| Parameter | Value |
|---|---|
| EAN | 4011209717398 |
| UPC | 754554946399 |
| ETIM | 5 |
| IDEA | 4 |
| depth | 120 mm |
| width | 45 mm |
| UNSPSC | 14 |
| eClass | 6 |
| height | 138.5 mm |
| ● at DC | 0.9 ... 1.2 |
| ● solid | 2x (0.25 ... 1.5 mm²) |
| Group Code | R711 |
| — at 24 V | 2 A |
| ● maximum | 690 V |
| Date5/9/2022 | Subject to change without notice© Copyright Siemens 2022 |
| Metal Factor | LAO----- |
| — at 115 V | 3 A |
| — at 230 V | 3 A |
| ● stranded | 2x (20 ... 16) |
| Product Group | 5837 |
| Product class | A: Standard product which is a stock item could be returned within the returns guidelines/period. |
| Quantity Unit | 1 Piece |
| Commodity Code | 85364190 |
| Product family | With special functions |
| last modified: | 4/1/2022 |
| Net Weight (kg) | 0,386 Kg |
| design of input | |
| ● UL approval | Yes |
| ● start input | No |
| Depth (EF000049) | 120.0 |
| Model (EF000010) | Other |
| Width (EF000008) | 45.0 |
| fastening method | screw and snap-on mounting |
| product function | |
| shock resistance | 8g / 10 ms |
| Country of origin | Germany |
| Height (EF000040) | 138.5 |
| Test Certificates | other |
| mounting position | any |
| ● as NC contact | |
| ● as NO contact | |
| ● safety switch | Yes |
| LKZ_FDB/ CatalogID | CC-IC10 |
| Packaging Quantity | 1 |
| product brand name | SIRIUS |
| ● during storage | -40 ... +75 °C |
| ● feedback input | Yes |
| ● safety-related | |
| Packaging Dimension | 112,00 x 127,00 x 55,00 |
| Product Description | SIRIUS safety relay safety-oriented Standstill monitoring 24 V DC, 45 mm Spring-type terminal EC instantaneous: 3 NO + 1 NC EC delayed: 0 SC: 3 Auto-start Basic unit max. error category EN 954-1: 4 Maximum achievable PL according to EN 13849-1: Maximum achievable SIL according to IEC 61508: 3 |
| adjustable downtime | 0.2 ... 6 s |
| ambient temperature | |
| product designation | Standstill monitor |
| suitability for use | |
| ● BG BIA approval | Yes |
| ● automatic start | No |
| ● finely stranded | |
| ● during operation | -25 ... +60 °C |
| ● valve monitoring | No |
| design of the product | for safe stoppage monitoring |
| — delayed switching | 0 |
| ● at DC rated value | 24 V |
| performance level (PL) | |
| ● monitored start-up | No |
| Product Lifecycle (PLM) | PM300:Active Product |
| design of the cascading | none |
| number of sensor inputs | |
| EMC emitted interference | IEC 61000-6-2, IEC 61000-6-3 |
| General Product Approval | Functional Safety/Safety of Machinery |
| Release-delay (EF001129) | ['0.2', '6.0'] |
| Special Test Certificate | Confirmation |
| control supply voltage 1 | |
| — instantaneous contact | 0 |
| ● standstill monitoring | Yes |
| Export Control Regulations | AL : N / ECCN : N |
| certificate of suitability | UL, CSA, EN 60204-1, EN ISO 12100, EN 954-1, IEC 61508 |
| switching capacity current | |
| ● 1-channel or 2-channel | 1 |
| ● EMERGENCY OFF function | No |
| ● according to IEC 61508 | 3 |
| ● according to IEC 62061 | 3 |
| ● for signaling function | |
| ● light array monitoring | No |
| Standard lead time ex-works | 5 Day/Days |
| Surcharge for Raw Materials | None |
| With start input (EF003342) | false |
| operating frequency maximum | 1 200 1/h |
| ● according to UL maximum | 600 V |
| ● safety-related circuits | Yes |
| Evaluation inputs (EF008245) | Other |
| Package size unit of measure | MM |
| Safety Integrity Level (SIL) | |
| — with core end processing | 2 x (0.25 ... 1.5 mm²) |
| ● according to ISO 13849-1 | e |
| ● laser scanner monitoring | No |
| ● light barrier monitoring | No |
| ● of semiconductor outputs | |
| type of electrical connection | spring-loaded terminals |
| ● rotation speed monitoring | No |
| ● tactile sensor monitoring | No |
| insulation voltage rated value | 690 V |
| ● position switch monitoring | No |
| ● protective door monitoring | No |
| With muting function (EF004057) | false |
| — without core end processing | 2x (0.25 ... 1.5 mm²) |
| With feedback circuit (EF003343) | true |
| Rail mounting possible (EF003972) | FALSE |
| With approval for TÜV (EF004144) | true |
| With detachable clamps (EF003340) | true |
| air pressure according to SN 31205 | 90 ... 106 kPa |
| relative humidity during operation | 10 ... 95 % |
| With approval for BG BIA (EF004145) | true |
| product feature cross-circuit-proof | No |
| protection class IP of the terminal | IP20 |
| category according to EN ISO 13849-1 | 4 |
| protection class IP of the enclosure | IP20 |
| surge voltage resistance rated value | 6 000 V |
| — safety-related delayed switching | 0 |
| ● EMERGENCY-OFF circuit monitoring | No |
| Article Number (Market Facing Number) | 3TK2810-0BA02 |
| SIL according to IEC 61508 (EF009889) | 3 |
| Voltage type for actuating (EF008242) | DC |
| stop category according to EN 60204-1 | 0 |
| ● pressure-sensitive mat monitoring | No |
| Type of electric connection (EF003961) | Other |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| installation environment regarding EMC | This product is suitable for Class A environments only. In household environments, this device can cause unwanted radio interference. The user is required to implement appropriate measures in this case. |
| reference code according to EN 61346-2 | F |
| With approval according to UL (EF001783) | true |
| — safety-related instantaneous contact | 4 |
| ● cascading input/functional switching | No |
| Category according to EN 954-1 (EF006782) | 4 |
| suitability for interaction press control | No |
| touch protection against electrical shock | finger-safe |
| input resistance at the measurement inputs | 500 kΩ |
| safety device type according to IEC 61508-2 | Type B |
| — for signaling function at DC-13 at 24 V | 0.1 A |
| ● magnetically operated switch monitoring | No |
| Suitable for monitoring of valves (EF007272) | false |
| type of connectable conductor cross-sections | |
| type of electrical connection plug-in socket | Yes |
| type of voltage of the control supply voltage | DC |
| Stop category according to IEC 60204 (EF007498) | 0 |
| electrical endurance (switching cycles) typical | 200 000 |
| hardware fault tolerance according to IEC 61508 | 1 |
| type of the safety-related wiring of the inputs | measuring inputs |
| vibration resistance according to IEC 60068-2-6 | 10 ... 55 Hz: 0.35 mm |
| PFHD with high demand rate according to EN 62061 | 0.0000000015 1/h |
| Rated control supply voltage Us at DC (EF003980) | ['-', '24'] |
| — for signaling function instantaneous contact | 2 |
| SIL Claim Limit (subsystem) according to EN 62061 | 3 |
| ● magnetically operated switch monitoring NC-NC | No |
| ● magnetically operated switch monitoring NC-NO | No |
| Type of safety according to IEC 61496-1 (EF004105) | - |
| mechanical service life (switching cycles) typical | 50 000 000 |
| Region Specific PriceGroup / Headquarter Price Group | 41L / 41L |
| ● TÜV (German technical inspectorate) certificate | Yes |
| ● of the NC contacts of the relay outputs at AC-15 | |
| ● of the NC contacts of the relay outputs at DC-13 | |
| ● of the NO contacts of the relay outputs at AC-15 | |
| ● of the NO contacts of the relay outputs at DC-13 | |
| Rated control supply voltage Us at AC 50HZ (EF003978) | ['-', '-'] |
| Rated control supply voltage Us at AC 60HZ (EF003979) | ['-', '-'] |
| Suitable for monitoring of tactile sensors (EF007271) | false |
| ● for delayed release circuit according to IEC 61508 | SIL3 |
| Suitable for monitoring of magnetic switches (EF007266) | false |
| Suitable for monitoring of position switches (EF007270) | false |
| installation altitude at height above sea level maximum | 2 000 m |
| number of outputs as contact-affected switching element | |
| voltage measuring range at the measurement inputs at AC | |
| Performance level according to EN ISO 13849-1 (EF007399) | Level e |
| Suitable for monitoring of proximity switches (EF007267) | false |
| adjustable response value voltage for standstill detection | 20 ... 400 mV |
| type of connectable conductor cross-sections at AWG cables | |
| Suitable for monitoring of emergency-stop circuits (EF007268) | false |
| thermal current of the switching element with contacts maximum | 5 A |
| number of outputs as contact-less semiconductor switching element | |
| Number of outputs, safety related, delayed, with contact (EF003345) | - |
| Number of outputs, safety related, delayed, semiconductors (EF003347) | 0 |
| Number of outputs, safety related, undelayed, with contact (EF003344) | - |
| Compliance with the substance restrictions according to RoHS directive | Since: 01.05.2012 |
| Number of outputs, safety related, undelayed, semiconductors (EF003346) | 0 |
| T1 value for proof test interval or service life according to IEC 61508 | 20 y |
| Number of outputs, signalling function, delayed, with contact (EF003349) | - |
| REACH Art. 33 Duty to inform according to the current list of candidates | Reach InformationThere is currently no information on SVHC (Substances of Very High Concern http://echa.europa.eu/web/guest/candidate-list-table) from the supply chain and our established procedures for screening our products for Substances of Very High Concern.We compare our products regularly with the information of the upstream users with regard to the substances indicated in the candidate list in accordance with the requirements of the REACH regulation. As soon as we have new findings, our information will be updated accordingly. |
| operating range factor control supply voltage rated value of magnet coil | |
| Suitable for monitoring of optoelectronic protection equipment (EF007269) | false |
| Number of outputs, signalling function, delayed, semiconductors (EF003351) | 0 |
| Number of outputs, signalling function, undelayed, with contact (EF003348) | - |
| Number of outputs, signalling function, undelayed, semiconductors (EF003350) | 2 |
| Average probability of failure on demand (PFDavg) with low demand rate acc. to IEC 61508 | 0.002 1/y |
| reference code according to DIN 40719 extended according to IEC 204-2 according to IEC 750 | KT |
| design of the fuse link for short-circuit protection of the NO contacts of the relay outputs required | quick: 5 A |
| General Product ApprovalFunctional Safety/Safety of MachineryDeclaration of ConformityType Examination CertificateTest CertificatesotherRailwaySpecial Test CertificateConfirmationConfirmation | General Product Approval |
Technical specifications and performance data
Installation and operation guide