| Parameter | Value |
|---|---|
| ● at DC | 0.85 ... 1.1 |
| ● solid | 1x (0.2 ... 2.5 mm²) |
| — at 24 V | 10 A |
| ● maximum | 7 000 ms |
| ● typical | 60 ms |
| — at 115 V | 1 A |
| — at 230 V | 0.3 A |
| — at AC-15 | |
| — at DC-13 | |
| ● stranded | 1x (24 ... 18) |
| Pulse duration | |
| ● UL approval | Yes |
| Shock resistance | 5g / 11 ms |
| Mounting position | any |
| ● at DC maximum | 100 ms |
| ● safety switch | Yes |
| product brand name | SIRIUS |
| ● during storage | -40 ... +80 °C |
| Ambient temperature | |
| Suitability for use | |
| ● finely stranded | |
| ● during operation | -25 ... +60 °C |
| ● valve monitoring | No |
| ● acc. to IEC 61508 | SIL3 |
| ● at DC rated value | 24 V |
| Performance level (PL) | |
| ● BG BIA certificate | Yes |
| Number of sensor inputs | |
| Control supply voltage 1 | |
| EMC emitted interference | IEC 60947-5-1, IEC 60000-4-3, IEC 60000-4-5, IEC 60000-4-6 |
| General Product Approval | EMC |
| Certificate of suitability | UL, CSA, EN 60204-1, EN ISO 12100, EN 954-1, IEC 61508 |
| Switching capacity current | |
| ● 1-channel or 2-channel | 1 |
| ● acc. to EN ISO 13849-1 | e |
| Baumusterprüfbescheinigung | |
| Operating frequency maximum | 1 000 1/h |
| ● safety-related circuits | Yes |
| Safety Integrity Level (SIL) | |
| Air pressure acc. to SN 31205 | 90 ... 106 kPa |
| Type of electrical connection | spring-loaded terminals |
| ● tactile sensor monitoring | Yes |
| Insulation voltage rated value | 690 V |
| Make time with automatic start | |
| Make time with monitored start | |
| ● position switch monitoring | Yes |
| Category acc. to EN ISO 13849-1 | 4 |
| — without core end processing | 1x (0.25 ... 1.5 mm²) |
| ● of the sensor input minimum | 45 ms |
| DC resistance of the cable maximum | 500 Ω |
| Relative humidity during operation | 10 ... 95 % |
| ● Monitoring of floating sensors | Yes |
| ● of the cascading input minimum | 0.045 s |
| Protection against electrical shock | finger-safe |
| Protection class IP of the terminal | IP20 |
| Protection class IP of the enclosure | IP20 |
| Stop category acc. to DIN EN 60204-1 | 0 |
| Surge voltage resistance rated value | 6 000 V |
| ● EMERGENCY-OFF circuit monitoring | Yes |
| Functional Safety/Safety of Machinery | Declaration of Conformity |
| Safety device type acc. to IEC 61508-2 | Type B |
| ● Monitoring of non-floating sensors | Yes |
| ● of the ON pushbutton input minimum | 0.2 s |
| Contact reliability of auxiliary contacts | < 1 error per 100 million operating cycles |
| Recovery time after power failure typical | 7 000 ms |
| Hardware fault tolerance acc. to IEC 61508 | 1 |
| Vibration resistance acc. to IEC 60068-2-6 | 5 ... 500 Hz: 0,075 mm |
| PFHD with high demand rate acc. to EN 62061 | 0.000000011 1/h |
| ● magnetically operated switch monitoring | No |
| ● of the NC contacts of the relay outputs | |
| ● of the NO contacts of the relay outputs | |
| Type of connectable conductor cross-sections | |
| Type of voltage of the control supply voltage | DC |
| Backslide delay time in the event of power failure | |
| Make time with automatic start after power failure | |
| Mechanical service life (switching cycles) typical | 30 000 000 |
| ● TÜV (German technical inspectorate) certificate | Yes |
| Installation altitude at height above sea level maximum | 2 000 m |
| Recovery time after opening of the safety circuits typical | 500 ms |
| Type of connectable conductor cross-sections at AWG conductors | |
| Backslide delay time after opening of the safety circuits typical | 50 ms |
| T1 value for proof test interval or service life acc. to IEC 61508 | 20 y |
| Operating range factor control supply voltage rated value of magnet coil | |
| Wire length between sensor and electronic evaluation device with Cu 1.5 mm² and 150 nF/km maximum | 2 000 m |
| Design of the fuse link for short-circuit protection of the NO contacts of the relay outputs required | gL/gG: 10 A |
| maximum permissible voltage for safe isolation between electronic evaluation device and enabling circuit acc. to EN 60947-1 | 400 V |
| General Product ApprovalEMCFunctional Safety/Safety of MachineryDeclaration of ConformityTest CertificatesotherBaumusterprüfbescheinigungspezielle PrüfbescheinigungenUmweltbestätigungBestätigungen | General Product Approval |
Technical specifications and performance data
Installation and operation guide