| Parameter | Value |
|---|---|
| Confirmation | |
| EAN | 4047621038223 |
| UPC | 804766690129 |
| ETIM | 5 |
| IDEA | 4 |
| depth | 203 mm |
| width | 210 mm |
| UNSPSC | 15 |
| eClass | 6 |
| height | 393 mm |
| Group Code | R711 |
| trip class | CLASS 10A (default) / 10E / 20E; acc. to IEC 60947-4-2 |
| wire length | |
| ● minimum | 240 A |
| ● upwards | 100 mm |
| Metal Factor | LAO----- |
| ● PROFIBUS | Yes |
| ● forwards | 10 mm |
| Date5/12/2022 | Subject to change without notice© Copyright Siemens 2022 |
| Product Group | 4981 |
| Product class | C: products manufactured / produced to order, which cannot be reused or re-utilised or be returned against credit. |
| Quantity Unit | 1 Piece |
| ● backwards | 0 mm |
| ● downwards | 75 mm |
| Commodity Code | 85371098 |
| Product family | 3RW52 soft starters |
| last modified: | 4/10/2022 |
| service factor | 1 |
| ● CE marking | Yes |
| ● Modbus RTU | Yes |
| ● Modbus TCP | Yes |
| ● auto-RESET | Yes |
| Net Weight (kg) | 12,677 Kg |
| ● EtherNet/IP | Yes |
| ● PROFIenergy | Yes; in connection with the PROFINET Standard communication module |
| ● Soft Torque | Yes |
| ● UL approval | Yes |
| ● at the side | 5 mm |
| ● of the fuse | |
| ● rated value | 200 ... 480 V |
| fastening method | screw fixing |
| minimum load [%] | 15 %; Relative to smallest settable Ie |
| product category | Hybrid switching devices |
| product function | |
| shock resistance | 15 g / 11 ms, from 12 g / 11 ms with potential contact lifting |
| ● CSA approval | Yes |
| ● manual RESET | Yes |
| ● remote reset | Yes; By turning off the control supply voltage |
| Country of origin | Czech Republic |
| Marine / Shipping | other |
| mounting position | with vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back |
| operating voltage | |
| product component | |
| tightening torque | |
| ● analog output | No |
| ● error logbook | Yes; Only in conjunction with special accessories |
| LKZ_FDB/ CatalogID | CC-IC10 |
| Packaging Quantity | 1 |
| product brand name | SIRIUS |
| ● pump ramp down | Yes |
| ● torque control | No |
| Function (EF000030) | Single direction |
| Packaging Dimension | 328,00 x 500,00 x 328,00 |
| Product Description | SIRIUS soft starter 200-480 V 570 A, 24 V AC/DC spring-type terminals Thermistor input |
| ambient temperature | |
| degree of pollution | 3, acc. to IEC 60947-4-2 |
| operational current | |
| product designation | Soft starter |
| ● firmware update | Yes |
| starting voltage [%] | 30 ... 100 % |
| stopping voltage [%] | 50 %; non-adjustable |
| vibration resistance | 15 mm to 6 Hz; 2g to 500 Hz |
| ● HMI-High Feature | No |
| ● during operation | -25 ... +60 °C; Please observe derating at temperatures of 40 °C or above |
| ● PROFINET standard | Yes |
| ● at DC rated value | 24 V |
| control supply voltage | |
| digital output version | 2 normally-open contacts (NO) / 1 changeover contact (CO) |
| environmental category | |
| Product Lifecycle (PLM) | PM300:Active Product |
| With display (EF000458) | - |
| ● for control circuit | 100 ms |
| ● not parameterizable | 2 |
| EMC emitted interference | acc. to IEC 60947-4-2: Class A |
| General Product Approval | EMC |
| Release class (EF006668) | Adjustable |
| adjustable motor current | |
| number of analog outputs | 0 |
| number of digital inputs | 1 |
| product type designation | 3RW52 |
| weight without packaging | 10.6 kg |
| ● at 50 Hz rated value | 24 V |
| ● at 60 Hz rated value | 24 V |
| ● inside-delta circuit | Yes |
| Declaration of Conformity | Test Certificates |
| Torque control (EF009215) | false |
| number of digital outputs | 3 |
| ● at 40 °C rated value | 570 A |
| ● at 50 °C rated value | 504 A |
| ● at 60 °C rated value | 460 A |
| ● ramp-down (soft stop) | Yes |
| Export Control Regulations | AL : N / ECCN : N |
| Internal bypass (EF009214) | true |
| certificate of suitability | |
| ● communication function | Yes |
| Standard lead time ex-works | 100 Day/Days |
| Surcharge for Raw Materials | None |
| impulse voltage rated value | 6 kV |
| number of controlled phases | 3 |
| tightening torque [lbf·in] | |
| ● at 40 °C after startup | 183 W |
| ● at 50 °C after startup | 163 W |
| ● at 60 °C after startup | 153 W |
| ● ramp-up (soft starting) | Yes |
| Package size unit of measure | MM |
| UK Declaration of Conformity | |
| control supply voltage at AC | |
| ● at 40 °C during startup | 10 241 W |
| ● at 50 °C during startup | 8 500 W |
| ● at 60 °C during startup | 7 663 W |
| ● for main current circuit | 100 ms |
| Substance Prohibitance (Date) | 02/15/2018 |
| electromagnetic compatibility | in accordance with IEC 60947-4-2 |
| manufacturer's article number | |
| type of electrical connection | |
| ● for control circuit solid | 2x (0.25 ... 1.5 mm²) |
| ● is supported HMI-Standard | Yes |
| ● motor overload protection | Yes; Full motor protection (thermistor motor protection and electronic motor overload protection) |
| ● via software configurable | Yes |
| insulation voltage rated value | 600 V |
| width of connection bar maximum | 45 mm |
| ● intrinsic device protection | Yes |
| control supply voltage frequency | 50 ... 60 Hz |
| ● at DC-13 at 24 V rated value | 1 A |
| ● during storage and transport | -40 ... +80 °C |
| ● via software parameterizable | No |
| Operating frequency 1 rated value | 50 Hz |
| Operating frequency 2 rated value | 60 Hz |
| communication module is supported | |
| ● adjustable current limitation | Yes |
| ● at AC-15 at 250 V rated value | 3 A |
| ● is supported HMI-High Feature | Yes |
| ● of standard HMI module usable | 3RW5980-0HS00 |
| operating power for 3-phase motors | |
| start-up ramp time of soft starter | 0 ... 20 s |
| ● at 230 V at 40 °C rated value | 160 kW |
| ● at 400 V at 40 °C rated value | 315 kW |
| ● at inside-delta circuit minimum | 416 A |
| Degree of protection (IP) (EF005474) | IP00 |
| design of the overvoltage protection | Varistor |
| surge voltage resistance rated value | 6 kV |
| ● operating measured value display | Yes; Only in conjunction with special accessories |
| Article Number (Market Facing Number) | 3RW5248-2TC04 |
| Rated operating voltage Ue (EF002418) | ['200', '480'] |
| Voltage type for actuating (EF008242) | AC/DC |
| current limiting value [%] adjustable | 130 ... 700 % |
| wire length for thermistor connection | |
| ● of high feature HMI module usable | 3RW5980-0HF00 |
| ● of the gG fuse usable up to 690 V | 2x3NA3365-6; Type of coordination 1, Iq = 65 kA |
| Degree of protection (NEMA) (EF011959) | - |
| WEEE (2012/19/EU) Take-Back Obligation | Yes |
| ● at 200/208 V at 50 °C rated value | 150 hp |
| ● at 220/230 V at 50 °C rated value | 200 hp |
| ● at 460/480 V at 50 °C rated value | 400 hp |
| ● between main and auxiliary circuit | 600 V |
| ● of circuit breaker usable at 400 V | 3VA2580-6HN32-0AA0; Type of coordination 1, Iq = 65 kA, CLASS 10 |
| ● of circuit breaker usable at 500 V | 3VA2580-6HN32-0AA0; Type of coordination 1, Iq = 65 kA, CLASS 10 |
| operating power [hp] for 3-phase motors | |
| reference code according to IEC 81346-2 | Q |
| ● at inside-delta circuit rated value | 200 ... 480 V |
| ● at the digital inputs at AC maximum | 100 m |
| ● at the digital inputs at DC maximum | 1 000 m |
| ● of communication module Ethernet/IP | 3RW5980-0CE00 |
| blocking voltage of the thyristor maximum | 1 600 V |
| ● during storage according to IEC 60721 | 1K6 (only occasional condensation), 1C2 (no salt mist), 1S2 (sand must not get inside the devices), 1M4 |
| ● between soft starter and motor maximum | 800 m |
| ● removable terminal for control circuit | Yes |
| operational current at inside-delta circuit | |
| required spacing with side-by-side mounting | |
| ● at AWG cables for control circuit solid | 2x (24 ... 16) |
| ● during operation according to IEC 60721 | 3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6 |
| ● during transport according to IEC 60721 | 2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m) |
| ● of communication module PROFIBUS usable | 3RW5980-0CP00 |
| buffering time in the event of power failure | |
| type of connectable conductor cross-sections | |
| type of voltage of the control supply voltage | AC/DC |
| ● evaluation of thermistor motor protection | Yes; Type A PTC or Klixon / Thermoclick |
| ● of communication module Modbus RTU usable | 3RW5980-0CR00 |
| ● of communication module Modbus TCP usable | 3RW5980-0CT00 |
| maximum permissible voltage for safe isolation | |
| Integrated motor overload protection (EF007297) | - |
| holding current in bypass operation rated value | 470 mA |
| switching capacity current of the relay outputs | |
| utilization category according to IEC 60947-4-2 | AC 53a |
| ● for main contacts with screw-type terminals | 14 ... 24 N·m |
| Rated control supply voltage Us at DC (EF003980) | ['24', '-'] |
| power loss [W] at AC at current limitation 350 % | |
| product feature integrated bypass contact system | Yes |
| ● at rotary coding switch on switch position 1 | 240 A |
| ● at rotary coding switch on switch position 2 | 262 A |
| ● at rotary coding switch on switch position 3 | 284 A |
| ● at rotary coding switch on switch position 4 | 306 A |
| ● at rotary coding switch on switch position 5 | 328 A |
| ● at rotary coding switch on switch position 6 | 350 A |
| ● at rotary coding switch on switch position 7 | 372 A |
| ● at rotary coding switch on switch position 8 | 394 A |
| ● at rotary coding switch on switch position 9 | 416 A |
| ● for DIN cable lug for main contacts stranded | 2x (50 ... 240 mm²) |
| ● at rotary coding switch on switch position 10 | 438 A |
| ● at rotary coding switch on switch position 11 | 460 A |
| ● at rotary coding switch on switch position 12 | 482 A |
| ● at rotary coding switch on switch position 13 | 504 A |
| ● at rotary coding switch on switch position 14 | 526 A |
| ● at rotary coding switch on switch position 15 | 548 A |
| ● at rotary coding switch on switch position 16 | 570 A |
| Rated operation current Ie at 40 °C Tu (EF007039) | 570 |
| control supply current in standby mode rated value | 160 mA |
| power loss [W] for rated value of the current at AC | |
| ● with conductor cross-section = 0.5 mm² maximum | 50 m |
| ● with conductor cross-section = 1.5 mm² maximum | 150 m |
| ● with conductor cross-section = 2.5 mm² maximum | 250 m |
| Region Specific PriceGroup / Headquarter Price Group | 42S / 42S |
| contact rating of auxiliary contacts according to UL | R300-B300 |
| relative negative tolerance of the operating voltage | -15 % |
| relative positive tolerance of the operating voltage | 10 % |
| touch protection on the front according to IEC 60529 | finger-safe, for vertical contact from the front with cover |
| ● of communication module PROFINET standard usable | 3RW5980-0CS00 |
| Rated control supply voltage Us at AC 50HZ (EF003978) | ['24', '-'] |
| Rated control supply voltage Us at AC 60HZ (EF003979) | ['24', '-'] |
| design of short-circuit protection for control circuit | 4 A gG fuse (Icu=1 kA), 6 A quick-acting fuse (Icu=1 kA), C1 miniature circuit breaker (Icu= 600 A), C6 miniature circuit breaker (Icu= 300 A); Is not part of scope of supply |
| relative negative tolerance of the operating frequency | -10 % |
| relative positive tolerance of the operating frequency | 10 % |
| installation altitude at height above sea level maximum | 5 000 m; Derating as of 1000 m, see catalog |
| locked-rotor current at close of bypass contact maximum | 7.6 A |
| protection class IP on the front according to IEC 60529 | IP00; IP20 with cover |
| ● for DIN cable lug for main contacts finely stranded | 2x (70 ... 240 mm²) |
| Rated surrounding temperature without derating (EF007074) | 40 °C |
| Rated power three-phase motor, inline, at 230 V (EF007053) | 160.0 |
| Rated power three-phase motor, inline, at 400 V (EF007054) | 315.0 |
| — usable for High Faults up to 575/600 V according to UL | Type: Class J / L, max. 1200 A; Iq = 100 kA |
| ● at 230 V at inside-delta circuit at 40 °C rated value | 315 kW |
| ● at 400 V at inside-delta circuit at 40 °C rated value | 560 kW |
| ● of the gG fuse usable at inside-delta circuit up to 500 V | 2x3NA3365-6; Type of coordination 1, Iq = 65 kA |
| — usable for Standard Faults up to 575/600 V according to UL | Type: Class J / L, max. 1600 A; Iq = 30 kA |
| ● at 200/208 V at inside-delta circuit at 50 °C rated value | 300 hp |
| ● at 220/230 V at inside-delta circuit at 50 °C rated value | 350 hp |
| ● at 460/480 V at inside-delta circuit at 50 °C rated value | 750 hp |
| ● of circuit breaker usable at 400 V at inside-delta circuit | 3VA2510-6HN32-0AA0; Type of coordination 1, Iq = 65 kA, CLASS 10 |
| ● of circuit breaker usable at 500 V at inside-delta circuit | 3VA2510-6HN32-0AA0; Type of coordination 1, Iq = 65 kA, CLASS 10 |
| relative negative tolerance of the control supply voltage at DC | -20 % |
| relative positive tolerance of the control supply voltage at DC | 20 % |
| Rated power three-phase motor, inside delta, at 230 V (EF007055) | 315.0 |
| Rated power three-phase motor, inside delta, at 400 V (EF007056) | 560.0 |
| ● for auxiliary and control contacts with screw-type terminals | 0.8 ... 1.2 N·m |
| ● for control circuit finely stranded with core end processing | 2x (0.25 ... 1.5 mm²) |
| relative negative tolerance of the control supply voltage frequency | -10 % |
| relative positive tolerance of the control supply voltage frequency | 10 % |
| inrush current peak at application of control supply voltage maximum | 3.3 A |
| Compliance with the substance restrictions according to RoHS directive | Since: 15.02.2018 |
| REACH Art. 33 Duty to inform according to the current list of candidates | Lead CAS-No. 7439-92-1 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):LeadBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.Lead monoxide (lead ... CAS-No. 1317-36-8 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):Lead monoxide (lead oxide)Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.Dodecachloropentacyclo[12... > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):Dodecachloropentacyclo[12.2.1.16,9.02,13.05,10]octadeca-7,15-diene (“Dechlorane Plus”™)covering any of its individual anti- and syn-isomers or any combination thereofBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.2-methyl-1-(4-methyl... CAS-No. 71868-10-5 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):2-methyl-1-(4-methylthiophenyl)-2-morpholinopropan-1-oneBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.Dicyclohexyl phthala... CAS-No. 84-61-7 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):Dicyclohexyl phthalate (DCHP)Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.Dibutylbis(pentane-2... CAS-No. 22673-19-4 > 0, 1 % (w / w)Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):Dibutylbis(pentane-2,4-dionato-O,O')tinBased on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation. |
| duration of inrush current peak at application of control supply voltage | 12.1 ms |
| relative negative tolerance of the control supply voltage at AC at 50 Hz | -20 % |
| relative negative tolerance of the control supply voltage at AC at 60 Hz | -20 % |
| relative positive tolerance of the control supply voltage at AC at 50 Hz | 20 % |
| relative positive tolerance of the control supply voltage at AC at 60 Hz | 20 % |
| ● for inside-delta circuit at rotary coding switch on switch position 1 | 416 A |
| ● for inside-delta circuit at rotary coding switch on switch position 2 | 454 A |
| ● for inside-delta circuit at rotary coding switch on switch position 3 | 492 A |
| ● for inside-delta circuit at rotary coding switch on switch position 4 | 530 A |
| ● for inside-delta circuit at rotary coding switch on switch position 5 | 568 A |
| ● for inside-delta circuit at rotary coding switch on switch position 6 | 606 A |
| ● for inside-delta circuit at rotary coding switch on switch position 7 | 644 A |
| ● for inside-delta circuit at rotary coding switch on switch position 8 | 682 A |
| ● for inside-delta circuit at rotary coding switch on switch position 9 | 721 A |
| ● for inside-delta circuit at rotary coding switch on switch position 10 | 759 A |
| ● for inside-delta circuit at rotary coding switch on switch position 11 | 797 A |
| ● for inside-delta circuit at rotary coding switch on switch position 12 | 835 A |
| ● for inside-delta circuit at rotary coding switch on switch position 13 | 873 A |
| ● for inside-delta circuit at rotary coding switch on switch position 14 | 911 A |
| ● for inside-delta circuit at rotary coding switch on switch position 15 | 949 A |
| ● for inside-delta circuit at rotary coding switch on switch position 16 | 987 A |
| ● of back-up R fuse link for semiconductor protection usable up to 690 V | 3NE3340-8; Type of coordination 2, Iq = 65 kA |
| relative negative tolerance of the operating voltage at inside-delta circuit | -15 % |
| relative positive tolerance of the operating voltage at inside-delta circuit | 10 % |
| ● of full range R fuse link for semiconductor protection usable up to 690 V | 3NE1437-2; Type of coordination 2, Iq = 65 kA |
| ● at AWG cables for control circuit finely stranded with core end processing | 2x (24 ... 16) |
| — usable for High Faults at inside-delta circuit up to 575/600 V according to UL | Type: Class J / L, max. 1200 A; Iq = 100 kA |
| — usable for Standard Faults at inside-delta circuit up to 575/600 V according to UL | Type: Class J / L, max. 1600 A; Iq = 30 kA |
| General Product ApprovalEMCConfirmationDeclaration of ConformityTest CertificatesMarine / ShippingUK Declaration of ConformityType Test Certificates/Test ReportMarine / ShippingotherConfirmation | General Product Approval |
Technical specifications and performance data