| Group Code | R711 |
| safe state | Safety outputs switched off |
| ● bottom | 40 mm |
| ● at 24 V | 3 A |
| ● at 60 V | 0.55 A |
| ● maximum | 100 ms |
| ● typical | 50 ms |
| Date5/6/2022 | Subject to change without notice© Copyright Siemens 2022 |
| Metal Factor | None |
| ● at 120 V | 3 A |
| ● at 125 V | 0.22 A |
| ● at 240 V | 1.5 A |
| ● at 250 V | 0.11 A |
| Product Group | 5836 |
| Product class | A: Standard product which is a stock item could be returned within the returns guidelines/period. |
| Quantity Unit | 1 Piece |
| ● 1 maximum | 2 000 m |
| ● 2 maximum | 3 000 m; max. +50 °C (no protective separation) |
| ● 2-channel | 1 |
| ● 3 maximum | 4 000 m; max. +40 °C (no protective separation) |
| Commodity Code | 85389091 |
| Product family | SIMOCODE pro 3UF7 motor management and control devices |
| last modified: | 4/8/2022 |
| pulse duration | |
| Net Weight (kg) | 0,360 Kg |
| design of input | |
| ● rated value | 24 V |
| ● start input | Yes |
| Model (EF000010) | Digital module |
| fastening method | screw and snap-on mounting |
| number of inputs | 5 |
| product function | |
| required spacing | |
| ● relay output | Yes |
| Country of origin | Germany |
| Marine / Shipping | other |
| mounting position | any |
| number of outputs | 2 |
| product component | |
| ● at DC maximum | 100 ms |
| ● digital input | Yes |
| ● initial value | 0.8 |
| ● safety switch | Yes |
| LKZ_FDB/ CatalogID | CC-IC10 |
| Packaging Quantity | 1 |
| failure rate [FIT] | |
| product brand name | SIRIUS |
| switching behavior | monostable |
| ● during storage | -40 ... +80 °C |
| ● feedback input | Yes |
| Packaging Dimension | 52,50 x 133,00 x 133,00 |
| Product Description | Fail-safe digital module DM-F local, for fail-safe shutdown via hardware signal Us: 24 V DC 2 relay enabling circuits, 2 relay outputs, safety function can be set via DIP switch, maximum achievable SIL IEC 61508: 3, maximum achievable PL ISO 13849-1: E |
| ambient temperature | |
| contact reliability | 0.1 million operating cycles (AC15, 230 V, 2 A) |
| inrush current peak | |
| product designation | Fail-safe digital module |
| protection class IP | IP20 |
| suitability for use | |
| ● automatic start | Yes |
| ● during operation | -25 ... +60 °C |
| ● during transport | -40 ... +80 °C |
| ● full-scale value | 1.2 |
| ● valve monitoring | No |
| consumed active power | 3 W |
| design of the product | for emergency off and safety doors |
| digital input version | |
| conducted interference | |
| environmental category | |
| performance level (PL) | |
| ● monitored start-up | Yes |
| Product Lifecycle (PLM) | PM300:Active Product |
| number of analog inputs | 0 |
| number of sensor inputs | |
| ● at AWG cables solid | 1x (20 ... 12), 2x (20 ... 14) |
| General Product Approval | EMC |
| hardware fault tolerance | |
| number of analog outputs | 0 |
| number of digital inputs | 0 |
| product type designation | DM-FL |
| Export Control Regulations | AL : N / ECCN : N |
| ● 1-channel or 2-channel | 1 |
| ● EMERGENCY OFF function | Yes |
| ● at AWG cables stranded | 1x (20 ... 14), 2x (20 ... 16) |
| ● light array monitoring | Yes |
| ● parameterizable inputs | Yes |
| PFDavg with low demand rate | |
| SIL Claim Limit (subsystem) | |
| Standard lead time ex-works | 1 Day/Days |
| Surcharge for Raw Materials | None |
| operating frequency maximum | 360 1/h |
| ● parameterizable outputs | Yes |
| ● safety-related circuits | Yes |
| Package size unit of measure | MM |
| Safety Integrity Level (SIL) | |
| control supply voltage at DC | |
| type of input characteristic | Type 2 in accordance with EN 61131-2 |
| ● light barrier monitoring | Yes |
| ● type 1 acc. to IEC 61131 | No |
| ● type 2 acc. to IEC 61131 | Yes |
| Substance Prohibitance (Date) | 05/01/2012 |
| Switching function (EF000189) | Mono stable |
| ● at two-channel evaluation | 99 % |
| ● tactile sensor monitoring | No |
| For use in hazardous locations | Functional Safety/Safety of Machinery |
| make time with automatic start | |
| ● position switch monitoring | Yes |
| ● protective door monitoring | Yes |
| duration of inrush current peak | |
| number of semiconductor outputs | 0 |
| ● after power failure maximum | 8 200 ms |
| ● after power failure typical | 8 000 ms |
| ● of the sensor input minimum | 30 ms |
| ● proximity switch monitoring | No |
| ● at single-channel evaluation | 90 % |
| Number of binary inputs (EF003817) | 0 |
| design of the electrical isolation | Protective separation in accordance with IEC 60947-1 for all circuits, up to installation altitude of 2000 m |
| relative humidity during operation | 5 ... 95 % |
| ● of the cascading input minimum | 0.2 s |
| product feature cross-circuit-proof | Yes |
| ● input for thermistor connection | No |
| Degree of protection (IP) (EF005474) | IP20 |
| Number of analogue inputs (EF001994) | 0 |
| surge voltage resistance rated value | 4 000 V |
| ● EMERGENCY-OFF circuit monitoring | Yes |
| ● input for ground fault detection | No |
| Article Number (Market Facing Number) | 3UF7320-1AB00-0 |
| EMC immunity according to IEC 60947-1 | corresponds to degree of severity 3 |
| Number of analogue outputs (EF001995) | 0 |
| Voltage type for actuating (EF008242) | DC |
| stop category according to EN 60204-1 | 0 |
| ● pressure-sensitive mat monitoring | Yes |
| ● with a common reference potential | 4 |
| Degree of protection (NEMA) (EF011959) | - |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| ● of the ON pushbutton input minimum | 0.2 s |
| Number of electronic outputs (EF006929) | - |
| reference code according to IEC 81346-2 | F |
| wire length for digital signals maximum | 1 500 m |
| ● cascading input/functional switching | Yes |
| ● input for analog temperature sensors | No |
| average diagnostic coverage level (DCavg) | |
| property of contacts of the relay outputs | Fail-safe NO contacts |
| touch protection against electrical shock | finger-safe |
| ● as contact-affected switching element | 2 |
| ● during storage according to IEC 60721 | 1K6 (no condensation, relative humidity 10 ... 95%), 1C2 (no salt mist), 1S2 (sand must not get into the devices), 1M4 |
| Input for earth fault detection (EF007115) | false |
| Input for thermistor connection (EF007116) | false |
| Number of outputs, with contact (EF006936) | 2 |
| input version with safety-related function | 2 sensor inputs 24 V DC, 1 start signal input 24 V DC, 1 cascading input 24 V DC, 1 feedback circuit input 24 V DC |
| safety device type according to IEC 61508-2 | Type B |
| tightening torque with screw-type terminals | 0.8 ... 1.2 N·m |
| ● due to burst according to IEC 61000-4-4 | 2 kV network connection / 1 kV control connection |
| ● during operation according to IEC 60721 | 3K6 (no formation of ice, no condensation, relative humidity 10 ... 95%), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6 |
| ● during transport according to IEC 60721 | 2K2, 2C1, 2S1, 2M2 |
| ● magnetically operated switch monitoring | Yes |
| buffering time in the event of power failure | 60 ms |
| shock resistance according to IEC 60068-2-27 | 15g / 11 ms |
| type of connectable conductor cross-sections | |
| ● finely stranded with core end processing | 1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²) |
| type of voltage of the control supply voltage | DC |
| electrical endurance (switching cycles) typical | 100 000 |
| installation altitude at height above sea level | |
| type of the safety-related wiring of the inputs | single-channel and two-channel |
| vibration resistance according to IEC 60068-2-6 | 1 ... 6 Hz: 15 mm, 6 ... 500 Hz: 2g |
| Input for analogue temperature sensor (EF007114) | false |
| Rated control supply voltage Us at DC (EF003980) | ['24', '24'] |
| ● opto-electronic protection device monitoring | Yes |
| EMC emitted interference according to IEC 60947-1 | class A |
| ● magnetically operated switch monitoring NC-NC | Yes |
| ● magnetically operated switch monitoring NC-NO | Yes |
| backslide delay time in the event of power failure | |
| electrostatic discharge according to IEC 61000-4-2 | 6 kV contact discharge / 8 kV air discharge |
| mechanical service life (switching cycles) typical | 10 000 000 |
| field-based interference according to IEC 61000-4-3 | 10 V/m |
| Region Specific PriceGroup / Headquarter Price Group | 42J / 42J |
| contact rating of auxiliary contacts according to UL | B300 / R300 |
| ● at two-channel evaluation according to IEC 61508 | 3 |
| ● at two-channel evaluation according to IEC 62061 | 3 |
| Rated control supply voltage Us at AC 50HZ (EF003978) | - |
| Rated control supply voltage Us at AC 60HZ (EF003979) | - |
| tightening torque [lbf·in] with screw-type terminals | 7 ... 10.3 lbf·in |
| ● at rate of recognizable hazardous failures (λdd) | 867.96 FIT |
| ● at single-channel evaluation according to IEC 61508 | 1 |
| ● at single-channel evaluation according to IEC 62061 | 1 |
| conducted HF interference emissions according to CISPR11 | corresponds to degree of severity A |
| field-bound HF interference emission according to CISPR11 | corresponds to degree of severity A |
| ● at rate of non-recognizable hazardous failures (λdu) | 7.06 FIT |
| ● at two-channel evaluation according to EN ISO 13849-1 | e |
| diagnostics test interval by internal test function maximum | 28 800 s |
| ● due to conductor-earth surge according to IEC 61000-4-5 | 1 kV |
| ● at single-channel evaluation according to EN ISO 13849-1 | d |
| (electrically) protective separation according to IEC 60947-1 | All circuits in SIMOCODE pro are with protective separation, i.e. they are designed with doubled creepage paths and clearances. NOTICE: The information in the "Protective Separation" test report, No. 2668, must be observed. |
| switching capacity current of relay enabling circuits at AC-15 | |
| switching capacity current of relay enabling circuits at DC-13 | |
| ● due to high-frequency radiation according to IEC 61000-4-6 | 10 V |
| insulation voltage with degree of pollution 3 at AC rated value | 300 V |
| operating range factor control supply voltage rated value at DC | |
| ● due to conductor-conductor surge according to IEC 61000-4-5 | 0.5 kV |
| backslide delay time after opening of the safety circuits typical | 50 ms |
| certificate of suitability according to ATEX directive 2014/34/EU | BVS 06 ATEX F001 |
| Compliance with the substance restrictions according to RoHS directive | Since: 01.05.2012 |
| product component removable terminal for auxiliary and control circuit | Yes |
| REACH Art. 33 Duty to inform according to the current list of candidates | Lead titanium zircon... CAS-No. 12626-81-2 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):Lead titanium zirconium oxideBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.Lead CAS-No. 7439-92-1 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):LeadBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.Lead monoxide (lead ... CAS-No. 1317-36-8 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):Lead monoxide (lead oxide)Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. |
| explosion device group and category according to ATEX directive 2014/34/EU | II (2) G, II (2 ) D, I (M2) |
| switching capacity current of the NO contacts of the relay outputs at AC-15 | |
| switching capacity current of the NO contacts of the relay outputs at DC-13 | |
| Type of electrical connection for auxiliary- and control current circuit (EF006979) | Screw connection |
| design of the fuse link for short-circuit protection of relay enabling circuits required | gL/gG: 4 A |
| ● as contact-affected switching element as NO contact safety-related instantaneous contact | 2 |
| General Product ApprovalEMCConfirmationFor use in hazardous locationsFunctional Safety/Safety of MachineryDeclaration of ConformityTest CertificatesMarine / ShippingType Examination CertificateType Test Certificates/Test ReportMarine / ShippingotherConfirmation | General Product Approval |
Technical specifications and performance data
Installation and operation guide